Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20079S165 + (03:46:38, 15 December 2024)
- ML20079S164 + (03:46:38, 15 December 2024)
- ML20079S154 + (03:46:39, 15 December 2024)
- 05000373/LER-1983-155-03, /03L-0:on 831229,util Informed by Sargent & Lundy That Engineering Change Notice Forthcoming Re Overload Bypass Circuit Design on RHR Min Flow Bypass Valves.Mod Immediately Implemented & Completed on 831230 + (03:46:41, 15 December 2024)
- 05000370/LER-1983-088-03, /03L-0:on 831219,invalid Fire Alarm for Fire Detection Zone Efa 128 Received in Control Room & Alarm Would Not Reset.Caused by Draft from Open Lab Door.Alarm Reset + (03:46:44, 15 December 2024)
- ML20079S144 + (03:46:47, 15 December 2024)
- ML20079S138 + (03:46:47, 15 December 2024)
- ML20079S137 + (03:46:48, 15 December 2024)
- 05000369/LER-1983-115-03, /03L-0:on 831129,annulus Ventilation Train a Unable to Meet Required Vacuum Decay Time & Declared Inoperable.Caused by Poor Sealing on Annulus Doors.Seals Replaced,Shimmed & Adjusted + (03:46:50, 15 December 2024)
- 05000373/LER-1983-156-03, /03L-0:on 831229,during LES-MS-101,MSIV 1B21-FO22A Reactor Protection Limit Switch 4 Setpoint Exceeded Tech Spec Limits.Cause Undetermined.Limit Switch Readjusted + (03:46:52, 15 December 2024)
- ML20079S132 + (03:46:53, 15 December 2024)
- ML20079S131 + (03:46:54, 15 December 2024)
- 05000387/LER-1983-109-03, RCIC Barometric Condenser Condensate Vacuum Pump Tripped During Spray Pond Testing.Caused by Mechanical Failure of Pump Motor Commutator.Condensate Motor Replaced + (03:47:01, 15 December 2024)
- SNRC-2184, Forwards Shoreham Decommissioning Project Termination Survey Final Rept Phase 4. Portions Withheld + (03:47:02, 15 December 2024)
- ML20079S126 + (03:47:02, 15 December 2024)
- ML20079S118 + (03:47:03, 15 December 2024)
- ML20079S111 + (03:47:03, 15 December 2024)
- ML20079S107 + (03:47:04, 15 December 2024)
- ML20079S103 + (03:47:05, 15 December 2024)
- ML20079S100 + (03:47:06, 15 December 2024)
- 05000272/LER-1983-069-03, /03L-0:on 831226,fire Protection Header Pressure Dropped Suddenly Due to Ruptured 4-inch Alarm Valve.Caused by Frozen Water within Valve.New Valve Ordered & Will Be Installed Upon Receipt + (03:47:07, 15 December 2024)
- ML20079S098 + (03:47:08, 15 December 2024)
- 05000272/LER-1983-071-03, /03L-0:on 831222,containment Fan Coil Unit (Cfcu) 14 Removed from Svc to Repair Flexible Connector.Connector Temporarily Repaired.Cfcu Returned to Operable Status + (03:47:10, 15 December 2024)
- ML20079S093 + (03:47:11, 15 December 2024)
- ML20079S091 + (03:47:12, 15 December 2024)
- ML20079S089 + (03:47:12, 15 December 2024)
- ML20079S086 + (03:47:13, 15 December 2024)
- ML20079S084 + (03:47:13, 15 December 2024)
- ML20079S080 + (03:47:14, 15 December 2024)
- ML20079S078 + (03:47:15, 15 December 2024)
- ML20079S075 + (03:47:16, 15 December 2024)
- 05000272/LER-1983-075-03, /03L-0:on 831227,microprocessor Memory Lost for Hydrogen Analyzer Channel 12 & 13.Caused by Voltage Transient on Vital Instrument Bus 2B Making Microprocessor Lose Constants.Constants Reinstalled + (03:47:18, 15 December 2024)
- ML20079S072 + (03:47:19, 15 December 2024)
- ML20079S069 + (03:47:20, 15 December 2024)
- ML20079S050 + (03:47:21, 15 December 2024)
- ML20079S055 + (03:47:21, 15 December 2024)
- 05000272/LER-1983-073-03, /03L-0:on 831223,during Surveillance Testing on Emergency Diesel Generator 1B,jacket Water Cooling Leak from Instrument Line Discovered.Caused by Elbow Cracking Due to Engine Vibration.Design Change Initiated + (03:47:24, 15 December 2024)
- ML20079S047 + (03:47:25, 15 December 2024)
- ML20079S045 + (03:47:25, 15 December 2024)
- ML20079S044 + (03:47:26, 15 December 2024)
- RBG-16-830, Forwards Responses to Geosciences Branch Items Identified During 830621 Meeting & Question 231.15 in 831114 Request for Addl Info.W/One Oversize Figure.Aperture Card Is in PDR + (03:47:27, 15 December 2024)
- ML20079S039 + (03:47:28, 15 December 2024)
- ML20079S033 + (03:47:28, 15 December 2024)
- ML20079S028 + (03:47:29, 15 December 2024)
- ML20079S020 + (03:47:33, 15 December 2024)
- ML20079S018 + (03:47:35, 15 December 2024)
- ML20079S017 + (03:47:36, 15 December 2024)
- ML20079S012 + (03:47:37, 15 December 2024)
- ML20079S006 + (03:47:38, 15 December 2024)
- ML20079S011 + (03:47:38, 15 December 2024)
- ML20079R995 + (03:47:40, 15 December 2024)
- ML20079R988 + (03:47:41, 15 December 2024)