Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000387/LER-1984-029, :on 840703,startup Transformer T-10 Isolated, Causing Trip in Unit 1 & Unit 2 Reactor Protection Sys A. Caused by Lightning Strike on 230-kV Transmission Line.W/ + (14:39:41, 13 December 2024)
- ML20094E921 + (14:39:42, 13 December 2024)
- 05000265/LER-1995-006-07, :on 951004,feed Breaker for Motor Control Ctr at Switchgear Tripped from Current Overlaod.Caused by Trip Setting Too Low for Given Plant.Motor Control Ctr Restored & Exit LCO + (14:39:44, 13 December 2024)
- 05000362/LER-1984-020, :on 840527,8 H Grab Sample Due at 0800 Not Taken Until 0945.Low-range Flow at Sample Conditioning Skid Diverted from Filter a to Filter B,Causing Blown Fuse. Alternate Flow Path Established + (14:39:46, 13 December 2024)
- ML20094E909 + (14:39:47, 13 December 2024)
- ML20094E906 + (14:39:48, 13 December 2024)
- ML20094E904 + (14:39:49, 13 December 2024)
- ML20094E895 + (14:39:49, 13 December 2024)
- 05000285/LER-1984-014, :on 840703,during Weekly Replacement of Iodine Collection Cartridge on RM-060,actuation of Ventilation Isolation Actuation Sys Occurred.No Cause given.RM-060 Will Be Out of Svc During Filter Replacement + (14:39:51, 13 December 2024)
- 05000265/LER-1995-006, Forwards LER 95-006-00 Re Feed Breaker for Motor Control at Switchgear Tripped from Current Overload + (14:39:52, 13 December 2024)
- 05000255/LER-1984-009-01, :on 840704,spurious Left Channel Safety Injection Signal Actuation Occurred.Caused by Inadequate Procedure.Procedure Revised & Personnel Counseled + (14:39:54, 13 December 2024)
- ML20094E873 + (14:39:55, 13 December 2024)
- 05000387/LER-1984-031, :on 840703,HPCI Sys Declared Inoperable for 15 Minutes.Method Used to Seat Check Valve Not Adequate. Procedural Changes Being Evaluated + (14:39:57, 13 December 2024)
- 05000387/LER-1984-030, :on 840627,boron Concentration in Standby Liquid Control Tank Fell to 0.4% Below Tech Spec Limit.Cause Unknown.Tank Level & Concentration Returned to within Limits + (14:39:59, 13 December 2024)
- ML20094E868 + (14:40:00, 13 December 2024)
- 05000388/LER-1984-011-01, :on 840705 & 06,four Spurious Actuations of Standby Gas Treatment Sys & Control Room Emergency Outside Air Supply Sys Experienced.Caused by Malfunctioning Output Breaker.Breaker Replaced + (14:40:02, 13 December 2024)
- BSEP-95-0428, NPDES Noncompliance Notification:On 950817,sewage Treatment Plant Lift Station Overflow Occurred Due to Electrical Failure of Lift Station Pump.Discharge Secured & Area Surrounding Lift Station & Discharge Flow Path Disinfected + (14:40:05, 13 December 2024)
- PY-CEI-NRR-1450, Responds to SALP II Covering Aug 1990 Through Oct 1991, Supplementing Comments Expressed During 920121 Meeting Re Issues Noted in NRC .Corrective Actions Taken Re EOPs & Emergency Instructions + (14:40:05, 13 December 2024)
- BSEP-95-0526, Informs of Noncompliance Notification Submitted to Nc Div of Environ Mgt (Ncdem) on 950822 of Temporary Overflow of Sewage Treatment Plant Lift Station.Ltr to Ncdem Encl + (14:40:06, 13 December 2024)
- ML20094E852 + (14:40:07, 13 December 2024)
- ML20094E763 + (14:40:11, 13 December 2024)
- ML20094E769 + (14:40:11, 13 December 2024)
- ML20094E760 + (14:40:12, 13 December 2024)
- 05000373/LER-1984-042, :on 840703,reactor Water Cleanup Outboard Isolation Valve Room Area Overlooked in Routine Surveys Up to 840703.Posting on Entrance Door 463 Upgraded to Danger High Radiation Area & Security Level Upgraded + (14:40:14, 13 December 2024)
- U-602494, Informs That SALP 14 Period End Date Has Been Rescheduled to End Date of 970329 + (14:40:15, 13 December 2024)
- GO2-95-204, Informs That Ltr Submitted in Accordance W/License Condition 2.F Which Requires Written follow-up Rept within 14 Days of Facility Operation at Reactor Core Power Levels in Excess of Full Power + (14:40:16, 13 December 2024)
- ML20094E736 + (14:40:17, 13 December 2024)
- ML20094E735 + (14:40:18, 13 December 2024)
- ML20094E733 + (14:40:18, 13 December 2024)
- GO2-95-188, Notifies NRC Regional Administrator That Facility Operation at Reactor Core Power Levels in Excess of Full Power + (14:40:19, 13 December 2024)
- ST-HL-AE-5227, Special Rept:On 951022,completed ISI of Unit 2 Sg.Tube Plugs Visually Inspected for Evidence of Leakage.Welded Plugs Installed at Locations + (14:40:19, 13 December 2024)
- ML20094E720 + (14:40:20, 13 December 2024)
- 05000456/LER-1995-012-04, :on 951004,mgt Decisions Lead to Positive Reactivity Events,While Shutdown W/Source Range Nuclear Instrument Inoperable Occurred.Caused by Mgt Deficiency. Subsequent Makeups Performed + (14:40:22, 13 December 2024)
- ML20094E705 + (14:40:23, 13 December 2024)
- ML20094E704 + (14:40:24, 13 December 2024)
- ML20094E692 + (14:40:24, 13 December 2024)
- 3F0192-10, Forwards Rev to Facility Nov 1991 Monthly Operating Rept. Info Re Reactor Rept on 911125 Inadvertently Omitted from Rept Submitted on 911211 + (14:40:29, 13 December 2024)
- ML20094E675 + (14:40:29, 13 December 2024)
- PY-CEI-NRR-1978, Application for Amend to License NPF-58,requesting Rev to TS for Onsite Power Distribution Sys:Ts 3/4.8.3.1, Distribution - Operating + (14:40:30, 13 December 2024)
- ML20094E663 + (14:40:31, 13 December 2024)
- ML20094E654 + (14:40:32, 13 December 2024)
- ML20094E642 + (14:40:32, 13 December 2024)
- ML20094E641 + (14:40:33, 13 December 2024)
- ML20094E624 + (14:40:34, 13 December 2024)
- ML20094E633 + (14:40:34, 13 December 2024)
- ML20094E620 + (14:40:35, 13 December 2024)
- ML20094E618 + (14:40:36, 13 December 2024)
- 05000370/LER-1984-015-01, :on 840703,test Indicator Lamp on MSIV Failed to Light,Leading to Inadvertent MSIV Closure & Automatic ESF Actuation.Caused by Personnel Error.Personnel Cautioned + (14:40:37, 13 December 2024)
- ML20094E612 + (14:40:38, 13 December 2024)
- 05000483/LER-1984-019, :on 840719,fuel Bldg Ventilation Isolation Signal Actuated by Fuel Bldg Radiation Monitor Alarm.Caused by Monitor Not Powered & Feeder Breaker Accidentally Opened. Radiation Monitor Restored + (14:40:40, 13 December 2024)
- ML20094E604 + (14:40:41, 13 December 2024)