- 05000302/LER-1992-013, :on 920612,during post-maint Testing,Isolation Valve Failed to Close on Demand from Main Cr.Caused by Bent Valve Stems Due to Insufficient Matl Strength.Stem Replaced W/Stem Made of Superior Matl + (05:06:22, 13 December 2024)
- ST-HL-AE-4163, Advises That Security Measures Associated W/Temporary Const, Delineated in Util ,Declassified as Safeguards Info on 920714.All Const Work Completed & Protected Area Boundary Restored to Normal Configuration + (05:06:23, 13 December 2024)
- ML20113H563 + (05:06:24, 13 December 2024)
- ML20113H559 + (05:06:24, 13 December 2024)
- 05000456/LER-1992-006-06, :on 920701,discovered Two non-conservative Assumptions in Safety Analysis for Bdps.Caused by Inadequate Safety Analysis & Subsequent Review for Bdps.Special Operating Order Revised + (05:06:26, 13 December 2024)
- 05000425/LER-1992-005, :on 920421,plant Vent Radiation Monitor Deenergized When ESFAS Testing Initiated,Resulting in Failure to Monitor for Noble Gases.Caused by Poor Communications.Personnel Reinstructed + (05:06:28, 13 December 2024)
- 05000266/LER-1992-006, :on 920531,SG a MSIV IMS-2018 Failed to Fully Close During Initial Test.Caused by Galling on Both Ends of Valve Shaft Due to Mispositioning of Gaskets.Msiv Instructions Will Be Updated & Revised + (05:06:30, 13 December 2024)
- 05000266/LER-1992-005, :on 920527,during Performance of Refueling Procedure Temp cool-down Limit Was Exeeded Per Ts.Caused by Personnel Error.Need to Perform SG Crevice Flushing in Future Will Be Assessed + (05:06:33, 13 December 2024)
- ML20113H546 + (05:06:34, 13 December 2024)
- 05000277/LER-1992-010-01, :on 920704, 1 Auto Transformer Failed & 3 Startup Feed Lost When Breaker Tripped Open.Caused by Defective E-313 Breaker Control Switch.Affected Sys Restored to Appropriate Conditions as Necessary + (05:06:36, 13 December 2024)
- ML20113H533 + (05:06:37, 13 December 2024)
- 05000321/LER-1992-018, :on 920704,unplanned Automatic Actuations of ESF Occurred.Cause Undetermined.Trip Contacts Bypassed Temporarily While Installing Monitoring Equipment on Power Supply + (05:06:38, 13 December 2024)
- ML20113H530 + (05:06:39, 13 December 2024)
- 05000324/LER-1992-003, :on 920413,observed That Foundation Bolts on Control Bldg Emergency Air Filtration Unit Appeared Not to Be in Full Contact W/Nuts.Caused by Missing Clip Angle Weld. Bolts Repaired & Welds Fabricated at Angle + (05:06:41, 13 December 2024)
- HL-2341, Special Rept 2-92-004:on 920630,battery Powered Emergency Lighting Units Inoperable for Period Greater than 72 H.Event Had No Adverse Impact on Nuclear Safety.Battery Discharge Test Performed + (05:06:42, 13 December 2024)
- 05000321/LER-1992-003, :on 920121,air-operated Cooling Water Supply Valves to Emergency Equipment Room Coolers Failed to Open Automatically.Caused by Failure of solenoid-operated Valves. Air Supply to Valves Disconnected + (05:06:44, 13 December 2024)
- ML20113H524 + (05:06:45, 13 December 2024)
- ELV-03929, Special Rept 2-92-5:on 920709-12,temp in Room 122 of Equipment Bldg Exceeded Max Normal Temp of 115 F for More than 8 H.Periods of Plant Operation W/Higher than Normal Temps Had No Effect on Continued Operability of Equipment + (05:06:46, 13 December 2024)
- ML20113H520 + (05:06:46, 13 December 2024)
- 05000331/LER-1992-007, :on 920507,fire Barrier Penetration Found Unsealed During Maint on Instrument Air Pipe.Caused by Insufficient Procedural Controls During Original Const.Fire Watch Initiated for Affected Fire Zones + (05:06:48, 13 December 2024)
- ET-NRC-92-3725, Forwards Response to NRC Questions on Farley SG Tube Alternate Plugging Criteria.Encl Withheld (Ref 10CFR2.790) + (05:06:49, 13 December 2024)
- ML20113H515 + (05:06:50, 13 December 2024)
- 05000331/LER-1992-009, :on 920301,during Local Leak Rate Testing,Three of Eight MSIVs Failed to Meet Established Acceptance Criteria.Caused by Improper Positioning of Disk Piston.Msivs Remachined to within Design Specs + (05:06:51, 13 December 2024)
- 05000440/LER-1992-015, :on 920701,HPCS Sys Declared Inoperable Due to Inoperability of Suppression Pool Suction Valve.Daily Instruction Written to Remind Personnel to Hold Control Switch in Appropriate Position + (05:06:57, 13 December 2024)
- ML20113H507 + (05:06:58, 13 December 2024)
- ML20113H509 + (05:06:58, 13 December 2024)
- ML20113H505 + (05:06:59, 13 December 2024)
- ML20113H499 + (05:07:00, 13 December 2024)
- ML20113H500 + (05:07:00, 13 December 2024)
- 05000302/LER-1992-014, :on 920701,determined That Computer Alarm for Rod Index Limits Not Updated During Cycle 8 to Reflect Changes Due to Fuel Burnup.Caused by Personnel Error. Procedures Revised to Assure Alarm Updated + (05:07:02, 13 December 2024)
- ML20113H496 + (05:07:03, 13 December 2024)
- ML20113H493 + (05:07:04, 13 December 2024)
- ST-HL-AE-4165, Suppl to 920430 Special Rept:On 920408,nonvalid Failure of Sdg 21 Occurred When Sdg Tripped When Released from Emergency Mode.Cause Not Determined.Power Supply Mfg by Beta Products.No Corrective Actions Warranted + (05:07:04, 13 December 2024)
- ML20113H487 + (05:07:05, 13 December 2024)
- ML20113H481 + (05:07:06, 13 December 2024)
- ML20113H485 + (05:07:06, 13 December 2024)
- ML20113H480 + (05:07:07, 13 December 2024)
- ML20113H478 + (05:07:08, 13 December 2024)
- ML20113H477 + (05:07:08, 13 December 2024)
- 05000482/LER-1992-011, :on 920626,discovered That Testing Frequency for EDG B Had Not Been Increased to at Least Once Per Seven Days,Per Tss.Caused by Personnel Error.Procedure Adm 01-0244 EDG Reliability... Will Be Revised + (05:07:10, 13 December 2024)
- ML20113H458 + (05:07:11, 13 December 2024)
- ML20113H452 + (05:07:12, 13 December 2024)
- ML20113H455 + (05:07:12, 13 December 2024)
- ML20113H449 + (05:07:13, 13 December 2024)
- TXX-4399, Forwards Updated Engineering & Const Status Rept.Pages Deleted for Items Whose Deferral Beyond Fuel Load Has Been Accepted by NRC + (05:07:14, 13 December 2024)
- 05000458/LER-1992-010, :on 920624,radiation Protection Technician Encountered Two Mechanical Maint Craftsmen in High Radiation Area.Caused by Failure to Heed Physical Barriers. Personnel Disciplined & Retrained + (05:07:16, 13 December 2024)
- 05000321/LER-1992-020, :on 920710,main CR Environ Control Sys Automatically Transferred to Pressurization Mode When CR Air Intake Radiation Monitor Tripped.Caused by Instrument Setpoint Drift.Trip Setpoint Adjusted + (05:07:18, 13 December 2024)