- 05000289/LER-1979-005-03, /03L-0 on 790225:during Leakage Surveillance on Decay Heat Removal Sys,Total Measured Leakage Exceeded Tech Specs.Caused by Leakage from Valve Packing Glands in Valves DH-V-15 A/B,DH-V-6A,DH-V-5A & BS-V-3B.Glands Adjusted + (07:02:46, 1 January 2025)
- 05000289/LER-1979-005, Forwards LER 79-005/03L-0 + (07:02:48, 1 January 2025)
- ML19322A281 + (07:02:49, 1 January 2025)
- 05000289/LER-1979-004-03, /03L-0 on 790217:emergency Diesel Tripped on Overspeed During Emergency Loading & Power Transfer Test. Caused by Governor Not Shutting Off Fuel When Set Speed Reached.Maint Procedures Revised + (07:02:50, 1 January 2025)
- 05000289/LER-1979-004, Forwards LER 79-004/03L-0 + (07:02:52, 1 January 2025)
- ML19322A277 + (07:02:53, 1 January 2025)
- ML19322A276 + (07:02:54, 1 January 2025)
- 05000289/LER-1979-003-03, /03L-0 on 790217:during post-shutdown Operations, While Performing Emergency Sequence & Power Transfer Test, High Pressure Injection Pump MU-P-1C Tripped on Overload. Caused by Failed Lead Between Winding & Motor.Lead Repair + (07:02:55, 1 January 2025)
- 05000289/LER-1979-003, Forwards LER 79-003/03L-0 + (07:02:58, 1 January 2025)
- ML19322A270 + (07:02:59, 1 January 2025)
- ML19322A272 + (07:02:59, 1 January 2025)
- ML19322A268 + (07:03:01, 1 January 2025)
- ML19322A269 + (07:03:01, 1 January 2025)
- ML19322A267 + (07:03:03, 1 January 2025)
- ML19322A266 + (07:03:04, 1 January 2025)
- ML19322A265 + (07:03:05, 1 January 2025)
- ML19322A264 + (07:03:05, 1 January 2025)
- ML19322A263 + (07:03:06, 1 January 2025)
- ML19322A261 + (07:03:07, 1 January 2025)
- ML19322A262 + (07:03:07, 1 January 2025)
- ML19322A260 + (07:03:08, 1 January 2025)
- ML19322A259 + (07:03:10, 1 January 2025)
- ML19322A257 + (07:03:11, 1 January 2025)
- ML19322A256 + (07:03:11, 1 January 2025)
- ML19322A255 + (07:03:12, 1 January 2025)
- ML19322A254 + (07:03:12, 1 January 2025)
- ML19322A252 + (07:03:13, 1 January 2025)
- ML19322A249 + (07:03:14, 1 January 2025)
- 05000289/LER-1979-002-03, /03L-0 on 790112:when Actuation Signal Was Applied to Open Valve from Its mid-position DH-V-58,motor Breaker Tripped. Caused by Motor Brake Not Releasing. Brake Will Be Inspected by 790331 + (07:03:16, 1 January 2025)
- 05000289/LER-1979-002, Forwards LER 79-002/03L-0 + (07:03:18, 1 January 2025)
- ML19322A245 + (07:03:19, 1 January 2025)
- ML19322A243 + (07:03:20, 1 January 2025)
- ML19322A242 + (07:03:21, 1 January 2025)
- 05000289/LER-1979-001-03, /03L-0 on 790107:during Inservice Insp Test on Decay Heat River Water Pump 1A(DR-P1a),vibration Level Was within Required Action Range. Caused by Imbalance Due to Rag in Pump Section & Perturbed by Shaft Sleeve Wear + (07:03:23, 1 January 2025)
- 05000289/LER-1979-001, Forwards LER 79-001/03L-0 + (07:03:25, 1 January 2025)
- IR 05000289/1978019 + (07:03:34, 1 January 2025)
- ML19322A234 + (07:03:36, 1 January 2025)
- ML19322A233 + (07:03:37, 1 January 2025)
- ML19322A232 + (07:03:38, 1 January 2025)
- ML19322A230 + (07:03:39, 1 January 2025)
- 05000289/LER-1979-001-01, /01T-1 on 780106:informed by B&W That Difference Between Reactor Power as Indicated by out-of-core Instrumentation & as Calculated by Heat Balance May Exceed 4% of Full Power.Tech Spec Change Initiated + (07:03:41, 1 January 2025)