Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ENS 40328 +
- ENS 42194 +
- ENS 44262 +
- 05000325/LER-2008-002 +
- IR 05000259/2015001 +
- IR 05000259/2013004 +
- IR 05000259/2013003 +
- IR 05000259/2013002 +
- 05000259/FIN-2013003-02 +
- ML17213B091 +
- ML17317A743 +
- ML17347B157 +
- ML18152A125 +
- ML19207A273 +
- ML19274D154 +
- ML19260A226 +
- ML19296D145 +
- ML051390181 +
- ENS 40804 +
- ENS 51715 +
- ENS 48540 +
- L-04-014, January 2004 Monthly Operating Report for Beaver Valley, Units 1 and 2 +
- ML20064B273 +
- ML033430360 +
- ML20070K811 +
- ML20083A228 +
- ML20079C126 +
- ML20096C410 +
- ML20134K581 +
- ML20155B103 +
- ML20246M695 +
- ENS 55586 +
- L-98-178, Monthly Operating Repts for Aug 1998 for Bvps,Units 1 & 2. with +
- ST-HL-AE-3767, Responds to NRC Re Violations Noted in Insp Rept 50-498/91-08.Corrective Actions:Electrician Involved W/Event Counseled & Operational Improvement Program Addressed Initiatives to Improve Personnel Performance +
- U-601795, Responds to NRC Re Violations Noted in Insp Rept 50-461/90-26.Corrective Actions:Procedure 1905.21 Re Restricted High Radiation Area Key Control Revised to Restrict Issuance of Keys to Radiation Protection Personnel +
- 05000339/LER-1989-004-02, :on 890502,unexpected Automatic Reactor Trip Signal Generated During Performance of ICP-FW-2-F-2486. Caused by Procedure Inadequacy.Instrument Dept Procedures Will Be Reviewed & Revised +
- 05000461/LER-1989-024, :on 890619,west RWCU HX Room Temp Module Failed Channel Checks.Investigation Into Failures Revealed That Modules Miscalibrated on 890616.Caused by Personnel Error. Technicians Briefed on Use of Manuals +
- 05000313/LER-1989-011, :Between 890326 & 0421,control Room Emergency Ventilation Sys (CREVS) Unexpectedly Automatically Actuated 13 Times.Caused by Spiking of Radiation Monitor & Inadequate Corrective Actions from Previous Events +
- 05000325/LER-1989-014, :on 890514,inner Air Lock Fire Door Removed from Frame W/O Required Fire Protection Tech Specs Limiting Condition for Operation Established.Caused by Poor Communication of Personnel.Training Initiated +
- 05000346/LER-1998-006, :on 980624,loss of Offsite Power Was Noted. Caused by Tornado Damage to Switchyard.Tested & Repaired Affected Electrical & Mechanical Equipment Necessary to Restore Two Offsite Power Sources +
- 05000374/LER-1989-005-01, :on 890207,isolation of Shutdown Cooling Sys Due to Spurious High Flow Signal.Pulsation Dampeners Installed in Unit 2 Switches.Instrument Lines Completely Walked Down & Verified to Be Properly Routed +
- 05000354/LER-1987-009, :on 870124,cooling Tower Blowdown RMS Sample Pump Froze.Sampling of Radioactive Liquid Effluent Not Initiated Until Tech Spec Action Statement Entered on 870126.Caused by Personnel Error +
- 05000382/LER-1985-036, :on 850801,inadvertent Actuation of ESF Portion of Control Room Ventilation Sys Occurred Due to Spike in Control Room Outside Air Intake Radiation Monitor.Caused by Tears in Foil on Detectors.Detectors Replaced +
- 05000341/LER-1993-002, :on 930114,HPCI Sys Failed to Start on Simulated Auto Injection Signal During Performance of Surveillance.Caused by Loss of Supply Voltage to Governor Control sys.Voltage-dropping Resistor Replaced +
- 05000353/LER-1992-012-02, :on 921204,both Reactor Recirculation Pumps Tripped When end-of-cycle Recirculation Pump Trip Breakers Tripped Open.Root Cause Undetermined.Upcoming Continuing Training Programs Will Be Enhanced +
- 05000254/LER-1992-010-03, :on 920407,loss of 125 Volt Dc Turbine Bldg Bus 1A & 1A-2 Occurred.Caused by Personnel Error.Plexiglass Covers Placed Over Disconnects Until Work Completed +
- 05000353/LER-1991-017, :on 911115,oil Leak Discovered in HPCI Sys Which Could Have Prevented Sys from Maintaining Reactor in Safe Shutdown Condition.Caused by Local Defect in Section of Tube.Line Replaced W/Hard Pipe Line +
- 05000341/LER-1992-003, :on 920407,vacuum Breaker Did Not Close After Being Opened.Caused by Actuator Binding Up with Actuator Cylinder in Open Position.Actuator Cylinder for Vacuum Breaker Replaced +
- 05000353/LER-1991-017-03, :on 911115,discovered Oil Leak in Oil Line to Turbine Stop Valve.Cause Under Investigation.Line Sent to Lab for Failure Analyses & Replaced W/Hard Pipe Line.W/ +
- ML19327A650 +