Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000306/LER-1992-002, :on 920220,interruption of One Train of Residual Heat Removal During Unit 2 RCS Draining Operation Occurred.Procedure D2 Did Not Provide Adequate Guidance. Procedure D2.3 Written for one-time Use + (ML20118A573)
- HL-2160, Forwards Application for Amends to Licenses DPR-57 & NPF-5, Allowing Southern Nuclear Operating Co,Inc to Possess, Manage,Use & Operate & Maintain Facilities + (ML20118A574)
- ML20118A576 + (ML20118A576)
- ML20118A577 + (ML20118A577)
- PLA-3852, Requests Exemption from Emergency Plan Exercise Biennial Requirements for Full Participation of State & Local Authorities During 1993 Exercise.Detailed Description of Scope & Extent of Play for Federal Field Exercise 3 Encl + (ML20118A579)
- 05000254/LER-1992-019-02, :on 920815,emergency Load Drop Initiated Due to Unisolable Electrohydraulic Control Unit Fluid Leak, Resulting in Automatic Reactor Scram.Caused by Insufficient Operator Training.Training Will Be Provided + (ML20118A580)
- 05000331/LER-1992-013, :on 920817,automatic Reactor Scram Initiated Due to Perceived High Average power-range Neutron Flux Level.Caused by Noise Signal Which Affected Recirculation Flow Signals.Circuit Inductors Installed + (ML20118A581)
- 05000219/LER-1992-011, :on 920826,discovered That Circuitry of Six Valves May Be Susceptible to Hot Shorts During CR Fire That Could Render Valves Inoperable.Caused by Failure to Meet App R Design.All Valves Will Be Modified + (ML20118A582)
- 05000366/LER-1992-013-02, :on 920722,confirmed That Single Failure or Misoperation of Electrical Circuit Breaker Would Result in Loss of Power to 120/208-volt Ac Distribution Panel.Caused by Inadequate Design.Design Mod Developed + (ML20118A584)
- ML20118A585 + (ML20118A585)
- 05000277/LER-1992-015-01, :on 920817,reactor Scram Occurred Following Main Generator Lock Out.Caused by Less than Adequate Generation & Approval of Substation Load Dispatcher Permit. Isolations Reset & Affected Sys Restored + (ML20118A586)
- 05000293/LER-1992-010, :on 920818,RCIC Removed from Svc & Made Inoperable to Repair Area Temp Switch Terminal Block Termination Point.Caused by Repeated Torquing of Terminal Screw.Terminal Replaced & Circuitry Tested + (ML20118A587)
- ML20118A588 + (ML20118A588)
- ML20118A590 + (ML20118A590)
- ML20118A591 + (ML20118A591)
- 05000482/LER-1992-014, :on 920817,discovered That Two Containment Isolation Valves Not Verified in Locked Closed Position from 920123-0215.Caused by Operator Error.Surveillance Procedure Re Valve Listing Revised + (ML20118A592)
- BSEP-92-0014, Suppls 920803 Response to Violations Noted in Insp Repts 50-324/92-15 & 50-325/92-15.Schedule for Rev of Procedures OMMM-002 Re Stds for Preparing Maint Procedures & OMMM-001 Re Conduct of Operations Revised to 921231 + (ML20118A593)
- ML20118A594 + (ML20118A594)
- ML20118A596 + (ML20118A596)
- 05000266/LER-1992-007, :on 920818,RPS Engineered Safeguards Sys & Process Instrumentation within Cabinets Declared Inoperable. Caused by Friction Clip Assemblies Loaded Beyond Yield Point.Cabinet Bolting Upgraded + (ML20118A598)
- 05000285/LER-1992-027, :on 920817,determined That Open Stop Valve Between Regenerative Heat Exchanger & CH-202 Did Not Conform to Code Requirements.Caused by Inadequate Design Review. Plant Procedures Will Be Reviewed & Revised + (ML20118A600)
- JPN-92-049, Withdraws 910419 Application for Amend to License DPR-59, Changing TS to Add Operability & SR for HVAC Equipment Associated W/Four Environ Encls.Analyses & Mods Initiated to Allow post-accident Qualification of Load Ctrs + (ML20118A602)
- 3F0922-09, Requests That NRC Review Findings in Insp Rept 50-302/92-201 Re Insp of Procurement & commercial-grade Dedication Programs,In Light of NRC Mgt Direction,Per 920813 Meeting. Updated Technical Assessment & Viewgraphs Encl + (ML20118A604)
- 05000423/LER-1992-019-01, :on 920818,determined That Trains a & B of Hydrogen Recombiner Sys Had Been Inoperable Between 920812 & 17 & Train a Positive Displacement Blower Motor Found W/ Lifted Lead Due to Personnel Error + (ML20118A607)
- 05000454/LER-1992-007-09, :on 920727,discovered Nonconservative Method Used to Calculate Shutdown Margin.On 920818,determined That TS 3.1.1.1 Not Met for Surveillance Performed on 900211. Caused by Procedural Flaw.Procedure Revised + (ML20118A608)
- ML20118A609 + (ML20118A609)
- ML20118A612 + (ML20118A612)
- ML20118A613 + (ML20118A613)
- ML20118A615 + (ML20118A615)
- 05000336/LER-1992-015-01, :on 920821,determined That SPEC 200 Cabinets Mfg by Foxboro Co May Not Be Seismically Qualified as Result of Missing Bumpers.Caused by Lack of Vendor Instruction.Seismic Bumpers Ordered + (ML20118A618)
- 05000325/LER-1992-019, :on 920821,safety Relief Valves Tested at Wyle Laboratories Exceeded TS Limit Due to Pilot disc-to-seat Bonding.Srv Pilots Will Be Recertified Prior to Startup of Units 1 & 2 + (ML20118A619)
- ML20118A622 + (ML20118A622)
- ML20118A623 + (ML20118A623)
- ML20118A625 + (ML20118A625)
- NRC-92-0101, Monthly Operating Rept for Aug 1992 for Fermi 2 + (ML20118A627)
- ML20118A629 + (ML20118A629)
- ML20118A631 + (ML20118A631)
- RBG-37494, Updates 891027 Initial Response to GL 88-20 Re IPE, Consisting of Revised Completion Dates for Milestones.Level 1 & 2 IPE Submittals,Per GL 88-20,Suppls 1,2 & 3,will Be Submitted by 930201 + (ML20118A634)
- ML20118A635 + (ML20118A635)
- ML20118A636 + (ML20118A636)
- 05000219/LER-1992-009, :on 920822,reactor Scrammed on Low Water Level Due to Failure of Proportional Amplifier.Failed Proportional Amplifier Replaced & Plant Restarted + (ML20118A638)
- ELV-04004, Application for Amends to Licenses NPF-68 & NPF-81,revising TS Re Overtemp delta-T & Overpower delta-T Reactor Trip Functions to Provide Addl Operating Margin to Reactor Trip & Turbine Runback Setpoints to Account for Flow Phenomena + (ML20118A639)
- ML20118A641 + (ML20118A641)
- 05000327/LER-1992-016, :on 920819,LCO 3.0.3 Entered for 18 Minutes When Both CREVS Trains Taken Out of Svc to Replace Inlet Damper in Each Train.Caused by Bypass Leakage Through Existing Dampers.Both Dampers Replaced + (ML20118A644)
- ML20118A645 + (ML20118A645)
- ML20118A646 + (ML20118A646)
- ML20118A648 + (ML20118A648)
- ML20118A649 + (ML20118A649)
- ML20118A654 + (ML20118A654)
- ML20118A655 + (ML20118A655)
- 05000456/LER-1992-010-06, :on 920814,dual Accounting for Samarium to Boron Value Contained in Curvebook Table 1-1 Re Min Required Boron Concentration for Shutdown Margin Occurred.Caused by Procedural Flaw.Procedure Revs Submitted + (ML20118A656)