Submits Final Response to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Util Has Determined That There Are 46 Westinghouse Type DS-416 Breakers Installed in Unit 2 Class 1E Applications as Noted in Subj Bulletin
ML20118A612
Person / Time
Site: Comanche Peak 
Issue date: 09/15/1992
From: William Cahill
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-88-001, IEB-88-1, TAC-M65955, TAC-M65956, TXX-92432, NUDOCS 9209240120
Download: ML20118A612 (3)


Text

. -.

l 4

N 0-Log

  1. TXX-92432

{

]

File # 10119 NRCB 88-01 TUELECTRIC 908.3 Ref.

  1. 10CFR5U.71

[,N,"'

September 15, 1992 y,

U. S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555

SUBJECT:

C0HANCHE PF.AK STEAM ELECTRIC STATION (CPSES)

UNIT 2 DOCKET NO. 50 446 NRC BULLET'N 88 01 (TACSA65955 A65956)

DEFECTS IN WESTINGHOUSE CIRCUIT BREAKERS REF: 1)

NRC Bulletin 88-01: Defects in Westinghouse Circuit Breakers, dated February 5, 1988

2) Westinghouse Technical Bulletin NSID TB 87-11, Westinghouse Circuit Breakers Type DS/DSL: Weld on Pole Shaft, dated December 1, 1987
3) TO Electric Letter TXX 88377 from W. G. Counsil to U.S.N.R.C. dated April 8, 1988 l
4) NRC Letter from C. 1. Grimes to W. G. Counsil dated June 1, 1988
5) TV Electric Letter TXX-89080 from William J. Cahill to U.S.N.R.C. dated February 17, 1989 Gentlemen:

Reference 1) requested addressees to perform certain inspections of WestingL'use DS series circuit breakers used in Class 1E applications.

I Reference 3) provided TV Electric's interim response.

Reference 4) provided the results of the NRC's review of TV Electric's interim response.

Reference 5) provided TV Electric's final response for Unit 1.

provided below is TV Electric's final response to NRC Bulletin 88-01 for Unit 2.

TV Electric hss determined that there are a total of 46 Westinghouse type DS-416 breakers installed in Unit 2 Class 1E applications.

No other type DS or DSL breakers _ identified in reference 1 are used in Unit 2 Class 1E applications.

The pole shafts on all installed Unit 2 05-416 Class 1E breakers and spares have been replaced with new pole shafts from the

vendor, The replacement pole shafts were receipt inspected and accepted per the short term and long term inspection requirements contained in reference 2 as modified by reference 1.

The_ alignment check specified by reference 2 was satisfactorily performed 6; ring'the installation of the replacement pole shafts in the breakers, f

1 I

l 22 n u

{'. '

[ [

hhh

$O00k46 400 N. Ohve street LB. 81 Danas. Tem 75201

/

o PDR.

~

4 TXX-92432 Page 2 of 2 Six of the removed pole shafts were inadvertently discarded prior to being inspected.

Of the 40 pole shaf ts which were examined. 38 were found to have welds which did not meet the criteria specified in Reference 2.

The 40 pole shafts which were examined have been discarded.

Sincereb, i

k./

/

William J. Cahill, Jr.

Cbt'/JHG/tg i

Attachment c-Mr. J. L. Hiihoan, Region IV Hr. B. E. Holian, NRR 1

Residelat inspectors. CPSES (2) i.

t

}

d i

4 1

i

{

i l

Attachment to TXX 92432 i

l Page 1 of 1 UNITED STATES OF AHERICA i

i NUCLEAR REGULATORY COMMISSION In the Matter of

)

\\

)

}

Texas Utilities Electric Company

)

Docket No. 50-446

)

(Comanche Peak Steam Electric

)

Station, Unit 2)

)

AFFIDAVIT a

William J. Cahill, Jr. belag duly sworn, hereby deposes and says-that he is I

i Group Vice President. Nuclear of TU Electric. the lead Applicant herein:'that he is duly authorized to sign and file with the Nuclear Regulatory Conwission this response to NRC Bulletin 88-01 (TACS 65955/65956) for the captioned

=

facility: that he is familiar with the content-tliereof; and that.the matters

}

set forth therein are true and correct tr, *,he best nf his-knowledge, t

information and belief.-

I

' William J. Calgl, Jr. I V

Group Vice President, Nuclear p

STATE OF TEXAS

)

)

?

LOUNTY OF DALLAS- )

Subscribed and' sworn to before'me,-on this-14th day of September-

, 1992.

$/

_=

Nota Public l

N~

~...,-. a =..~ l':

,l