- ML20079L931 + (ML20079L931)
- ML20079L932 + (ML20079L932)
- 0CAN028312, Notifies That J Griffin Designated Senior Nuclear Mgt Representative + (ML20079L933)
- ML20079L934 + (ML20079L934)
- ML20079L938 + (ML20079L938)
- 05000317/LER-1983-073-03, /03L-0:on 831216,excessive Leak Rate Past Containment Personnel Air Lock Outer Door Discovered.Caused by Degradation of Gaskets & Misalignment of Door.New Gaskets Installed & Door Closure Mechanism Adjusted + (ML20079L941)
- ML20079L945 + (ML20079L945)
- 05000318/LER-1983-070-03, /03L-0:on 831125,pressure Level Decreased to 116 Inches While Loading Main Turbine.Caused by RCS Temp Swings. Change to Pressurizer Program in Progress + (ML20079L948)
- ML20079L949 + (ML20079L949)
- ML20079L951 + (ML20079L951)
- ML20079L953 + (ML20079L953)
- ML20079L958 + (ML20079L958)
- ML20079L959 + (ML20079L959)
- ML20079L960 + (ML20079L960)
- ML20079L961 + (ML20079L961)
- 05000458/LER-1991-003, :on 910322,damper Isolations & Automatic Swap of Divisional Control Bldg Ventilation/Chiller Occurred Due to Inadequate Work Plan.Work Plan Revised to Document Removal & Restoration of Hot & Neutral Wiring + (ML20079L965)
- ML20079L966 + (ML20079L966)
- ML20079L967 + (ML20079L967)
- 05000387/LER-1983-171-03, /03L-0:on 831217,both Reactor Water Cleanup Sys High Dp Channel Calibr Switches Had as-found Trip Settings Greater than Tech Spec Requirements.One Switch out-of-calibr Due to Bellows Failure.Other Switch Recalibr + (ML20079L969)
- ML20079L970 + (ML20079L970)
- ML20079L975 + (ML20079L975)
- 05000387/LER-1983-010-01, /01P-0:on 830209,runout Flow on Feedwater Pumps Found in Excess of 135% Assumption in Feedwater Controller Failure/Max Demand Transient Analysis.Feedwater Motor Speed Changer Reduced to Limit Flow.Stops Will Be Adjusted + (ML20079L978)
- ML20079L979 + (ML20079L979)
- ML20079L980 + (ML20079L980)
- ML20079L981 + (ML20079L981)
- ML20079L983 + (ML20079L983)
- ML20079L986 + (ML20079L986)
- ML20079L987 + (ML20079L987)
- 05000272/LER-1983-066-01, /01T-0:on 831225 & 26,fire Suppression Water Storage Tank Capacity Dropped Below Min.Caused by Ruptured Elbow on Sprinkler Riser Due to Freezing.Elbow Replaced & Number of Operating Pumps Increased + (ML20079L988)
- ML20079L989 + (ML20079L989)
- ML20079L990 + (ML20079L990)
- 05000333/LER-1982-059, Forwards LER 82-059/03L-0 + (ML20079L992)
- ML20079L995 + (ML20079L995)
- ML20079L999 + (ML20079L999)
- 05000346/LER-1983-002, Forwards LER 83-002/03L-0 + (ML20079M001)
- ML20079M009 + (ML20079M009)
- ML20079M013 + (ML20079M013)
- ML20079M016 + (ML20079M016)
- ML20079M017 + (ML20079M017)
- ML20079M023 + (ML20079M023)
- ML20079M024 + (ML20079M024)
- 05000333/LER-1982-059-03, /03L-0:on 821226,MSIV B Outboard 10% Switch Would Not Reset When Tested Per Tech Spec 3.1-1.Caused by Mismatch Between Activation & Striker Plate in Reset Direction of Valve Travel.Striker Plate Mechanically Reworked + (ML20079M025)
- ML20079M028 + (ML20079M028)
- 05000346/LER-1983-002-03, /03L-0:on 830114 & 15,after Reactor Trips,Rcs Dose Equivalent I-131 Exceeded Tech Spec Limit.Caused by Slight Leakage of Fission Products Through Fuel Cladding.Caused by Temp & Pressure Changes.Situation Monitored + (ML20079M031)
- 05000387/LER-1983-170-03, /03L-0:on 831213,charcoal Filters in Train a of Control Room Emergency Outside Air Supply Sys Did Not Satisfy Test Specs During Freon Leak Test.Caused by Insufficient Charcoal in Charcoal Filter + (ML20079M032)
- 05000220/LER-1983-045-03, /03L-0:on 831221,site Operations Review Committee Failed to Review Temporary Change Re Fuel Handling Procedure N1-FHP-32, Fort St Vrain Cask Handling, within 7 Day Tech Spec Limitation + (ML20079M038)
- 05000317/LER-1983-071-03, /03L-0:on 831210,pressurizer Pressure Decreased to 2,180 Psia.Pressure Switch in Stator Liquid Cooling Sys Failed,Causing Turbine Runback.Caused by Loose Screw Holding Switch Actuator to Bourdon Tube.Screw Replaced + (ML20079M043)
- 05000328/LER-1983-008, Forwards LER 83-008/03L-0 + (ML20079M046)
- ST-HL-AE-1045, Final Deficiency Rept Re Control & Issuance of Design Related Drawings.Initially Reported on 831216.Configuration Control Program Assures Compliance W/Technical Requirements. Item Not Reportable Per 10CFR50.55(e) + (ML20079M047)
- 05000333/LER-1983-041-04, /04T-0:on 831228,mollusk Samples Exceeded 10 Times Control Sample for Mn-54.Caused by High Release of Mn-54 Via Liquid Effluent,Producing High Concentration Factor in Mollusks.Release within Tech Spec Limits + (ML20079M050)