Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20078H176 + (ML20078H176)
- ML20078H183 + (ML20078H183)
- TXX-9502, Discusses Implementation of Rod Control Sys Changes in Response to GL 93-04, Rod Control Sys Failure & Withdrawal of Rod Control Cluster Assemblies + (ML20078H185)
- ML20078H186 + (ML20078H186)
- 05000373/LER-1983-109-03, /03L-0:on 830903,radwaste Discharge Line hi-hi Radiation Isolation Valve OWL067 Failed to Fully Close. Caused by Faulty Valve Piston.Internal Valve Piston Replaced + (ML20078H195)
- ML20078H198 + (ML20078H198)
- ML20078H203 + (ML20078H203)
- ML20078H205 + (ML20078H205)
- 05000373/LER-1983-111-03, /03L-0:on 830821,RHR Pump a Suction Valve 1E12-F004A Would Not Operate Properly from Control Room Panel 1H13-P601.Caused by Broken Torque Switch in Valve Motor.Motor & Torque Switch Replaced + (ML20078H208)
- AECM-83-0664, Final Deficiency Rept for Unit 1 & Interim Deficiency Rept for Unit 2 Re Potential Rupture of High Pressure Fuel Injection Lines on Div I & II Diesel Generators During Engine Operation.Also Reportable Under Part 21 for Unit 1 + (ML20078H214)
- ML20078H219 + (ML20078H219)
- ML20078H224 + (ML20078H224)
- ML20078H230 + (ML20078H230)
- ST-HL-AE-4957, Forwards Addl Info in Response to NRC Bulletin 90-001,Suppl 1, Loss of Fill-Oil in Transmitters Mfg by Rosemount, Per NRC 941115 Telcon Request + (ML20078H237)
- 05000315/LER-1983-092-03, /03L-0:on 830912,essential Svc Water Pump 1W Relay Timer Exceeded Tech Spec Tolerance.Caused by Instrument Drift.Timer Recalibr + (ML20078H246)
- ML20078H247 + (ML20078H247)
- ML20078H250 + (ML20078H250)
- 05000328/LER-1983-118-03, /03L-0:on 830907,SI-214 Re Uncontrolled Boron Dilution Not Performed within Required 72 H Frequency.Caused by Personnel Error.Operations Personnel Reinstructed.W/ + (ML20078H253)
- ML20078H260 + (ML20078H260)
- ML20078H263 + (ML20078H263)
- 2CAN108302, Forwards Corrected Attachments 24.1 & 27.1 to IAEA Design Info Questionnaire for Safeguards Program Submitted in + (ML20078H266)
- ML20078H269 + (ML20078H269)
- RBG-41109, Confirms That Util Complies W/Requirements of Approved Generic Topical Rept TDI-EDG-001-A & Requests That NRC Approve LAR 93-03 Re Removal of Tdi DG License Conditions as Soon as Practical + (ML20078H270)
- ML20078H273 + (ML20078H273)
- ML20078H279 + (ML20078H279)
- ML20078H280 + (ML20078H280)
- ST-HL-AE-4985, Forwards Change QA-024 to Operations QA Plan. Change Will Be Incorporated in Operations QA Plan in Next Biennial Update + (ML20078H283)
- ML20078H291 + (ML20078H291)
- ML20078H292 + (ML20078H292)
- B15025, Forwards Millstone Unit 3 Simulator 4-Year Certification Rept,Oct 1994 + (ML20078H297)
- ML20078H298 + (ML20078H298)
- ST-HL-AE-1015, Revises 830228 Response to Generic Ltr 83-01 Operator Licensing Exam Site Visit. Applications Will Be Submitted in Feb 1984 for 10 Persons Scheduled for Sept 1984 Instructor Certification Exam + (ML20078H301)
- ML20078H302 + (ML20078H302)
- ML20078H303 + (ML20078H303)
- ML20078H313 + (ML20078H313)
- ML20078H314 + (ML20078H314)
- 05000416/LER-1983-141-01, /01T-0:on 830919,determined Containment Spray Timers Could Operate Less Conservatively than Tech Spec Limit.Caused by Containment Spray & Core Cooling Modes Functioning W/Less Conservative Limits + (ML20078H316)
- 05000302/LER-1983-038-01, /01T-0:on 830922,followup Investigation of Quality Audit Finding Uncovered Procedural Inadequacy Allowing Requirement for Surveillance of Certain Fire Barrier Penetration Seals to Be Overlooked + (ML20078H318)
- ML20078H321 + (ML20078H321)
- ML20078H322 + (ML20078H322)
- 05000362/LER-1983-062-03, /03L-0:on 830901 & 05,during Low Power Physics Testing in Mode 2,control Element Assembly 84 Dropped More than 19 Inches.Caused by Improper Timing of Assembly Grippers.Timing Adjusted + (ML20078H324)
- ML20078H328 + (ML20078H328)
- 05000259/LER-1983-053-03, /03L-0:on 830314,control Room Emergency Ventilation Train a Flow Control Damper Found in Full Open Position.Caused by Loose Damper Arm.Damper Reset to Proper Position + (ML20078H331)
- ML20078H332 + (ML20078H332)
- ML20078H337 + (ML20078H337)
- ML20078H349 + (ML20078H349)
- ML20078H352 + (ML20078H352)
- 05000316/LER-1983-088-03, /03L-0:on 830912,nonfunctional Fire Seal Discovered.Caused by Fire Seal Pulled While Installing Another Cable.Fire Seal Repaired & Contractor Personnel Retrained + (ML20078H359)
- 05000316/LER-1983-089-03, /03L-0:on 830915,west Containment Spray Pump Discharge Valve Position Lights Noted Out & Breaker Open. Cause Could Not Be Determined.No Corrective Action Planned + (ML20078H363)
- PY-CEI-NRR-1895, Informs of Rev of Commitment Made in Response to Violation Noted in Insp Rept 50-440/93-23 Re Periodic Testing of Emergency Facility HVAC Sys + (ML20078H365)
- 05000316/LER-1983-090-03, /03L-0:on 830920,during Surveillance Test on solid-state Protection Sys,Two Logic Positions Tested Unsatisfactorily.Caused by Defective Universal Card A-311. Logic Card Replaced + (ML20078H366)