- 05000369/LER-1983-010-03, /03L-0:on 830216,while in Mode 6,control Room Outside Air Intake Radiation Monitors 1EMF-43A &43B Declared Inoperable.Caused by Personnel Error.Monitors Returned to Svc & Inlet Valves Opened After Testing + (ML20072N563)
- AECM-83-0386, Final/Interim Deficiency Rept PRD-82/14 for Units 1/2, Respectively Re Sheared Bolts on Rear Crankcase Cover of Delaval Diesel Generators.Unit 1 Bolts Not Defective.Unit 2 Rept Due on 850130.Also Reportable Per Part 21 + (ML20072N571)
- ML20072N573 + (ML20072N573)
- ML20072N575 + (ML20072N575)
- 05000369/LER-1983-009, Forwards LER 83-009/03L-0.Detailed Event Analysis Encl + (ML20072N582)
- ML20072N585 + (ML20072N585)
- RBG-15-389, Interim Deficiency Rept DR-105 Re Electrical Separation of Reactor Protection Sys Wiring from NSSS Shutoff Wiring within Power Generation Control Complex.Initially Reported on 830329.Info from GE Awaited.Next Rept Due by 830913 + (ML20072N588)
- ML20072N589 + (ML20072N589)
- ML20072N590 + (ML20072N590)
- 05000313/LER-1983-014-03, /03L-0:on 830609,auxiliary Feedwater Pump P-75 Rendered Inoperable.Caused by Supply Piping Seal Break Due to Piping Misalignment.Piping Replaced & Realigned to Reduce Stress + (ML20072N591)
- 05000366/LER-1983-026-03, /03L-0:on 830610,diesel Generator 2C Failed to auto-start After Manual Trip.Caused by Shutdown Solenoid Stuck in Shutdown Position.Solenoid Cleaned + (ML20072N594)
- ML20072N596 + (ML20072N596)
- ML20072N597 + (ML20072N597)
- 05000259/LER-1983-013-01, /01T-0:on 830307,standby Gas Treatment Train C Removed from Svc for Maint.Testing Revealed Train Failed to Meet Tech Spec Flowrate Requirements.Caused by Stuck Back Draft Damper.Damper Adjusted + (ML20072N598)
- RA-20-0067, Emergency Plan PLP-007, Revision 94 + (ML20072N601)
- ML20072N605 + (ML20072N605)
- ML20072N608 + (ML20072N608)
- 05000369/LER-1983-009-03, /03L-0:on 821112,during Troubleshooting & Checkout Activities Following Diesel Generator Mod Work,Diesel Generator 1B Experienced Failures.Caused by Wires on Wrong Terminal,Burned Diodes & Spurious Low Crankcase Signals + (ML20072N611)
- 05000318/LER-1983-017, Forwards LER 83-017/03L-0 + (ML20072N613)
- ML20072N614 + (ML20072N614)
- 0CAN038322, Requests Exemption from Implementation Schedule for 10CFR50, App R,Sections III.G.2.a,b & C Or,Alternatively,From 10CFR50.48(c) for All Fire Protection Barriers/Penetrations & All Suppression/Detection Sys.Justification Encl + (ML20072N618)
- ML20072N621 + (ML20072N621)
- 05000296/LER-1983-014, Forwards LER 83-014/03L-0 + (ML20072N623)
- ML20072N626 + (ML20072N626)
- 05000318/LER-1983-017-03, /03L-0:on 830218,power Lost to Saltwater Outlet Valves for 21 Svc Water & 21 Component Cooling Water Hx. Caused by Installation of Wrong Value Fuses.Correct Fuses Installed + (ML20072N629)
- ML20072N631 + (ML20072N631)
- ML20072N634 + (ML20072N634)
- ML20072N635 + (ML20072N635)
- ML20072N639 + (ML20072N639)
- ML20072N640 + (ML20072N640)
- W3P83-0982, Forwards Amend 31 to Fsar.Amend Includes Addl Info Re Completed Evaluation of Effects of SSE & LOCA Asymmetric Loads on Fuel & Results of Revised ECCS Analysis + (ML20072N642)
- ML20072N644 + (ML20072N644)
- PMNS20200249, Reactor Oversight Process Public Meeting + (ML20072N652)
- 05000387/LER-1983-034, Forwards LER 83-034/03L-0 + (ML20072N658)
- ML20072N660 + (ML20072N660)
- ML20072N669 + (ML20072N669)
- 05000387/LER-1983-034-03, /03L-0:on 830218,during Shutdown,Operator Discovered LPCI B Injection Throttle valve,F017B,vibrating Severely.Caused by Operating RHR B Shutdown Cooling W/Sys Flow Rates Outside Optimum Throttling Range + (ML20072N680)
- 05000296/LER-1983-014-03, /03L-0:on 830228,differential Pressure Controller PDIC-64-16 Found to Have Setpoint Above Tech Spec Limit. Caused by Pressure Controller Being Set at Incorrect Value. Setpoint Corrected + (ML20072N685)
- ML20072N688 + (ML20072N688)
- ML20072N693 + (ML20072N693)
- ML20072N697 + (ML20072N697)
- 05000269/LER-1983-007, Forwards LER 83-007/01T-0.Detailed Event Analysis Encl + (ML20072N703)
- ML20072N710 + (ML20072N710)
- ML20072N717 + (ML20072N717)
- ML20072N719 + (ML20072N719)
- 05000336/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20072N720)
- 05000269/LER-1983-007-01, /01T-0:on 830303,manual Containment Isolation Valve CF-19 Discovered Open on All Three Units.Caused by Personnel Error Due to Inadequate Review for Procedure Approval.Valve Closed & Procedures Revised + (ML20072N740)
- ML20072N744 + (ML20072N744)
- ML20072N749 + (ML20072N749)
- 05000328/LER-1983-027, Forwards LER 83-027/03L-0 + (ML20072N751)
- ML20072N755 + (ML20072N755)