Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000325/LER-1982-094, Forwards LER 82-094/03L-0 + (ML20063L810)
- 05000335/LER-1982-036, Forwards LER 82-036/03L-0 + (ML20063L813)
- ML20063L820 + (ML20063L820)
- ML20063L823 + (ML20063L823)
- ML20063L824 + (ML20063L824)
- ML20063L825 + (ML20063L825)
- 05000335/LER-1982-036-03, /03L-0:on 820813,at 99% Power W/Charging Pump B Out of Svc,Charging Pump C Taken Out of Svc to Recharge Discharge Accumulator.Pump Recharged & Restored to Operable Status + (ML20063L827)
- ML20063L841 + (ML20063L841)
- 05000249/LER-1982-012, Forwards Updated LER 82-012/03X-1 + (ML20063L842)
- ML20063L845 + (ML20063L845)
- 05000249/LER-1982-012-03, During Local Leak Testing of Primary Containment Isolation Valves,Drywell & Torus Purge Sys Valve Was Found to Leak at Rate in Violation of Tech Spec Limit.Caused by Failure of Resilient Seating Matl + (ML20063L847)
- ML20063L849 + (ML20063L849)
- ML20063L850 + (ML20063L850)
- IR 05000269/2019006 + (ML20063L851)
- ML20063L854 + (ML20063L854)
- 05000333/LER-1982-034, Forwards LER 82-034/03X-1 + (ML20063L855)
- 05000325/LER-1982-094-03, /03L-0:on 820809,review Revealed Failure of Tech Spec List of Fire Protection Detectors to Reflect Plant Design.Caused by Personnel Failure to Submit Tech Spec Change After Plant Mod Increased Number of Detectors + (ML20063L857)
- ML20063L861 + (ML20063L861)
- 05000333/LER-1982-034-03, /03X-1:on 820713,instrument Flow Components Drift Resulted in Nonconservative Calculation of Core Thermal Power.Rated Thermal Power Limit Exceeded on Approx 75 Days of Cycle 5 Operation.Caused by Instrument Drift + (ML20063L869)
- 05000259/LER-1982-055, Forwards LER 82-055/03L-0 + (ML20063L871)
- 05000369/LER-1993-011, :on 931115,determined That DG 1B Fuel Storage Tank Level Gauge Out of Tolerence Due to Malfuntion of Subj Gauge.Iae Technician Calibrated Level Gauge to Bring Gauge Back Into Tolerence + (ML20063L874)
- ML20063L886 + (ML20063L886)
- 05000259/LER-1982-055-03, /03L-0:on 820807,environ Data Station Delta Air Temp for 620-737 MSL (TDR-90-103) & 620-887 MSL (TDR-90-140) Observed to Read Downscale.Caused by Hewlett Packard Model 3450 Digital Voltmeter Failing on Ohms Range + (ML20063L900)
- ML20063L903 + (ML20063L903)
- ML20063L905 + (ML20063L905)
- 05000244/LER-1982-018, Forwards LER 82-018/03L-0 + (ML20063L913)
- 05000315/LER-1982-064-03, /03L-0:on 820803,fire Doors 460 & 462 of 4-kV Switchgear Room Found Open W/Doors Blocked by Air Hose. Caused by Personnel Error.Hose Removed.Training Conducted & Need to Comply W/Posted Requirements Emphasized + (ML20063L916)
- LIC-94-0047, Comment on Draft NUREG-1482, Guidelines for IST Programs at Npps. Licensee Should Not Have to State in IST Program Methods of Ensuring Code Compliance,If Licensee Complying W/ Code + (ML20063L922)
- 05000244/LER-1982-018-03, /03L-0:on 820730,computer Alarm Received, Indicating RPI for Control Rod Bank a Group 2 Position HO2 Deviated from Control Rod Bank a by 12 Steps.Caused by Instrument Drift.Rpi Adjusted to Correct Drift + (ML20063L924)
- RC-94-0057, Comment Supporting NUREG-1488, Revised Livermore Seismic Hazard Estimates for 69 NPP Sites East of Rocky Mountains + (ML20063L925)
- 05000315/LER-1982-065-03, /03L-0:on 820804,containment Area Monitor R-2 Trip Alarm Setpoint Set Above Tech Spec Limits to Free Fuel Assembly Caught on Containment Upender Cable.Caused by Conscious Decision to Violate Tech Specs + (ML20063L927)
- 05000482/LER-1994-002, :on 940124,WCGS Entered TS 3.1.3.1 Action Statement (c)(4) Due to Electrical Problem W/Crdm M-12. Caused by Loose Cable Connector for CRDM M-12.Maint Performed on Connector + (ML20063L930)
- 05000336/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20063L931)
- ML20063L935 + (ML20063L935)
- 05000315/LER-1982-066-03, /03L-0:on 820805,surface Cracks Discovered in Two Portions of Divider Barrier Seal.Cause Could Not Be Determined.Affected Portions of Seal Replaced W/Uniroyal H300.Matl Replaced in Areas Similar to Cracked Areas + (ML20063L936)
- 05000315/LER-1982-067-03, /03L-0:on 820816,fire Door 373 Would Not Latch. Caused by Loose & Missing Screws.Screws Replaced/Tightened & Staked.Insp Procedure Changed to Require Staking of All Screws in Doors & Associated Hardware + (ML20063L938)
- 05000336/LER-1982-034-03, /03L-0:on 820801,while Performing Plant Heatup, Change from Mode 5 to Mode 4 Was Made W/O Performing Required Surveillance of Containment Personnel Airlock. Caused by Operator Error + (ML20063L941)
- 05000315/LER-1982-068-03, /03L-0:on 820817,4-kV Switchgear Room Cardox Sys Isolated W/No Names on Entry Board & No Personnel in Room. Caused by Personnel Error.Technician Had Erased Name But Failed to Return Carbon Dioxide Switch to Normal + (ML20063L946)
- ML20063L955 + (ML20063L955)
- JAFP-94-0116, Forwards Ja FitzPatrick Nuclear Power Plant Effluent & Waste Disposal Semiannual Rept Jul-Dec 1993 & Rev 0 to DVP-01.02, Radiological Effluent Controls & Odcm + (ML20063L957)
- ML20063L960 + (ML20063L960)
- ML20063L962 + (ML20063L962)
- 05000362/LER-1993-005, :on 931130,containment Isolation Valve 3HV6371 Failed to Open.Caused by Inverted Upstream Skirt.Valve Correctly Assembled,Tested & Determined Operable During Refueling Outage + (ML20063L970)
- ML20063L983 + (ML20063L983)
- ML20063L997 + (ML20063L997)
- ML20063M000 + (ML20063M000)
- ML20063M002 + (ML20063M002)
- ML20063M003 + (ML20063M003)
- ML20063M004 + (ML20063M004)
- ML20063M005 + (ML20063M005)
- ML20063M008 + (ML20063M008)