Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- JAFP-94-0062, 10CFR20.407 Rept for CY93 for Ja FitzPatrick Nuclear Power Plant,Consisting of Number of Individuals for Whom Personnel Radiation Monitoring Provided + (ML20063F303)
- ML20063F307 + (ML20063F307)
- ML20063F308 + (ML20063F308)
- 05000373/LER-1982-076-03, /03L-0:on 820727,during Reactor Core Isolation Cooling Calibr & Functional Test for Pressure Switches IE31-NO22 A,B & C,Trip Setpoints Found Below Tech Spec Limit.Caused by Setpoint Drift.Switches Will Be Monitored + (ML20063F315)
- NRC-94-4055, Reviews Rai,Dtd 940126-27,on AP600 for Proprietary Info & Finds No Proprietary Info Included + (ML20063F316)
- 05000346/LER-1982-006, Forwards LER 82-006/03L-1 + (ML20063F324)
- ML20063F325 + (ML20063F325)
- ML20063F334 + (ML20063F334)
- ML20063F336 + (ML20063F336)
- 05000373/LER-1982-066, Forwards LER 82-066/03L-0 + (ML20063F338)
- ML20063F344 + (ML20063F344)
- 05000346/LER-1982-006-03, /03L-1:on 820126,determination of Reportability Made Re 820113 Event.During Attempt to Start Component Cooling Water Pump 1-1,breaker AC113 Would Not Close.Caused by Worn Rack in Mechanism.Mechanism Replaced + (ML20063F346)
- ML20063F349 + (ML20063F349)
- ML20063F353 + (ML20063F353)
- 05000249/LER-1982-018, Forwards LER 82-018/03X-1 + (ML20063F355)
- ML20063F356 + (ML20063F356)
- RC-94-0024, Forwards Revised Basis for No Significant Hazards Determination for TS Change TSP 930017 Submitted by Ltr ,per 940125 Telcon.Rev Consists of Editorial Changes to Wording of Three Points Explained in Evaluation + (ML20063F359)
- ML20063F366 + (ML20063F366)
- ML20063F367 + (ML20063F367)
- 05000373/LER-1982-066-03, /03L-0:on 820722,reactor Core Cooling Sys Declared Inoperable Due to Leaks in Reactor Core Isolation Cooling Turbine Sys & Suspected Failure of Turbine Governor.Caused by Sys Being Inoperative for 2 Yrs.Oil Leak Repaired + (ML20063F375)
- ML20063F378 + (ML20063F378)
- ML20063F381 + (ML20063F381)
- 05000249/LER-1982-018-03, /03X-1:on 820414,during Refueling Outage Quarterly Valve Timing Per Procedure DOS 1600-1,nitrogen Inerting Stop Valve 3-1601-55 Closure Time Exceeded Tech Specs.Caused by Hardening of Internal Seals.Valve Actuator Replaced + (ML20063F389)
- ML20063F395 + (ML20063F395)
- ML20063F396 + (ML20063F396)
- 05000373/LER-1982-069, Forwards LER 82-069/03L-0 + (ML20063F407)
- ML20063F426 + (ML20063F426)
- ML20063F430 + (ML20063F430)
- 05000373/LER-1982-069-03, /03L-0:on 820722,drywell Pressure Was - 0.6 Psig Vacuum,Exceeding Tech Spec.Caused by Improperly Installed Steam Traps Downstream of Instrument Nitrogen Compressors. Traps Reinstalled + (ML20063F431)
- ML20063F444 + (ML20063F444)
- ML20063F449 + (ML20063F449)
- ML20063F458 + (ML20063F458)
- ML20063F461 + (ML20063F461)
- 05000373/LER-1982-073, Forwards LER 82-073/03L-0 + (ML20063F478)
- 05000373/LER-1982-073-03, /03L-0:on 820725,during Heatup for Startup Testing,Heatup Max Rate of 100 F/H Exceeded.Caused by Overdependence on CRT Ramp Rate Display.Operating Personnel Reminded to Use Multiple Indications + (ML20063F494)
- RBG-13-250, Final Deficiency Rept Re 10 Stainless Steel Forgings Delivered from Suspect Heat Lot.Initially Reported on 820304.Reinsp Uncovered No Matl Deficiencies.Deficiency Not Reportable Per 10CFR50.55(e) + (ML20063F505)
- ML20063F524 + (ML20063F524)
- B14741, Forwards ISI 1993 Outage Summary Rept of Millstone Unit 3 Nuclear Power Station for Interval 1,Period 2 + (ML20063F534)
- 05000301/LER-1982-006, Forwards LER 82-006/03L-0 + (ML20063F541)
- SNRC-2144, Forwards Vols 1-4 to Shoreham Decommissioning Project Termination Survey Final Rept. Twenty Proprietary Pages of Rept Withheld (Ref 10CFR2.790) + (ML20063F547)
- 05000301/LER-1982-006-03, /03L-0:on 820728,during Pipe Restraint Welding to Section of Chemical & Vol Control Sys Divert Line Piping, Pinhole Leak Developed in Pipe Adjacent to Weld.Caused by Welding Process.Hole Repaired & Hydrostatically Tested + (ML20063F550)
- ML20063F553 + (ML20063F553)
- ML20063F606 + (ML20063F606)
- 05000272/LER-1982-048, Forwards LER 82-048/03L-0.Detailed Event Analysis Encl + (ML20063F618)
- ML20063F622 + (ML20063F622)
- AECM-82-352, Informs of Appointment of DW Jones to Ms Power & Light Safety Review Committee,Replacing J Paulk,Who Resigned Because of Potential Conflict of Interest + (ML20063F624)
- ML20063F625 + (ML20063F625)
- 05000272/LER-1982-048-03, /03L-0:on 820724,inner Door Seal Leakage of 100 Ft Elevation Containment Air Lock Door Greater than Tech Spec. Caused by Personnel Closing Door W/Excessive Force.Seal Replaced & Personnel Trained in Proper Door Closing + (ML20063F626)
- 05000373/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20063F631)
- 05000373/LER-1982-078-03, /03L-0:on 820726,mgt Informed That 820721 Analysis Revealed Snubber RH04-1520S Installed Improperly.Caused by Fillet Weld Overlooked by Production & Qc.Missing Weld Discovered by Design Engineer & Repaired within 30 Days + (ML20063F634)
- ML20063F659 + (ML20063F659)