Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000301/LER-1982-002, Forwards LER 82-002/01T-0 + (ML20052G438)
- 05000335/LER-1982-012-03, /03L-0:on 820410,while Operating at 99% Power,W/ Charging Pump B Out of Svc,Charging Pump C Exhibited Low Flow & Declared Inoperable.Caused by Faulty Pump Internal Suction & Discharge Valves.Valves Replaced + (ML20052G440)
- ML20052G441 + (ML20052G441)
- 05000316/LER-1982-034-03, /03L-0:on 820412,during Normal Operation,Test of Control Room Emergency Ventilation Sys Found That Air Flow Was 7,370 Cfm for 2-ACRF-1.Caused by Lack of Procedure to Verify Airflow After Prefilter Changes.Procedure Modified + (ML20052G442)
- ML20052G443 + (ML20052G443)
- 05000344/LER-1982-006, Forwards LER 82-006/01T-0.Detailed Event Analysis Encl + (ML20052G444)
- 05000289/LER-1982-005, Forwards LER 82-005/03L-0 + (ML20052G446)
- ML20052G448 + (ML20052G448)
- 05000344/LER-1982-006-01, /01T-0:on 820426,17 Fuel Assemblies Found to Have Abnormal Clad Degradation.Caused by Water Jet Impingement & Induced Vibration on Fuel Rods.Fuel Assemblies Modified Using Stainless Steel Pins + (ML20052G449)
- 05000301/LER-1982-002-01, /01T-0:on 820428,during Eddy Current Exam, Discovered Abnormal Degradation in Fuel Cladding,Rcpb & Primary Containment.Seludge Lancing Will Be Performed + (ML20052G450)
- PNO-III-82-045, on 820511,plant Shut Down to Perform Maint to Repair Main Steam Line Drain Line Leakage in Reactor Containment Drywell & Repair Condensate Min Flow Valve. Leakage Not in Excess of Tech Spec Limits + (ML20052G451)
- 05000331/LER-1982-028, Forwards LER 82-028/03L-0 + (ML20052G452)
- ML20052G454 + (ML20052G454)
- ML20052G455 + (ML20052G455)
- PM-82-376, RO 50-321/1979-021:on 820423,tritium Levels Exceeded 3.0 E4 pCi/1 Allowance for Tritium in Environ Water Samples Per Table 3.2-3 of Ets.Cause Might Be Attributed to Slight Shifts in Main Body of Tritiated Groundwater + (ML20052G457)
- 05000289/LER-1982-005-03, /03L-0:on 820411,while in Ordered Shutdown,Liquid Effluent Radiation Monitor Discovered Inoperable.Caused by Failure of Pump SR-P4,due to Piping Clogged W/Mud.Piping Cleared & Motor Replaced + (ML20052G458)
- 05000324/LER-1982-065, Forwards LER 82-065/03L-0 + (ML20052G459)
- 05000324/LER-1982-065-03, /03L-0:on 820330,during Reactor Core Isolation Sys Isolation Channel Functional & Operability Test,Hpci Sys Automatically Isolated.Caused by Technician Inadvertently Lifting Terminal CC-19 Wire.Wire Reterminated + (ML20052G463)
- ML20052G464 + (ML20052G464)
- 1CAN058202, Advises of Error Made in NRC Providing 820302 Meeting Minutes Re Failed Fuel Investigations.Internal Clad Attack in Introduction Should Read External Clad Attack. First Paragraph Under Discussion & Conclusion Clarified + (ML20052G466)
- ML20052G467 + (ML20052G467)
- ML20052G468 + (ML20052G468)
- IR 05000409/1982004 + (ML20052G472)
- ML20052G473 + (ML20052G473)
- 05000327/LER-1982-050, Forwards LER 82-050/03L-0 + (ML20052G474)
- ML20052G478 + (ML20052G478)
- 05000327/LER-1982-050-03, /03L-0:on 820413,diesel Generator 1A.A Declared Inoperable When Power Fuses Blew in Control Circuitry.Caused by Broken Lead on Annunciator Horn Shorting to Case.Horn Replaced + (ML20052G479)
- ML20052G480 + (ML20052G480)
- ML20052G482 + (ML20052G482)
- 05000324/LER-1982-066, Forwards LER 82-066/03L-0 + (ML20052G483)
- 05000324/LER-1982-066-03, /03L-0:on 820407,control Rod Driveline Accumulator High Water Level Annunciation Received for Hydraulic Control Unit 30-43.Caused by High Water Level in Hydraulic Control Unit Due to Leakage Around Piston Seals.Water Level R + (ML20052G485)
- ML20052G486 + (ML20052G486)
- ML20052G487 + (ML20052G487)
- ML20052G488 + (ML20052G488)
- ML20052G489 + (ML20052G489)
- IR 05000275/1982007 + (ML20052G490)
- ML20052G493 + (ML20052G493)
- IR 05000206/1982010 + (ML20052G494)
- 05000321/LER-1982-044, Forwards LER 82-044/01T-0 + (ML20052G496)
- ML20052G498 + (ML20052G498)
- 05000321/LER-1982-044-01, /01T-0:on 820426,revolver & Ammunition Found in Vehicle During Search Prior to Exit from Protected Area. Security Officer Failed to Adequately Search Vehicle Prior to Entry Into Area.Officers Briefed on Searching Techniques + (ML20052G502)
- ML20052G504 + (ML20052G504)
- ML20052G505 + (ML20052G505)
- 05000269/LER-1982-010, Forwards LER 82-010/03L-0.Detailed Event Analysis Encl + (ML20052G506)
- A02345, Responds to NRC Re Violations Noted in IE Insp Rept 50-336/82-03.Corrective Actions:Worn Paper & Herculite Replaced W/New Herculite & Controls in Spent Fuel Pool Will Be Improved to Specify Clean Area for Storage + (ML20052G509)
- 05000269/LER-1982-010-03, /03L-0:on 820407,reactor Bldg Isolation Valve 1LWD-1 Failed to Close After Pumping Reactor Bldg Normal Sump.Apparently Caused by Dirty Contact in Valve Operating Motor Starting Compartment.Contact Cleaned + (ML20052G510)
- TXX-3519, Forward Revised Response to NRC Question 032.109 Re Steam Generator Level Control.Response Will Be Incorporated in FSAR Amend + (ML20052G512)
- ML20052G513 + (ML20052G513)
- ML20052G514 + (ML20052G514)
- 05000325/LER-1982-019, Forwards LER 82-019/03L-0 + (ML20052G516)
- 05000272/LER-1982-023, Forwards LER 82-023/03L-0.Detailed Event Analysis Encl + (ML20052G520)