- ML20027D265 + (ML20027D265)
- ML20027D266 + (ML20027D266)
- ML20027D267 + (ML20027D267)
- ML20027D268 + (ML20027D268)
- ML20027D273 + (ML20027D273)
- BSEP-82-2327, RO 1-82-112:on 821021,continuous Fire Watch Not Maintained as Required by Tech Spec 3.7.7.2.Caused by Misunderstanding on Part of Fire Watch.Fire Watch Established Until Sys Restored to Svc.Event Remains Under Investigation + (ML20027D274)
- PNO-II-82-115, on 821021 & 22,12 Contractor Employees Were Arrested by Sheriff of Burke County,Ga on Variety of drug-related Charges Involving Marijuana,Cocaine & Valium + (ML20027D275)
- ML20027D276 + (ML20027D276)
- ML20027D277 + (ML20027D277)
- ML20027D279 + (ML20027D279)
- 05000416/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20027D280)
- ML20027D281 + (ML20027D281)
- 05000295/LER-1982-031, Forwards LER 82-031/03L-0 + (ML20027D282)
- 05000416/LER-1982-078-03, /03L-0:on 821005,battery Surveillance Procedure 06-E1-1111-W-0001 Revealed Voltage on Div 1 Dc Supply to Be 121.7-volts Dc Resulting in Reduction in Electrical Reserves.Caused by Errors in Maint Instruction 07-S-12-45 + (ML20027D284)
- ML20027D286 + (ML20027D286)
- 05000295/LER-1982-031-03, /03L-0:on 820707,power Range Detectors Indicated Low by 46% of Span Nonconservatively,Changing Power Range High Flux Setpoints (25% & 109%).Caused by Miscalibr of Power Detectors.Detectors Readjusted + (ML20027D287)
- ML20027D289 + (ML20027D289)
- 05000335/LER-1982-043, Forwards LER 82-043/03L-0 + (ML20027D291)
- ML20027D292 + (ML20027D292)
- ML20027D294 + (ML20027D294)
- 05000259/LER-1982-078, Forwards LER 82-078/01T-0 + (ML20027D296)
- ML20027D297 + (ML20027D297)
- 05000335/LER-1982-043-03, /03L-0:on 820923,at 100% Power,T Hot Input to Subcooled Margin Monitor Became Erratic,Giving False Indication & Alarms.Cause Undetermined.Malfunction Cleared When Cover of Junction Box Removed + (ML20027D298)
- 05000366/LER-1982-104, Forwards LER 82-104/03L-0 + (ML20027D299)
- ML20027D300 + (ML20027D300)
- ML20027D302 + (ML20027D302)
- 05000366/LER-1982-104-03, /03L-0:on 820924,RHR Pump 2D Would Not Start W/Control Switch.Caused by Broken Relay Snap Ring in Pump Breaker.Ring Replaced & Breaker Tested Satisfactorily + (ML20027D303)
- 05000395/LER-1982-008, Forwards LER 82-008/03L-0.Detailed Event Analysis Encl + (ML20027D304)
- ML20027D305 + (ML20027D305)
- 05000325/LER-1982-102, Forwards LER 82-102/03L-0 + (ML20027D306)
- ML20027D307 + (ML20027D307)
- ML20027D308 + (ML20027D308)
- ML20027D310 + (ML20027D310)
- 05000395/LER-1982-008-03, /03L-0:on 820929,svc Water Pond Level Indication Not Verified for Modes 1,2,3 & 4 from 820922-29.Caused by Pond Level Entry Omitted from Operator Logs Due to Personnel Error.Logs Reviewed & Revised + (ML20027D311)
- ML20027D312 + (ML20027D312)
- PNO-II-82-114, on 821022,unit Achieved Initial Criticality. Actual Parameters Agreed W/Predicted Conditions.Licensee Will Issue News Release + (ML20027D313)
- 05000325/LER-1982-102-03, /03L-0:on 821003,source Range Monitor a Rendered Inoperable Due to Broken Detector Cable & Bent Drive Tube. Caused by Drive Control Switch Button Contacts Welded Closed & Moisture Accumulation on Cable Connector + (ML20027D314)
- IR 05000254/1982020 + (ML20027D315)
- ML20027D316 + (ML20027D316)
- 05000416/LER-1982-084, Forwards LER 82-084/03L-0 + (ML20027D317)
- ML20027D318 + (ML20027D318)
- ML20027D319 + (ML20027D319)
- ML20027D320 + (ML20027D320)
- 05000416/LER-1982-084-03, /03L-0:on 820929,control Room Indication Lost on Plant Chilled Water Auxiliary Bldg Isolation Valve 1P71F301 During Procedure 06-OP-1P71-Q-0001 Cycling.Caused by out-of- Adjustment Limit Switch.Switch Adjusted + (ML20027D321)
- 05000328/LER-1982-119, Forwards LER 82-119/03L-0 + (ML20027D322)
- ML20027D323 + (ML20027D323)
- 05000339/LER-1982-056, Forwards LER 82-056/03L-0 + (ML20027D324)
- ML20027D325 + (ML20027D325)
- 05000328/LER-1982-119-03, /03L-0:on 820927,during Mode 1 Operation & Performance of SI-166-1,containment Isolation Valve 2-FCV-30-17 Failed to Open.Caused by Open Coil in Valve Operator.Coil Replaced.Valve Returned to Svc + (ML20027D326)
- 05000339/LER-1982-056-03, /03L-0:on 820926,breaker for Chemical Addition Tank Train a Discharge Valve MOV-QS-202A Found in Off Position.Caused by Omission of Procedure When Securing Quench Spray Pump 2-QS-P-1A.Breaker Energized + (ML20027D327)