- 05000315/LER-1980-001-03, /03L-0:on 800123,while Performing Airlock Seal Leak Rate Testing,Inner Airlock Declared Inoperable.Caused by Broken Adjustment Bolt.Bolt Will Be Replaced During Next Unit Refueling Outage + (ML17326A530)
- 05000315/LER-1980-002-03, /03L-0:on 800125,during Normal Operation,Loop 3 T-average & delta-T Indication Decreased & Determined Inoperable.Caused by Resistance Temp Detector Producing Erroneous Temp Readings.Detector Was Replaced + (ML17326A531)
- 05000316/LER-1980-003, Forwards LER 80-003/03L-0 + (ML17326A534)
- ML17326A535 + (ML17326A535)
- 05000316/LER-1980-003-03, /03L-0:on 800124,during Surveillance Test,Turbine Driven Auxiliary Feed Pump Trip & Throttle Valve Unlatched. Caused by Burned Up Reset Coil on Trip & Throttle Valve Linkage.Linkage Not Engaging Due to Worn Mating Surfaces + (ML17326A536)
- ML17326A537 + (ML17326A537)
- ML17326A539 + (ML17326A539)
- 05000316/LER-1980-005-03, /03L-0:on 791113,re-evaluation of Calibr Data Taken During Last Refueling Outage Revealed That Steam Line Pressure Transmitter Data Would Result in Nonconservative Differential Steam Line Pressure Setpoint for Loops 3 & 4 + (ML17326A540)
- 05000316/LER-1980-006-03, /03L-0:on 800129,during Surveillance Test on Pressurizer Pressure Protection Set 3,discovered That Bistable 2 PB-457D Tripped at Value Exceeding Tech Specs. Cause Unknown.Bistable Set within Allowable Values + (ML17326A541)
- 05000316/LER-1980-007-03, /03L-0:on 800129,during Surveillance Test, Containment Isolation Valve NCR-252 Did Not Close Fully. Cause Unknown.New Diaphragm Placed in Valve Operator.Valve Restroked & Timed Before Returning to Svc + (ML17326A542)
- 05000316/LER-1980-004, Forwards LER 80-004/03L-0 + (ML17326A544)
- ML17326A545 + (ML17326A545)
- 05000316/LER-1980-004-03, /03L-0:on 800202,during Normal Operation,While Investigating Problem W/Test Circuit for B Main Turbine Stop Valve,Found Mounting Bracket for Proximity Switch Failed. Caused by Loosened Mounting Assembly Due to Vibration + (ML17326A546)
- ML17326A547 + (ML17326A547)
- ML17326A548 + (ML17326A548)
- ML17326A549 + (ML17326A549)
- ML17326A550 + (ML17326A550)
- ML17326A552 + (ML17326A552)
- 05000316/LER-1980-008, Forwards LER 80-008/03L-0 + (ML17326A553)
- ML17326A554 + (ML17326A554)
- 05000316/LER-1980-008-03, /03L-0:on 800201,review of 791102 Test Procedure Indicated as-found Data for Loop 1,channel 1,reactor Coolant Flow Transmitter Found 3.8% Out of Calibr.Caused by Transmitter Drift.Transmitter Recalibr + (ML17326A556)
- ML17326A557 + (ML17326A557)
- ML17326A558 + (ML17326A558)
- ML17326A559 + (ML17326A559)
- ML17326A561 + (ML17326A561)
- 05000316/LER-1980-009-03, /03L-0:on 800208,during Normal Operation,Steam Generator 3 Level Indication Became Erratic & Was Declared Inoperable.Caused by Faulty Transmitter.New Transmitter Installed + (ML17326A562)
- ML17326A563 + (ML17326A563)
- ML17326A564 + (ML17326A564)
- ML17326A565 + (ML17326A565)
- ML17326A566 + (ML17326A566)
- ML17326A572 + (ML17326A572)
- ML17326A573 + (ML17326A573)
- ML17326A574 + (ML17326A574)
- ML17326A575 + (ML17326A575)
- ML17326A576 + (ML17326A576)
- PNO-III-80-031A, on 800219,unplanned Radioactive Release Occurred Associated W/Reactor Trip/Loss of Offsite Power. Na-24 Tracer Added to Secondary Sys Escaped When Relief Valves Opened + (ML17326A577)
- ML17326A578 + (ML17326A578)
- ML17326A579 + (ML17326A579)
- ML17326A580 + (ML17326A580)
- ML17326A582 + (ML17326A582)
- ML17326A583 + (ML17326A583)
- ML17326A585 + (ML17326A585)
- 05000315/LER-1980-003, Forwards LER 80-003/03L-0 + (ML17326A587)
- ML17326A588 + (ML17326A588)
- 05000315/LER-1980-003-03, /03L-0:on 800219,found Spent Fuel Pit Area Monitor Indicating Erratically & High Radiation Alarm On.Caused by Bad Detector Tube.Detector Tube Replaced & Normal Operation Verified + (ML17326A589)
- ML17326A590 + (ML17326A590)
- ML17326A593 + (ML17326A593)
- ML17326A595 + (ML17326A595)
- ML17326A596 + (ML17326A596)
- ML17326A597 + (ML17326A597)