- 05000335/LER-1987-014-02, :on 871008,unidentified RCS Leakage Greater than Tech Spec Limit Discovered.Caused by Weld Joint Failure Due to Previous Misalignment of Listed Flanges.Reactor Shut Down & Required Repairs Performed + (ML17221A497)
- L-87-448, Responds to NRC 870610 Request for Addl Info Re TMI Item Ii.D I of NUREG-0737, Performance Testing of Relief & Safety Valves. Remaining Questions Will Be Addressed by 880205 + (ML17221A498)
- L-87-458, Informs That Response to Item 5 of Generic Ltr 87-12, Loss of RHR While RCS Partially Filled, Will Be Submitted by 880229 + (ML17221A499)
- L-87-457, Special Rept:On 871005,emergency Diesel Generator 2B Took Greater than 17 to Start Up & Load Onto Bus.Caused by Failure of Governor of Engines.Mechanical Section of Governor Replaced + (ML17221A500)
- L-87-455, Responds to NRC Ltr Re Exercise Weaknesses Noted in Insp Repts 50-335/87-19 & 50-389/87-18.Corrective Actions:Meeting Planned W/State Officials Re Possible Time Saving Measures & Emergency Plan Implementing Procedures Will Be Revised + (ML17221A501)
- 05000335/LER-1987-015-02, :on 871014,Mode 4 Entered W/O Shield Bldg Integrity.Caused by Inadequate Procedural Controls of Shield Bldg Doors Once Checked as Being Closed.Operating Procedure 1-0030120 Will Be Revised + (ML17221A502)
- ML17221A503 + (ML17221A503)
- ML17221A505 + (ML17221A505)
- L-87-477, Informs NRC That motor-operated Valve Testing Scheduled Completion Date of 871114,not Met.Valves Will Be Tested When Conditions Can Be Established During Startup from Cycle 3/4 Refueling Outage + (ML17221A506)
- L-87-469, Application for Amend to License DPR-67,changing Tech Specs Re Pump & Valve Program.Nrc Requested to Approve Amend by 880115 Since First 10-yr Insp Interval Ends 880211 + (ML17221A507)
- ML17221A508 + (ML17221A508)
- ML17221A509 + (ML17221A509)
- ML17221A511 + (ML17221A511)
- ML17221A512 + (ML17221A512)
- ML17221A514 + (ML17221A514)
- ML17221A515 + (ML17221A515)
- ML17221A516 + (ML17221A516)
- ML17221A518 + (ML17221A518)
- ML17221A519 + (ML17221A519)
- L-87-462, Application for Amend to License NPF-16,revising Tech Specs on Surveillance Requirements for MSIVs & Main Feedwater Isolation Valves.Fee Paid + (ML17221A520)
- ML17221A521 + (ML17221A521)
- ML17221A522 + (ML17221A522)
- ML17221A523 + (ML17221A523)
- ML17221A526 + (ML17221A526)
- L-87-482, Application for Amend to License NPF-16,incorporating Revised Pressure/Temp Limits & Results of Recent Low Temp Overpressure Protection Analysis.Nrc Approval Requested Prior to Plant Reaching 32 Efpys.Fee Paid + (ML17221A527)
- ML17221A528 + (ML17221A528)
- ML17221A530 + (ML17221A530)
- 05000335/LER-1987-016-02, :on 871029,reactor Tripped Due to Loss of Condensate Pump.Caused by Inadequate Operating Procedure. Procedure Being Revised.Plant Training Dept Will Review Loss of Condensate Pump + (ML17221A531)
- ML17221A532 + (ML17221A532)
- ML17221A534 + (ML17221A534)
- ML17221A536 + (ML17221A536)
- ML17221A538 + (ML17221A538)
- ML17221A539 + (ML17221A539)
- IR 05000483/2017404 + (ML17221A541)
- ML17221A543 + (ML17221A543)
- L-87-509, Discusses Status of Completion of Spds/Safety Assessment Sys Periodic Update.Ei Intl Hardware Design Finalized at End of Nov 1987 & Software Modules Continue to Be Integrated W/ Overall Sys Configuration + (ML17221A544)
- ML17221A547 + (ML17221A547)
- ML17221A548 + (ML17221A548)
- 05000389/LER-1986-011, :on 860709,emergency Diesel Generator 2A Taken Out of Svc Due to Failure to Meet Required Start Time.Caused by Excessive Tightening of Friction Clutch Locknut.Cooling Fan Shroud Removed & Fan Repositioned + (ML17221A549)
- L-87-512, Forwards Results of Nonradiological Confirmatory Measurements Samples Analyzed During Insp Rept 50-335/87-24 & 50-389/87-23,per Wj Ross Request.Part of Sample 86C Sent to Bnl.Results of Analysis Requested + (ML17221A550)
- L-87-514, Responds to Violations Noted in Insp Repts 50-335/87-21 & 50-389/87-20.Corrective actions:in-core Instrumentation Straightened & Acceptance Criteria Met Prior to Head Reassembly.Alignment Method Procedure Will Be Revised + (ML17221A551)
- ML17221A552 + (ML17221A552)
- ML17221A554 + (ML17221A554)
- L-87-538, Responds to NRC 871125 Request for Addl Info Re Util 870612 Proposed License Amend Re Replacement of Spent Fuel Pool Racks to Ensure That Sufficient Future Capacity Exists for Storage of Spent Fuel + (ML17221A556)
- L-87-535, Forwards Revised Response to Questions Re Spent Fuel Pool Rerack Design Analysis.Potential for rack-to-wall Impact Considered in Fuel Rack Models.Analysis of Pool Walls for Impact Loading Not Required + (ML17221A557)
- L-87-536, Responds to NRC 871023 Request for Addl Info Re Util 870612 Proposed License Amend to Permit Replacement of Spent Fuel Pool Racks to Ensure That Sufficient Future Capacity Exists for Storage of Spent Fuel + (ML17221A558)
- L-87-537, Forwards Revised Responses to Questions 2,6 & 7 Re Replacement of Spent Fuel Racks,Per NRC 870716 Request for Addl Info & Subsequent Discussions W/Util + (ML17221A560)
- L-87-526, Responds to Violations Noted in Insp Repts 50-335/87-27 & 50-389/87-26.Corrective Actions:All Personnel Instructed in Strict Adherence to Radiation Protection Procedures & Signs Posted Re Consequences of Not Following Procedures + (ML17221A561)
- 05000389/LER-1987-008-03, :on 871128,oil Fire Occurred at Reactor Coolant Pump (Rcp).Caused by Oil Leak from Loose Packing Gland on Instrument Isolation Valve.Leaking Valve Repaired.Visual Insp & Leak Test Conducted on 2A1 RCP Oil Pans + (ML17221A562)
- L-87-524, Application for Amend to License NPF-16,changing Action Statement for Tech Spec 3.7.1.6 to Allow 72 H to Restore Inoperable,Open Main Feedwater Isolation Valve.Safety Evaluation Determination of NSHC Also Encl.Fee Paid + (ML17221A563)
- ML17221A564 + (ML17221A564)