Semantic search

Jump to navigation Jump to search
 Issue dateTitleTopic
ML20045D90724 June 1993Special Rept:From 930511-0611,7 Fire Detectors in Circuit FLP3-3 Out of Svc for 32 Days.Caused by Failed Fire Detector.Detector Replaced & Containment Air Temps Monitored Hourly
ML20044G53728 May 1993Rev to 910925,1231 & 930731 Special Repts,Correcting Administrative Error in Equipment Designation of Passive Triaxial Peak Accelerograph.All Other Info Remains Unchanged
ML20024H30122 May 1991Special Rept:On 910412,loose Parts Detection Sys Declared Inoperable Due to Repetitive Spurious Alarms & Inoperable pre-amplifier Unit.Loose Parts Monitoring Troubleshooting Currently Under Review
ML20043F8258 June 1990Special Rept:On 890425,gas Sample Drawn from PASS Indicated Reactor Gases Not Removed from Liquid Sample Rcs.Four RCS Liquid Samples Successfully Obtained & Two of 4 Samples Produced RCS Dissolved Gas Samples
ML20042G8917 May 1990Special Rept:On 900408,pressurizer Spray Valve Failed Open Causing Depressurization of Rcs.Caused by Equipment Malfunction.Feedback Arm Holding Screw on Pressurizer Spray Valves Replaced W/Longer Screws & Secured W/LocknutsUnanalyzed Condition
ML20006C21423 January 1990Special Rept:On 900102,radiation Monitor Removed from Svc & 7-day Time Allowed Exceeded During Calibr.Replacement Detector on Order Since Nov 1989 & Will Be Replaced & Recalibr
ML20005G1282 January 1990Supplemental Special Rept:On 890716,2 of 12 Loose Parts Monitor Channels Declared Inoperable When Monitors Alarmed Continuously.Caused by Malfunctions in Equipment Inside Containment Bldg.Replacement Scheduled for Next OutageHigh Radiation Area
ML19351C73411 December 1989Special Rept:On 891110,turbine Electrical Trip Solenoid Valve Failed to Meet Surveillance Acceptance Criteria. Caused by Particulate Contamination in Secondary or Electronic Trip Valves.Valves Replaced W/Rebuilt ValvesDownpower
ML20024D02515 July 1983Ro:On 830421,following Preliminary Manual Test Insertion (Mti)Test,Actuation Module Lights Came on Due to Module Energizing.Cause Unknown.Operators Stationed to Mitigate Problems or Actuation If Mti RequiredBoric Acid
ML20052D77729 April 1982Ro:On 820415,steam Generator 1 Increased Primary to Secondary Leakage Rate of 0.049 Gpm from Valve.Cause of Leak Rate Unknown.Increase Appears to Be Related to Plant Shutdowns/Trips Experience in Thermal Cycling
ML20050A00818 March 1982RO Re Steam Generator Tube Plugging as Specified in Tech Spec 4.4.5.1.4.Degradation Resulting in Tube Plugging Is Characterized by Localized Areas of Small Pits on Tube Outside Diameter.Investigation of Corrosion Cause Continues
ML20040F60929 January 1982RO:30-day Rept & 10-day Rept Per App B ETS Re Excessive Liquid Waste Discharge & Excessive Level of Radioactivity.Caused by Steam Generator Primary Side to Secondary Side Leakage.Doses within Bases for 2.5 Ci Limit
ML20039E04028 December 1981RO 50-336/81-41:discovered Abnormal Degradation of Reactor Coolant Sys Pressure Boundary,Specifically,Steam Generator Tubes.Frequency of Occurrence Primarily on Cold Leg Side. Two-wk Rept Will Be Submitted
ML19350F13317 June 1981RO 50-336/81-20:Dresser Industries Model 31739A Safety Valves Found to Have Less than Min Upstream Inside Diameter. Caused by Facility Design.Significant Impact Unlikely
ML20004E3615 June 1981RO 81-018/03L-0:insp of safety-related Pipe Hangers Inside Containment Containing Mechanical Snubbers Revealed Snubbers Installed on Small Diameter Piping.Caused by Listing Not Including Review of Diameter Piping
ML20003B64917 February 1981RO 50-336/81-8:as-built Hanger Review of Reactor Vessel Head Vent Piping Sys Determined Spring Can Type Hanger Was Installed Incorrectly,Resulting in Overstressing Socket Welded Joint.Spring Can Hanger Removed
ML20002D63613 January 1981Ro:On 801209,inservice Insp Revealed That Required Valve Operability Tests Not Performed During Third Calendar Quarter 1980.Valves Successfully Tested.Action Taken to Assure Timely Review of Valve Test DataStroke time
ML19330C0201 August 1980RO 80-26:water Seal for Piping Penetration in Refueling Water Storage Tank Pipe Tunnel Does Not Meet Design Requirements.Plugged Yard Storm Drain Caused Water Backup. Repairs to Water Seal Will Be Evaluated
ML19323C3579 May 1980RO 50-336/80-18:during Ongoing Hanger Base Plate Analysis Required by IE Bulletin 79-02,discovered That Several Svc Water Support Hangers Did Not Provide Factor of Safety Greater than Two.Repair Work on 12 Hangers Is Underway
ML19294B67723 January 1980Ro:On 791229,loss of Main Control Board Annunciators Occurred.Fourteen Power Supplies That Are Paralleled to Provide Voltages for Annunciator Electronics,Lamps & Field Contacts Failed.Surveillance Implemented
ML19275A27525 September 1979RO 50-336/79-27:during Engineering Review,Section of 4-inch Cast Iron Floor Drain Piping Passing Each Station Battery Was Found Not Supported in Accordance W/Design.Drain Working & Ductwork Removed