o f-o o

A NORTHEASTBrrILrrIEs

~

3

?,O72%?W:::"

O Cfyfo%'*countcr\\cui ostat,

~

! C":P""::l."l ?l"" ***"

m ses-sett L

x A

C :,2,",:,X?:::::

~

y.

q March 18, 1982 MP-2-5096 a

n.

s e-f D,

Mr. Ronald C. Haynes Regional Administrator, Relion I f

(,

Office.of Inspection and, Enforcement E

.-rer-e g D

'U'.S. Nuclear Regulatory Commission a

631 Park Avenue '

5..g Gj982W -10

~

. King,of. Prussia, Pennsylvania 19406 m-margau be Referencef Facility Operating License No. DPR-65.

//

8 -

Dock'et No.' 50-336-w

~

r

- (

De'ar Mr. Haynes:

c. -

e This letier is submitted pursuant to Millstone Unit 2 Appendix A

'g,

Te'chnicai Specification Section 4.4.5.1.5.A, Report of Steam Generator Tube Pl.ugging.

^

Re

'Ni' min accordance ewith Technical Specification Section 4.4.5.T.4, all-steam

.,[

generator stubes with degradation'in excess of the plugging limit were u

. remobed,froni service by plygging.

Four tubes in Steam Generator No.1

'were removed from seFvice because:they were cut to allow removal of tube samples for investigation of the cause of degradation.

Four tubes would no pass a 0.540 inch diameter e y current probe'. A total of 425 tube (were plugged in., Steam Genera @ tor No. I and 284 tubes in Steam s

j

-Generator No72:

~

The degradation which,r'sulted in tube plugging is chgracterized by

,[

localizqdareasofsmQ1pitsonthetubeoutsidediameter.

Investigation of the causes of this corrosion is continuing. A final report of the

~

results of this investigation.and the, corrective actions proceeding from it will be provid'i.

Yours truly, NOR HEAST NUCLEAR ENERGY COMPANY IJ.Mroczka'l

~

Station Superintendent Millstone Nuclear Power Station D

EJM/JJK:mo cc: Director, Office of Inspection and Enforcement Washington, D.C.

0203290537 020310 f6gp PDH ADOCK 03000336 0

PDH

$0