ML21125A316

From kanterella
Jump to navigation Jump to search
5 to Updated Final Safety Analysis Report, Chapter 9, Tables
ML21125A316
Person / Time
Site: Palisades 
Issue date: 04/14/2021
From:
Entergy Nuclear Operations
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21125A344 List: ... further results
References
PNP 2021-008
Download: ML21125A316 (73)


Text

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-1 Revision 34 Page 1 of 2 SERVICE WATER SYSTEM FLOW REQUIREMENTS (gpm)(3)

Normal Shutdown DBA Operation Operation Operation Component Name (Nominal)

(Nominal)

SW = 85°F Critical Service Water Header Containment Air Coolers 2000-7500 2000-7500 4800(7)

CCW Heat Exchangers(2)

<6000

<6000 4214(8) 4286(12)

Engineered Safeguards Room Coolers 400(4) 400(4) 70(9)

Emergency Diesel Generators 214(10)

Control Room Air Conditioning 12(5) 12(5) 39(11)

Instrument Air Compressors (C-2A, C-2C) 16 16 16(14)

Alternate to Replenish SFP(13) 40 Noncritical Service Water Header(6)

Hydrogen Coolers 2610(1)

Exciter Air Coolers 370(1)

Turbine Lube Oil Coolers 2510(1)

Seal Oil Cooler 125 EHC Oil Coolers(5) 20 Isophase Bus Cooler(5) 35 Instrument Air Compressor C-2B Aftercooler 8

8 Main Feedwater Pump Lube Oil Cooler 78 Main Feedwater Pump Gland Cooler 40 Heater Drain Pump Cooling 50 Blowdown Heat Exchanger (E-31)60-420 Circ Water and Intake Basin Chlorinator 50 50 Hydrogen Dryer 2

Cooling tower Pump Seal and Bearing Water 95 Makeup Raw Water Supply (Intermittent) 150-500 150-500 Condensor Vacuum Pump 10 Aux Building Addition Air Conditioning Unit 28.8 28.8 Ventilation Equipment Room Air Cooling Unit 28.8 28.8 Radwaste Area Compressor 20 20 Auxiliary Building Condensing Unit 130 130 FWP Air Compressor 65.2 65.2 C-42 Panel and Sample Coolers 84 FWS Sample Cooler SCI-0710-C (to M-97(B))

40 Condensate Pumps 16 CD Bldg Boiler Sample (measured) Cooler 1.6 1.6 Radiation Monitors 10

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-1 Revision 34 Page 2 of 2 SERVICE WATER SYSTEM FLOW REQUIREMENTS (gpm)(3)

NOTES:

(1)-

Flow is temperature controlled.

(2)-

DBA Requirement for Post-RAS mode only, flow is temperature controlled prior to RAS.

(3)-

The flows listed for DBA operation are required flows at that SW temperature, the actual flow to each component is set periodically by Technical Specification Surveillance Test RO-216, which balances the system flows.

(4)-

SW flows continuously to the ESGR Coolers. There is minimum heat load in the rooms during normal operation and slightly more heat load (SDC System) during shutdown operation. The 400 gpm is not a cooling requirement but is the approximate indicated flow.

(5)-

Only one unit (or set of coolers) is operated at one time.

(6)-

Flows listed here are from original Bechtel figures and have not been verified.

(7)-

EA-LOCA-2001-01, Rev 1, Total of 4800 gpm to VHX-1,2,3 in D/G 1-1 failure case.

(8)-

EA-LOCA-2001-01, Rev 1, Total of 4214 gpm to both E-54A,B in D/G 1-2 failure case.

(9)-

EA-D-PAL-93-272F-01 Rev 1.

(10)- EA-EC28106-03 Rev 0 and EA-EC28106-04 Rev 0.

(11)- EA-D-PAL-93-272E-02 Rev 0.

(12)- EA-LOCA-2001-01, Rev 1, Total of 4286 gpm to E-54A,B in D/G 1-1 failure case.

(13)- Provisions exist to allow the Service Water System to replenish the Spent Fuel Pool (SFP) if SFP inventory is used as makeup to the Primary Coolant System in the event that the Safety Injection Refueling Water (SIRW) Tank is unavailable (see Section 1.8.5).

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-2 Revision 32 Page 1 of 2 SERVICE WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Service Water Pumps Type Vertical Turbine With Water Lubrication Number 3

Capacity (Each) 8,000 gpm*

Head 140 ft*

Pump Accelerating Time 4 Seconds @ 70% Voltage Material Bowls Cast Iron or Cast Steel or Cast Stainless Steel Discharge Head Carbon Steel Bowl Shaft 416 SS Line Shaft 1045 CS or 416 SS Discharge Column Carbon Steel Impeller Bronze or Stainless Steel Motor 350 hp, 3 Ph, 60 Hz, 2,300 V Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM The FSAR requirement of 8000 gpm and 140 ft of head is a design characteristic that was supplied to the vendor for individual pump performance.

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-2 Revision 32 Page 2 of 2 SERVICE WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

2.

Basket Strainers Type Simplex Multi-Basket Number 3

Design Flow (Each) 9,000 gpm Design Pressure 150 psig Design Temperature 70F Screen Mesh 3/16 in Perforation Material Body Cast Steel Baskets 304 SS

3.

Piping, Fittings and Valves Material Carbon Steel, Bronze, Stainless Steel, or Cast Iron & Ductile Iron (non-safety related only)

Design Pressure 100 psig Design Temperature 300F Piping and Fittings(a) 2-1/2 in and Larger - Butt-Welded Except at Flanged Equipment(a) 2 in and Smaller - Socket Welded Except at Flanged Equipment or Threaded Valves(a) 2-1/2 in and Larger - Butt-Welded 150 lb(a) 2 in and Smaller - Socket Welded 600 lb or Threaded 200 lb or Flanged 150 lb Class Code ASA B31.1-1955 ASA B16.5-1961 (a) These are considered to be classified as flanged equipment.

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 23 Page 1 of 4 REACTOR PRIMARY SHIELD COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Shield Cooling Coils Length (Each Coil)

Approx 24 ft Spacing of Coils 9 in Center-to-Center Number of Coil Sections in Each Set 3

Coil Diameter 3/4 in Material Seamless Carbon Steel Design Pressure 75 psig Design Temperature 220°F Code ASA B31.1

2.

Shield Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 2

Capacity (Each) 154 gpm TDH 79 ft Material Case Cast Iron Impeller CD4MCU (Stainless Steel)

Shaft Stainless Steel (Solid)

Motor 7.5 hp, 3 Ph, 60 Hz, 460 V, 1750 r/min Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 23 Page 2 of 4 REACTOR PRIMARY SHIELD COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3.

Shield Cooling Heat Exchanger Type Horizontal Counterflow, Shell With Straight Tubes Rolled Into Fixed Tube Sheets Number 1

Original Design Duty 200,000 Btu/h Original Heat Transfer Area 77 ft2 Shell Side Tube Side Design Pressure 150 psig 125 psig Design Temperature 200°F 200°F Fluid Component Shield Cooling Cooling Water Water Temperature In 90°F 100°F Temperature Out 93.2°F 96.8°F Material Shell Carbon Steel Tubes Admiralty Channels Carbon Steel Tube Sheets Aluminum Bronze Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW-2 (a);

TEMA Class C

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 23 Page 3 of 4 REACTOR PRIMARY SHIELD COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

4.

Shield Cooling Surge Tank Type Vertical Number 1

Design Pressure 50 psig Design Temperature 200°F Volume 1,700 Gallons (Based on Total Change in System Water Volume as a Result of Maximum Possible Change in Water Temperature From a Cold Start Condition at 60°F to 212°F)

Material Carbon Steel Code ASME B&PV Code Section III, Class C and ASME B&PV Code,Section VIII, Par UW-2 (a)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 23 Page 4 of 4 REACTOR PRIMARY SHIELD COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

5.

Piping, Fittings and Valves Material Seamless Carbon Steel Design Pressure 125 psig Design Temperature 360°F Not Embedded in Embedded in Concrete Concrete Construction Pipe, 2-1/2 in and Larger Butt-Welded Except None at Flanged Equipment Pipe, 2 in and Smaller Screwed Except at Socket Flanged Equipment Welded Valves, 2-1/2 in and Larger Cast Iron, None Flanged 125#

Valves, 2 in and Smaller Bronze, Screwed None 200# and Carbon Steel, flanged 150#

Code ASA B31.1

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-4 Revision 25 Page 1 of 1 COMPONENT COOLING SYSTEM HEAT LOADS (x 106 Btu/hr)

  • With containment high pressure
    • Maximum heat load at 7 days after shutdown = 12.5 for 1/3 core off load
      • An additional Post-RAS heat load of up to 0.09X106 Btu/hr could exist if LPSI pumps are used for post accident. However, LPSI pumps are not normally operating Post-RAS.
        • Heat load with P-50D being one of the two operating primary coolant pumps. heat load would be 1.15x106 Btu/hr if P-50D is not one of the two operating pumps.

Shutdown Cooling DBA Component and (Number)

Normal Initial

+30 h SI Post-RAS*

Shutdown Cooling HXs (2) 147.39 46.13 95 (max)

(max)

Primary and Auxiliary Systems Sample Cooling Coils (9) 0.3 0.15 Negligible Letdown HX (1) 11.8 1.54 Negligible 11.8 CRDM Seal Coolers (45)

.07

.07

.07

.07 Charging Pumps (3) 0.20 0.12 0.12 0.20 0.20 Primary Coolant Pumps (4) 2.47 1.32****

2.47 LPSI Pumps (2) 0.09 0.09 0.09 HPSI Pumps (2) 0.11 0.11 Containment Spray Pumps (3) 0.08 Spent Fuel Pool HX (1) 9.2 9.2 9.2**

Reactor Shield Cooling HX (1) 0.2 0.2 0.2 0.2 Waste Gas Compressors (3) 0.01 0.01 0.01 Vacuum Degasifier Pump Seal Water Cooler (1) 0.08 0.08 0.08 Radwaste Evaporators (2) 23.52 11.76 11.76 Total 47.85 171.93 67.66 14.77 95.39

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 27 Page 1 of 4 COMPONENT COOLING WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Component Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 3

Capacity (Each) 6,000 gpm (Based on Shut-down Cooling Requirements),

Including Approximately 10%

Wear Margin Head 164 ft Material Case Carbon Steel Impeller Bronze Shaft Alloy Steel Temperature Transient Designed To Withstand Increase of 25°F in 1-1/2 Minutes. This May Occur When System Switches to Shutdown Cooling or Post-DBA Cooling From Normal Operation.

Motor 300 hp, 3 Ph, 60 Hz, 2,300 V Time Required To Accelerate Pump to Full Speed at 70% Voltage 4 s Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 27 Page 2 of 4 COMPONENT COOLING WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

2.

Component Cooling Heat Exchangers Type Horizontal, Counterflow, Shell Straight Tubes, Tubes Rolled Into Tube Sheets Number 2

Original Design Duty (Each) 50.5 x 106 Btu/h (Normal) 94.8 x 106 Btu/h (At Start of Shutdown Cooling) 43.2 x 106 Btu/h (24 Hours After Shutdown Cooling) 85.0 x 106 Btu/h (Post-DBA)

Original Heat Transfer Area (Each) 7,840 ft2 Shell Side Tube Side Design Pressure 150 psig 125 psig Design Temperature 200°F 200°F Design Capacity (Each) 4700 gpm (Ref 13 and 14)

Temperature Transient Designed To Withstand Increase of 25°F in 1-1/2 Minutes.

This May Occur When System Switches to Shutdown Cooling or Post-DBA Cooling From Normal Operation.

Material Shell Side Carbon Steel, Firebox Quality Tube Side Admiralty Tube Sheet Carbon Steel With Aluminum Bronze Overlay Codes ASME B&PV Code,Section III, Class C, 1965 and ASME B&PV Code,Section VIII, Par UW-2 (a); TEMA Class C

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 27 Page 3 of 4 COMPONENT COOLING WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3.

Surge Tank Type Vertical Number 1

Design Pressure/Temperature 25 psig @ 140°F Design Temperature 140°F Volume 1,230 Gallons (Based on Total Change in System Water Volume as Result of Maximum Possible Change in Water Temperature From Cold Start Conditions at 60°F to 140°F)

Material Carbon Steel Code ASME B&PV Code,Section III, Class C, 1965

4.

Piping, Fittings and Valves Piping Material Carbon Steel, Seamless and Seam Welded (Seam Weld 100% Radiographed)

Design Pressure 150 psig Design Temperature 165F

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 27 Page 4 of 4 COMPONENT COOLING WATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Inside Outside Containment Containment Construction Pipe, 2-1/2 in and Larger Butt-Welded Except Butt-Welded at Flanged Equipment, Except at 10% of Circumferen-Flanged tial Welds Examined Equipment by Radiography Pipe, 2 in and Smaller Socket Welded Screwed Except-Except Flanged at Flanged Equipment Equipment Valves (Except Butterfly),

Carbon Steel, Cast Iron, 2-1/2 in and Larger Butt Weld Flanged Ends, 150#

Ends, 125#

Butterfly Valves, Carbon Steel, Carbon Steel, 2-1/2 in and Larger Flanged Ends, 150#

Flanged Ends, 150#

Valves, 2 in and Smaller Carbon Steel, Socket

Bronze, Welded Ends, Screwed 600#

Ends, 200#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-6 Revision 31 Page 1 of 1 COMPONENT COOLING SYSTEM REQUIRED FLOW RATES (GPM)

Shutdown Cooling DBA Component and (Number)

Normal Initial

+30 h SI Post-RAS*

Shutdown Cooling HXs (2) 5,000 5,000 4480 Primary and Auxiliary System Sample Cooling Coils (9) 20 20 20 Letdown HX (1)**

1,000 (max) 70 1,000 (max)

CRDM Seal Coolers (45) 68 68 68 68 Charging Pumps (3) ###

32 22-32 22-32 32 32 Primary Coolant Pumps (4) ###

410 230 230 410 LPSI Pumps (2) #

8 8

8 8

8 HPSI Pumps (2) #

29 29 29 29 29 Containment Spray Pumps (3) #

24 24 24 24 24 Spent Fuel Pool HX (1) ***

650 650 650***

Shield Cooling HX (1) 126 126 126 126(a)

Waste Gas Compressors (3) 6 6

6 Vacuum Degasifier Pump Seal Water Cooler (1) 8 8

8 Radwaste Evaporators (2) 2,136 1,068 1,068 Total 4,517

    1. 7,329
    1. 7,259 1,697 4573
  • With containment high pressure, loss of EDG 1-1/EDG 1-2.
    • Flow set by temperature control
      • Increases to 1334 gpm at 7 days after shutdown for 1/3 core off load.
        • These values are for bounding heat loads. (Reference 73, 74)
  1. The required flow rates are based on operation of the pumps under the worst case conditions. Actual flow requirements to prevent component degradation will vary upon operating conditions.
    1. Total flow rate assumes 22 gpm for charging pumps.
      1. Charging Pumps P-55B and P-55C can operated up to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> without cooling water flow to the oil coolers. Reference 36.
        1. CCW flowrate for P-50A, B & C is 90 gpm. CCW flowrate for P-50D is 140 gpm.

(a) This component still receives cooling water flow in an SI System alignment. However, there is no minimum flow requirement as the component is not required to function during a DBA.

(Reference 29)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 22 Page 1 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Fuel Pool Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 2

Capacity (Each) 1,700 gpm TDH 64 ft Temperature Transient Designed To Withstand an Increase from 60F to 212F in 5 Seconds Material Stainless Steel Motor 40 hp, 460 V, 60 Hz 3 Ph, Code Motor, NEMA; Pump, Standards of Hydraulic Institute

2.

Spent Fuel Pool Cooling Heat Exchange Unit Type Horizontal Counterflow, With Straight Tubes Rolled Into Tube Sheets Number 2 Shells in Series Original Duty (Total) 23 x 106 Btu/h Original Heat Transfer Area 4,080 ft2 Component Cooling Water Temperature: In/Out 90/115F Spent Fuel Cooling Water Temperature: In/Out 125/110F Temperature Transient Designed To Withstand an Increase From 60F to 212F in 5 Seconds

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 22 Page 2 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Material Shells Carbon Steel Tubes Stainless Steel Tube Sheets Stainless Steel With SS 308L Weld Overlay Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a);

TEMA Class C

3.

Fuel Pool Recirculation Booster Pump Type Horizontal Centrifugal With Mechanical Seals Number 1

Capacity 160 gpm TDH 160 ft Temperature Transient Designed To Withstand Increase From 60F to 212F in 5 Seconds Material Type 316 Stainless Steel Motor 15 hp, 3 Ph, 60 Hz 460 V Code Motor, NEMA; Pump, Standards of Hydraulic Institute

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 22 Page 3 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

4.

Fuel Pool Filter Type Cartridge With Replaceable Filter Element Number 1

Design Flow 150 gpm Design Pressure 200 psig Design Temperature 250F Temperature Transient Designed for Increase From 60F to 212F in 5 Seconds Filter Rating 25 Microns Nominal Material Stainless Steel Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a)

5.

Fuel Pool Demineralizer Type Mixed Bed Number 1

Design Flow 150 gpm Design Pressure 200 psig Design Temperature 220F Temperature Transient Design for an Increase From 60F to 212F in 5 Seconds Resin Equivalent Capacity Mixture of Nuclear Grade Cation and Anion Material Type 304 Stainless Steel for Vessel and Integral Parts

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 22 Page 4 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a)

6.

Piping, Fittings and Valves Material Stainless Steel Design Pressure 125 psig Design Temperature 150F Joints, 2 in and Larger ButtWelded Except at Flanged Equipment 1-1/2 in and Smaller Socket Welded Except at Flanged Equipment Valves, 2 in and Larger Stainless Steel, Butt Weld Ends, 150#

11/2 in and Smaller Stainless Steel, Socket Weld Ends, 150#

Butterflies, All Sizes Stainless Steel Flanged, 150#

Code ASA B31.1 Welds 100% Radiographically Checked

7.

Spent Fuel Pool Volume of Empty SFP Cavity 21,885 ft3 Volume of Empty North Tilt Pit Cavity 4,095 ft3

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 33 Page 1 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Instrument Air System

a.

Air Compressors Type Rotary Screw, Oil Free, Air Cooled Number 3

Design Capacity (Each) 288 scfm Design Pressure 125 psig Main Motor (Compressor) 75 hp, 3 Ph, 60 Hz, 460 V Fan Motor 5 hp, 3 Ph, 60 Hz, 460 V Code Motor, NEMA

b.

Aftercoolers

1.

Type Shell and Tube Number 3 (1 per Compressor)

2.

Type Cooling Coil Number 3 (1 per Compressor - onboard)

c.

Air Receivers Type Vertical Number 3

Design Pressure 125 psig Capacity 57 ft3 Code ASME B&PV Code,Section VIII

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 33 Page 2 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

d.

Air Dryer Type Silica Gel Absorbent, Electric Heater Reactivated Number 1

Capacity 205 scfm Outlet Moisture Content With Saturated Air Inlet

-40°F Dew Point at 100 psig Code ASME B&PV Code,Section VIII

e.

Piping and Valves Upstream of Dryer Carbon Steel Piping and CI, or Bronze Valves Downstream of Dryer Copper Piping and Bronze or Stainless Steel Valves Except at Containment Penetration and at Isolation Valves (Carbon Steel)

Code ASA B31.1

2.

High Pressure Air System

a.

Air Compressors Type Single Acting, Air Cooled Number 3

Design Capacity (Each) 22.3 scfm Design Pressure 325 psig Motor 10 hp, 440 V, 3 Phase Code Motor, NEMA

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 33 Page 3 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

b.

Air Dryer Type Desiccant Number 3 (1 per Compressor)

Capacity (Each) 35 scfm Dewpoint

-40 °F at 350 psig Code ASME B&PV Code,Section VIII

c.

Air Receivers Type Horizontal Number 3 (1 per Compressor)

Design Pressure 350 psig Capacity 60 ft3 Code ASME B&PV Code,Section VIII

d.

Aftercoolers Number 3 (1 per Compressor)

Type Air Cooled

e.

Piping Material Carbon Steel Code ASA B31.1 (Seismic Class I Supported From Receivers to Operators on Engineered Safe-guards Systems)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 33 Page 4 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3.

Feedwater Purity Air System

a.

Air Compressors Type Two stage air screw, oil free Number 2

Design Capacity (Each) 297 scfm Design Pressure 117 psi Motor 75 hp, 460 V, 3 Phase Air Dryer (Integral to Compressor)

Type Refrigerant Power Consumption (at full load) 1.6 kW Pressure 102 psig Dew Point 37.4°F @ 68°F/100% RH

c.

Aftercooler Number 2

Type Air Cooled

d. Receiver Type Vertical Number 1

Design Pressure 150 psig Design Temp 100°F Capacity 1060 gal Code ASME B&PV Code,Section VIII

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 33 Page 5 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

4. Nitrogen Backup Stations
a.

Nitrogen Bottles Pressure (nominal) 2400 psig

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 1 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

Primary Coolant System CV-0101 Flange Leak Drain C

C CV-0155 Quench Tank Spray C

C Chemical and Volume Control System CV-2009 Letdown Containment Isolation C

C CV-2083 PCP Bleedoff Containment Isolation C

C CV-2099 PCP Bleedoff Containment Isolation C

C CV-2111 Charging Line Stop O

O CV-2113 Loop 1A Charging Line Stop O/C O

CV-2115 Loop 2A Charging Line Stop O/C O

CV-2117 Pressurizer Auxiliary Spray O/C C

CV-2130 Boric Acid Recirculation Control C

C CV-2136 Boric Acid Recirculation Control C

C CV-2155 Makeup Stop C

C CV-2191(g)

PCP Bleedoff Relief Stop O

C Safety Injection, Containment Spray and Shutdown Cooling CV-3001(b)

Containment Spray Isolation O/C/T O

CV-3002(b)

Containment Spray Isolation O/C/T O

CV-3003 SI Tank Fill and Drain C

C CV-3004 SI Tank Fill and Drain C

C CV-3006 Shutdown HX Bypass O

O CV-3018(a)(f)

HPSI Pump Dischg (Redundant)

C C

CV-3025 Shutdown HX Discharge C

C CV-3027(a)(b)

Pump Mini-Flow Stop O/C As Is CV-3029(c)

Containment Sump Suction O/C As Is CV-3030(c)

Containment Sump Suction O/C As Is

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 2 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

CV-3031(c)

SIRW Tank Isolation O/C As Is CV-3036 HPSI Dischg (Redundant)

O O

CV-3037(a)

HPSI Dischg (Normal)

C C

CV-3038 SI Line Pressure Control C

C CV-3039 SI Tank Fill and Drain C

C CV-3040 SI Tank N2 Supply C

C CV-3042 SI Line Pressure Control C

C CV-3043 SI Tank Fill and Drain C

C CV-3044 SI Tank N2 Supply C

C CV-3046 SI Line Pressure Control C

C CV-3047 SI Line Pressure Control C

C CV-3048 SI Tank N2 Supply C

C CV-3050 SI Tank N2 Supply C

C CV-3051 SI Tank Purge C

C CV-3055(a)

LPSI Pump Dischg Crossover C

As Is CV-3056(a)(b)

Pump Mini-Flow Stop O/C As Is CV-3057(c)

SIRW Tank Isolation O/C As Is CV-3059(a)

HPSI Dischg (Normal)

O O

CV-3063 SI Tank Purge C

C CV-3065 SI Tank Purge C

C CV-3067 SI Tank Purge C

C CV-3069 Check Valve Leakage Drain C

C CV-3070(b)

Cooled Suction HPSI Pump O/C C

CV-3071(b)

Cooled Suction HPSI Pump O/C C

CV-3084 HPSI Hot Leg Drain Isolation C

C CV-3085 HPSI Hot Leg Drain Isolation C

C CV-3212 Shutdown HX Isolation O

As Is CV-3213 Shutdown HX Isolation O

As Is CV-3223 Shutdown HX Isolation O

As Is CV-3224 Shutdown HX Isolation O

As Is

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 3 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

Feed and Condensate System CV-0701 Feedwater Regulating Valve C

As Is CV-0703 Feedwater Regulating Valve C

As Is CV-0727(b)

Auxiliary Feed Control O/C O

CV-0734 Main Feedwater Bypass C

As Is CV-0735 Main Feedwater Bypass C

As Is CV-0736 Auxiliary Feed Control Bypass C

C CV-0736A(h)

Auxiliary Feed Control O/C O

CV-0737 Auxiliary Feed Control Bypass C

C CV-0737A(h)

Auxiliary Feed Control O/C O

CV-0749(b)

Auxiliary Feed Control O/C O

CV-2008(h)

Primary Sys Makeup Tank Outlet O

C CV-2010(h)

Condensate Storage Tank Inlet O/C C

Service Water System CV-0821 CCW Heat Exchanger Temp Control C

C CV-0822 CCW Heat Exchanger Temp Control C

C CV-0823 Component Cool HX Dischg O

O CV-0824(b)

Return From Containment Coolers O/C O

CV-0825 Eng Safe Room Cooler Supply O

O CV-0826 Component Cool HX Dischg O

O CV-0844 Critical Service Wtr Header Iso O

O CV-0845 Critical Service Wtr Header Iso O

O CV-0846 Critical Service Water Header Cross Connect O

O CV-0847(b)

Supply to Containment Coolers O

O CV-0857 Critical Service Water Header Cross Connect O

O CV-0861 8" Return From Cont Coolers O

O CV-0862 Containment Cooler Supply O

O CV-0864 8" Return From Cont Coolers O

O

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 4 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

CV-0865 Containment Cooler Supply O

O CV-0867 8" Return From Cont Coolers O

O CV-0869 Containment Cooler Supply C

C CV-0870 Containment Cooler Supply O

O CV-0873 8" Return From Cont Coolers O

O CV-0876 Diesel Generator Cool Supply O

O CV-0877 Diesel Generator Cool Supply O

O CV-0878 Eng Safe Room Cooler Supply O

O CV-0879 Backup Cool Safeguards Pumps C

C CV-0880 Backup Cool Safeguards Pumps C

C CV-0884 Diesel Generator Cool Supply O

O CV-0885 Diesel Generator Cool Supply O

O CV-1318 Service Water Pump Header Iso O

O CV-1319 Service Water Pump Header Iso O

O CV-1359 Noncritical Service Water Header Isolation C

C CV-1655 Control Room HVAC Service Water O

O CV-1656 Control Room HVAC Service Water O

O Component Cooling System CV-0910(g)

Component Cool to Cont Isolation C

O CV-0911(g)

Component Cool From Cont Isolation C

O CV-0913 Supply Safeguards Pumps O

O CV-0915 Comp Cool Surge Tank Vent C

C CV-0937 Supply to Shutdown HX O

O CV-0938 Supply to Shutdown HX O

O CV-0940(g)

Component Cool From Cont Isolation C

O CV-0944 Supply to Radwaste Evaporator C

C CV-0944A Supply to Spent Fuel HX C

C CV-0945 Supply to Comp Cool HX O

O CV-0946 Supply to Comp Cool HX O

O

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 5 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

CV-0947 Supply to Safeguards Pumps O

O CV-0948 Supply to Safeguards Pumps O

O CV-0949 Supply to Safeguards Pumps O

O CV-0950 Return From Safeguards Pumps O

O CV-0951 Return From Safeguards Pumps C

C CV-0977B Return From Radwaste Evaporator C

C Main Steam, Main and Auxiliary Turbine Systems CV-0501(g)

Main Steam Isolation Valve C

C CV-0510(g)

Main Steam Isolation Valve C

C CV-0522B(b)

Steam to Aux Feed Pump Turbine O/C C

CV-0738 Steam Generator Recirculation C

C CV-0739 Steam Generator Recirculation C

C CV-0767 Steam Generator Bottom Blowdown C

C CV-0768 Steam Generator Bottom Blowdown C

C CV-0770 Steam Generator Bottom Blowdown N

C CV-0771 Steam Generator Bottom Blowdown N

C CV-0779(e)

Atmospheric Steam Dump C

C CV-0780(e)

Atmospheric Steam Dump C

C CV-0781(e)

Atmospheric Steam Dump C

C CV-0782(e)

Atmospheric Steam Dump C

C Instrument Air Systems and Miscellaneous Gas CV-1211(b)

Instrument Air to Containment N

O CV-1358 Nitrogen to Containment C

C Process Sampling System CV-1910 PCS Sampling Isolation C

C

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 33 Page 6 of 6 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety After Loss No Valve Description Position of Air O

Open C

Closed T

Throttled N

No Safety Related Function Position (a) Air supplied by high-pressure air system.

(b) Nitrogen bottle backup.

(c)

Air supplied from high-pressure air system with backup from instrument air.

(e) Bulk nitrogen backup.

(f)

Manually operated air bottle backup.

(g) Accumulator installed.

(h) Handwheels credited for safety position.

CV-1911 PCS Sampling Isolation C

C Radioactive Waste Treatment System CV-1001 Primary System Drain Tank Recirc C

C CV-1002 Primary System Drain Tank Outlet C

C CV-1004 Degasifier Pump Discharge C

C CV-1007 Primary System Drain Tank Outlet C

C CV-1036 Pump P-70 Inlet C

C CV-1037 Clean Waste Tank Recirc C

C CV-1038 Pump P-70 Inlet C

C CV-1044 Pump P-69 A/B Suction C

C CV-1045 Pump P-69 A/B Suction C

C CV-1064 Clean Waste Tank Vent C

C CV-1065 Clean Waste Tank Vent C

C CV-1101 Waste Gas Surge Tank Vent C

C CV-1102 Waste Gas Surge Tank Vent C

C CV-1103 Containment Sump Drain C

C CV-1104 Containment Sump Drain C

C Shield Cooling System CV-0939 Shield Cooling Tank Inlet C

C

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 34 Page 1 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

1.

Cable Spreading Rm, Col M-28 1

Water Flow Sw (WFS-2B)

2.

1-D Switchgear Rm, Col G-28; Col G-22; Col G-22 4

Water Flow Sw (WFS-2B1, WFS-2B2, WFS-2B3, WFS-2D)

3.

1-1 Diesel Generator Rm, Col J-28 1

Water Flow Sw (WFS-2G1)

4.

1-2 Diesel Generator Rm, Col M-28 1

Water Flow Sw (WFS-2G2)

5.

Turbine Bldg 590', Col H-9 1

Water Flow Sw (WFS-2I)

6.

Control Room (Room 325) 8 Smoke

7.

Control Room Adj Offices Rms 324 & 320 2

Smoke

8.

Cable Spreading, Room 224 13 Smoke

9.

Refueling & Spent Fuel Area, Rm 220 4

Smoke

10.

1-D Switchgear Rm, Rm 223 9

Smoke

11.

North Penetration, Rm 332 2

Smoke

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 34 Page 2 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

12.

1-C Switchgear Rm, Rm 116A 2

Smoke

13.

Southwest Cable Penetration, Rm 250 2

Smoke

14.

Engineered Safeguards Panel Area, Rm 121 3

Smoke

15.

Stairwell Outside Engineered Safeguards Panel Area, Rm 016 2

Smoke

16.

Component Cooling Pump, Rm 123 2

Smoke

17.

Safeguard Area, Rm 4 3

Smoke

18.

Safeguard Area, Rm 5 2

Smoke

19.

Corridor 106 on 590' Elevation, Rm 106 6

Smoke

20.

Charging Pump, Rm 104 2

Smoke

21.

Containment, Interior North Penetration Area, Rm 332 3

Smoke

22.

Containment, Interior SW Penetration Area, Rm 141, 250 3

Smoke

23.

Containment Instrument Air Room 3

Smoke

24.

Auxiliary Feed Pump Room 570' Level of Turbine Bldg, Rm 007 3

Smoke

25.

Battery Rm 225A 1

Smoke

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 34 Page 3 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

26.

Battery Rm 225B 1

Smoke

27. HVAC Equipment Rooms & Chase:

West Mechanical Equipment Room 300 East Mechanical Equipment Room 300A Duct Chase, Rm 300B 1

1 1

Smoke Smoke Smoke

28. Air Handling Unit V-95 & V-96 Inlet Ducts, Rm 300, 300A 2

Smoke

29. Electrical Equipment Room, Rm 725 6

Smoke

30. Technical Support Center, Rm 320A 2

Smoke

31. Intake Structure, Room 136 11 Ultraviolet
32. Charging Pump Rooms 104, 104A, and 104B 1

Water Flow Sw (WFS-2J)

33.

Diesel - Driven Auxiliary Feedwater Pump Shed 2

Fire & Flame Det.

1 Water Flow Sw

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 24 Page 1 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Fire Pump, Motor Driven Type Vertical Turbine Number 1

Capacity 1,500 gpm Discharge Pressure 125 psig Material Discharge Head Cast Iron Impeller Bronze Motor 150 hp, 460 V, 3 Ph, 60 Hz Codes Underwriters Lab Label Motor, NEMA; Pump, Standards of Hydraulic Institute

2.

Fire Pump, Diesel Engine Driven Type Vertical Turbine Number 2

Capacity 1,500 gpm Discharge Pressure 125 psig Material Discharge Head Cast Iron Impeller Bronze Gear Drive Reduction Ratio 1:1, 200 hp Rating Diesel Engine 150 hp Codes Underwriters Lab Label Diesel Engine, NEMA; Pump, Standards of Hydraulic Institute

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 24 Page 2 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3.

Fire System Jockey Pump Type Vertical Turbine Number 1

Capacity 50 gpm Discharge Pressure 117 psig nominal Material Discharge Head Fabricated Steel Impellers Bronze Motor 7-1/2 hp, 460 V, 3 PH, 60 Hz Codes Motor, NEMA; Pump Standards of Hydraulic Institute

4.

Piping, Fittings and Valves

a.

To Auxiliary Feedwater Pump Suction Header and Critical Service Waterlines Material Seamless Carbon Steel Design Pressure 125 psig Design Temperature 100°F Construction Butt-Welded Except at Flanged Equipment Valves Carbon Steel, Butt-Weld Ends, 150#,

or Cast Iron, Flanged End, 175#,

Underwriters lab Label

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 24 Page 3 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

b.

To Spent Fuel Pool Blind Flange and Normal Fire Protection Service Underground Aboveground Material Original-Cast Iron Carbon Steel (150# Class)

Replacement-Ductile Iron (350# Class)

Design Pressure 150 psig 125 psig Design Temperature 100°F 100°F Construction Original-Mechanical Joint Butt-Welded Except at Flanged Equipment Replacement-Push-on Joint Valves Original-Cast Iron, Cast Iron, Flanged Mechanical Joint, End, 175#,

175#, Underwriters Underwriters Lab Lab Label Label Replacement-Ductile Iron, Mechanical Joint, 250#, UL Listed, FM Approved

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 34 Page 1 of 5 AUXILIARY FEEDWATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1.

Motor-Driven Auxiliary Feedwater Pump (P-8A)

Type Horizontal Centrifugal, With Packed Glands Number 1

Capacity 415 gpm Head 2,730 ft Material Case 4.6% Chrome Alloy Steel Impeller Bronze Shaft 11%-13% Chrome Alloy Steel Motor 450 hp, 3 Ph, 60 Hz, 2,300 V Codes Motor, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

2.

Turbine-Driven Auxiliary Feedwater Pump (P-8B)

Type Horizontal Centrifugal, With Packed Glands Number 1

Capacity 415 gpm Head 2,730 ft Material Case 4.6% Chrome Alloy Steel Impeller Bronze Shaft 11%-13% Chrome Alloy Steel

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 34 Page 2 of 5 AUXILIARY FEEDWATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Turbine Single Stage, Axial Flow, Exhaust to Atmosphere, 450 hp Codes Turbine, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

3.

Motor Driven Auxiliary Feedwater Pump (P-8C)

Type Horizontal Centrifugal, With Mechanical Seals Number 1

Capacity 330 gpm Head 2260 ft Material Case 18 Cr, 8 Ni Stainless Steel Impeller 12 Cr Stainless Steel Shaft 12 Cr, 0.6 Mo Stainless Steel Motor 400 hp, 3 Ph, 60 Hz, 2,300 V Codes Motor, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

4.

Piping and Valves for P-8A, P-8B, and P-8C

a.

Pump Suction Underground Aboveground Material 304 Stainless Steel Carbon Steel Design Pressure 50 psig 50 psig (Minimum)

Design Temperature 100°F 100°F (Minimum)

Construction Welded Except at Flanged Equipment Connections

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 34 Page 3 of 5 AUXILIARY FEEDWATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 150#

Valves 2-1/2 in and Smaller Carbon Steel, Socket Welded, 600#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

b.

Pump Discharge Underground Aboveground Material 304 Stainless Steel Carbon Steel Upstream Downstream of FW of FW Control Control Valve Valve Design Pressure 1,440 psig 1,337psig 1,100psig (Minimum)

Design Temperature 100°F 100°F 100°F (Minimum)

Construction Welded Except at Flanged Equipment Only Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 600#

Valves 2-1/2 in and Smaller Carbon Steel, Socket Welded, 600#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 34 Page 4 of 5 AUXILIARY FEEDWATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

c.

Auxiliary Turbine Steam Supply Design Pressure 1,000 psig Design Temperature 550°F Piping and Valves Same as for Aboveground Pump Discharge Piping

5.

Diesel-Driven Auxiliary Feedwater Pump (P-8D)

Type Horizontal Centrifugal, with Mechanical Seals Number 1

Capacity 510 gpm Head 3148 ft Diesel Engine (K-17) 800 hp, Starter with Storage Batteries Codes NFPA 20, NFPA 37, UL 1247

6.

Piping and Valves for P-8D

a.

Pump Section Underground Aboveground Material 304 Stainless Steel Carbon Steel Design Pressure 150 psig 150 psig Design Temperature 130oF 130oF Construction Welded Except at Flanged Equipment Connections Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 150#

Valves 2-1/2 in and Smaller Carbon Steel, Butt-Welded, 600#

Code ASA B31.1 1-2012 for procurement ASA B31.1 1-1973 for qualification

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 34 Page 5 of 5 AUXILIARY FEEDWATER SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

b.

Pump Discharge Underground Aboveground Material 304 Stainless Steel Carbon Steel Design Pressure 1,750 psig Upstream Downstream (Minimum) of Control of Control Valve Valve 1,750 psig 1,200 psig Design Temperature 34/120oF 34/120oF 34/120oF Construction Welded, Except Flanged at Material Transition Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 900#

Valves 2-1/2 in and Smaller Carbon Steel, Butt-Welded, 1500#

Code B31.1 (1973)

B31.1 (1973)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-13 Revision 31 Page 1 of 2 DESIGN BASIS AMBIENT CONDITIONS HVAC Original Design Winter, °F Summer, °F EEQ Average Arrhenius Temp. (°F)

(Ref. 70 except as noted)

(Note 6)

Location Outside Inside Outside Inside Maximum Bulk Air Temperature (°F)

Allowed During Normal Operation (Ref. 70, except as noted)

Normal Operation Cold Shutdown Turbine Building Operating Floor (EEQ Harsh Area)

-10 50 95 104 130 110 80 Auxiliary Feedwater Pump Room (EEQ Harsh Area) 104 104 90 Piping Area (EEQ Harsh Area)

-10 50 95 110 130 110 80 Shops and Offices

-10 65 95 104 Auxiliary Building (Non-EEQ Harsh Areas)

Radwaste Area and Radwaste Area Addition

-10 50 95 110 Fuel Handling Area and Fuel Handling Area Addition

-10 50 95 104 Office Area

-10 75 95 75 Room 116 (1-1 Diesel Generator Room) (Note 8) 102 (Ref. 65 & 66)

Room 116B (1-2 Diesel Generator Room) (Note 8) 102 (Ref. 65 & 66)

Auxiliary Building (EEQ Harsh Areas)

Room 123 (590 Component Cooling) (Note 3)

-10 50 95 104 110 100 100 Room 238 (607-6 Containment Purge Exhaust) (Note 3)

-10 50 95 104 145 115 105 Room 338 (625 Containment Purge Air Fan) (Note 3)

-10 50 95 104 150 130 110 Room 001 (Dirty Waste Tank T-60) 90 90 90 Room 004 (East Engineered Safeguards) (Note 4) 90 90 90 Room 005 (West Engineered Safeguards) 95 (Ref. 64) 90 90 Room 106 (590 Corridor) 100 90 90 Room 118 (590 Receiver Tank and Pump Room) 100 90 90 Room 120 (Degasifier Vacuum Pumps) 100 90 90 Room 121A (South Pipeway Doghouse) (Note 4) 125 110 110 Room 121B (Hydrogen Monitor EC-161) 100 90 90 Room 150 (602 Pipeway) 110 92 92

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-13 Revision 31 Page 2 of 2 DESIGN BASIS AMBIENT CONDITIONS HVAC Original Design Winter, °F Summer, °F EEQ Average Arrhenius Temp. (°F)

(Ref. 70 except as noted)

(Note 6)

Location Outside Inside Outside Inside Maximum Bulk Air Temperature (°F)

Allowed During Normal Operation (Ref. 70 except as noted)

Normal Operation Cold Shutdown Containment Building (EEQ Harsh Area) (Note 1)

-10 50 95 104 140 (Note 5)

(Note 2)

(Note 2)

Control Room (Non-EEQ Harsh Area) (Note 7)

-10 75 95 75 Condensate and Makeup Demineralizer Building -

Non-EEQ Harsh Areas Process and Equipment Area

-10 50 90 104 Covered Receiving and Loading Area

-10 50 90 104 Boiler Room

-10 50 90 104 Pipe Gallery

-10 50 90 104 Instrument Room

-10 75 90 90 Note 1:

Original equipment design was based on these conditions. To allow for elevated service water temperatures a higher building design temperature was specified for the containment air coolers. Chapter 14 contains containment temperature assumptions for analyzed accident situations.

Note 2:

Temperatures are dependent on elevation and location (References 71 and 72).

Note 3:

Rooms 123, 238 and 338 have a design temperature of 120°F per M-391, Specification for Installation of Ventilation Equipment and Ductwork Penetration and Fans Rooms.

Note 4:

The combined East Engineered Safeguards and South Pipeway Doghouse room can be maintained less than or equal to 135°F post-accident with the initial temperatures in room 004 and room 121A at 95°F (Reference 70).

Note 5:

Reference FSAR Section 14.18. The Technical Specifications restrict bulk air temperature to 140°F (LCO 3.6.5).

Note 6:

Maximum allowed post-accident temperature profiles in EEQ harsh areas outside containment are maintained by the EEQ program.

Note 7:

The relative humidity in the control room is 50%.

Note 8:

Actual rooms can be maintained less than or equal to 120°F with a diesel generator operating with the initial room temperature and outside air temperature of 102°F (Ref. 65).

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 30 Page 1 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA NOTE: All electrical equipment is Class 1E unless otherwise noted.

Makeup/Recirculation Air Filter Units Quantity Two - 100% Capacity Each Capacity 3,200 ft3/min Filters (per Filtering Unit)

Prefilter Quantity 3

Media Glass Fiber or Knitted Pad HEPA Filter Quantity 3 Upstream Filters 3 Downstream Filters Media Glass Fiber Charcoal Filter Trays Quantity 18 [2 Banks of 9]

Media Activated Carbon, 4 in. Bed Depth (Two-2 inch deep Trays in Series)

Fan Type Vaneaxial Fan Static Pressure at Rating, in wg 10 in Motor 20 hp, 460 V, 3 Ph Filter Test Efficiency HEPA 99.97% of Particulate Carbon Adsorber 99.9% of Elemental Iodine Electric Heating Coil Type Nickel/Chromium Capacity 15 kW, 480 V, 3 Ph Air Filter Unit Assembly P of wg 8.00 in (Maximum)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 30 Page 2 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA NOTE: All electrical equipment is Class 1E unless otherwise noted.

Air Handling Unit V-95 or V-96 Type Package (Filter, Cooling Coil, Fan)

Capacity 12,500 ft3/min Cooling Coil Type Direct Expansion Refrigerant Capacity (Total) 603,500 Btu/h Heating Coil (Nonclass 1E)

Type 80% Nickel and 20% Chromium Capacity 177 kW, 480 V, 3 Ph Fan Type Centrifugal Total Pressure, wg 3.85 in Motor 25 hp, 460 V, 3 Ph Filter Type, Media 6 in Thick Moderate Efficiency Prefilter P of wg (Clean) 0.25 in Refrigerant Condensing Unit Type Water-Cooled Reciprocating Refrigerant R-22 Compressor Type Reciprocating, 4 Cylinder Motor 60 hp, 460 V, 3 Ph Capacity 554,400 Btu/h @ 85 °F, 39 gpm Service Water Condenser Water Flow Set per RO-216

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 30 Page 3 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA NOTE: All electrical equipment is Class 1E unless otherwise noted.

Smoke Purge Exhaust Fan V-94 (Nonclass 1E)

Type Vaneaxial Capacity 7,800 ft3/min Motor 7-1/2 hp, 460 V, 3 Ph Exhaust Fan V-16 (Existing)

(Nonclass 1E)

Type Centrifugal Capacity 160 ft3 /min Motor 1/12 hp, 120 V, 1 Ph Humidifiers VH-12 and VH-13 (Nonclass 1E)

Type Steam Generator Capacity 50 lb/h (17 kW, 480 V, 3 Ph)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 1 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air Control Room (see Figure 7-24)

D-1 Normal Outside Air -

Open - Train A Open - Train A Close on CHP or Close Train A Close - Train B Close - Train B CHR D-2 Normal Outside Air -

Modulate - Train A Modulate - Train A Close on CHP or Close Train A Close - Train B Close - Train B CHR D-3 Normal Recirc Air -

Open Open Open on CHP or Open Train A CHR D-4 Supply Air Back Open - Train A Open - Train A Open - Train A NA Draft Dampers -

Close - Train B Close - Train B Close - Train B (Back Draft)

Train A on CHP or CHR D-5 Charcoal Filter Unit Close Close Open - Train A NA Supply Air - Train A Close - Train B (Back Draft) on CHP or CHR D-6 Charcoal Filter Unit Close Close Open - Train A Open Return Air - Train A Close - Train B on CHP or CHR

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 2 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air D-7 Charcoal Filter Unit Close Close Open - Train A, NA Outside Air -

(Manual Close (Elect Op Train A Avail) Close -

FAI)

Train B on CHP or CHR D-8 Normal Outside Air -

Open - Train B Open - Train B Close on CHP Close Train B Close - Train A Close - Train A or CHR D-9 Normal Outside Air -

Modulate - Train B Modulate - Train B Close on CHP or Close Train B Close - Train A Close - Train A CHR D-10 Normal Recirc Air -

Open Open Open on CHP or Open Train B CHR D-11 Supply Air Back Open - Train B Open - Train B Open - Train B NA Draft Damper -

Close - Train A Close - Train A Close - Train A (Back Draft)

Train B on CHP or CHR D-12 Charcoal Filter Unit Close Close Open - Train B NA Supply Air -

Close - Train A (Back Draft)

Train B on CHP or CHR

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 3 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air D-13 Charcoal Filter Unit Close Close Open - Train B Close Return Air -

Close - Train A Train B on CHP or CHR D-14 Charcoal Filter Unit Close Close Open - Train B, NA Outside Air -

(Manual Close (Elect Op FAI)

Train B Avail) Close -

Train A on CHP or CHR D-15 Purge Fan Isolation Close Close Close on CHP or Close CHR D-16 Purge Fan Isolation Close Close Close on CHP or Close CHR D-17 Exhaust Fan V-16 Open Open Close on CHP or Close Isolation CHR D-18 Exhaust Fan Open Open Close on CHP or Close Isolation CHR D-19 Number Not Used

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 4 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air D-20 Charcoal Filter Flow Open Open Modulate - Train A Open Control - Train A Open - Train B on CHP or CHR D-21 Charcoal Filter Flow Open Open Modulate - Train B Open Control - Train B Open - Train A on CHP or CHR Radioactive Waste Area and Engineered Safeguards Rooms PO-3010 Fresh Air Supply Open Open Close on Trip of Close Fan V-10 PO-1809 Radwaste Area Supply Open Open Close (RE-1809)

Close PO-1839 Radwaste Area Open Open Close on Trip of Close Exhaust Fan V-14A PO-1840 Radwaste Area Open Open Close on Trip of Close Exhaust Fan V-14B PO-1817 East Safeguards Open Open Close (RE-1810)

Close Room Supply PO-1810 East Safeguards Open Open Close (RE-1810)

Close Room Exhaust

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 5 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air PO-1812 West Safeguards Open Open Close (RE-1811)

Close Room Supply PO-1811 West Safeguards Open Open Close (RE-1811)

Close Room Exhaust Auxiliary Building Addition Radwaste Area Ventilation System PO-8006 Fresh Air Supply Open Open Close on Trip of Close Fan V-67 PO-8016A Radwaste Add Open Open Close on Trip of Close Exhaust Fan V-68A PO-8016B Radwaste Add Open Open Close on Trip of Close Exhaust Fan V-68B

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 6 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air Fuel Handling Area Damper PO-3007 is normally open during reactor operation or reactor shutdown and fails closed on loss of instrument air.

Auxiliary Building Addition Fuel Handling Area Ventilation System PO-8001 Fresh Air Supply Open Open Close on Trip of Close Fan V-69 PO-8013A Fuel Handling Add Open Open Close on Trip of Close Exhaust Fan V-70A PO-8013B Fuel Handling Add Open Open Close on Trip of Close Exhaust Fan V-70B Penetration and Fan Rooms Heating and Ventilation System PO-8035 Outside Air Supply Open Open Close (RIA-5710)

Close PO-8036 Exhaust Open Open Close (RIA-5710)

Close

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 21 Page 7 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Shutdown Position Auto Actuation Loss of Air Containment CV-1813 Air Space Purge Close Open Close on CHP or Close Supply CHR CV-1814 Air Space Purge Close Open Close on CHP or Close Supply CHR CV-1806 Cont Purge Exhaust Close Open Close on CHP or Close CHR CV-1805 Cont Purge Exhaust Close Open Close on CHP or Close CHR CV-1808 Cont Purge Exhaust Close Open Close on CHP or Close CHR CV-1807 Cont Purge Exhaust Close Open Close on CHP or Close CHR

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-16 Revision 23 Page 1 of 1 SAMPLING STATIONS NSSS Sampling Station Containment Hydrogen Monitoring System Turbine Analyzer Panel Radwaste Sampling Station Waste Gas Sample Panel Radwaste Addition Sampling System

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-17 Revision 23 Page 1 of 2 SAMPLE POINT

SUMMARY

1.

NSSS Sample Station Pressurizer Vapor Phase Grab Sample, Bomb Pressurizer Liquid Phase Grab Sample, Bomb Primary Coolant Hot Leg Grab Sample, Bomb Quench Tank Liquid Phase Grab Sample, Bomb Quench Tank Vapor Phase Grab Sample, Bomb Purification Ion Exchange Inlet Grab Sample Purification Filters Outlet Grab Sample LPSI Pumps Discharge Grab Sample Purification Ion Exchange Outlet Grab Sample SI Drain Tank Grab Sample Containment Spray Pumps Discharge Grab Sample SIRW Tank Recirculation Grab Sample HPSI Pumps Discharge Grab Sample

2.

Radwaste Sampling Station Primary System Drain Tank Recirc Grab Sample Equipment Drain Tank Recirc Grab Sample Vacuum Degasifier Pump Discharge Grab Sample Receiver Tank Pumps Discharge Grab Sample Receiver Tank Circ Pumps Discharge Grab Sample Radwaste Demin Tanks Outlet (3)

Grab Sample Treated Waste Mon Tanks Recirc (2)

Grab Sample Controlled Chem Lab Drain Tank Grab Sample Filtered Waste Monitor Tank Recirc Grab Sample Dirty Waste Drain Tank Recirc Grab Sample Component Cooling Pumps Discharge Grab Sample

3.

Turbine Analyzer Panel Steam Generator Blowdown (2)

Grab Sample, Conductivity, pH, Sodium, Hydrazine Feedwater Heater Train (2)

Grab Sample, Conductivity, pH, Oxygen, Sodium, Hydrazine Condensate Pumps Discharge (2)

Grab Sample, Conductivity, pH, Oxygen, Sodium, Hydrazine Heater Drains Discharge (2)

Grab Sample, pH Primary Storage Tank Grab Sample, Conductivity, pH, Sodium Condensate Pump P-11 Discharge Grab Sample, Conductivity, pH, Sodium Blowdown Demineralizer (3)

Grab Sample

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-17 Revision 23 Page 2 of 2 SAMPLE POINT

SUMMARY

4.

Waste Gas Sample Panel Volume Control Tank Bomb Waste Gas Surge Tank Bomb Waste Gas Decay Tanks (6)

Bomb Spurt Resin Storage Tank Bomb

5.

Radwaste Addition Sampling System Radwaste Polishing Demineralizer Discharge Grab Sample, Conductivity Clean Waste Transfer Pump Discharge Grab Sample Clean Waste Distillate Pump Discharge Grab Sample Misc Waste Distillate Pumps Discharge (2)

Grab Sample Misc Waste Demineralizer Tank Discharge (2)

Grab Sample, Conductivity (1)

Misc Waste Transfer Pumps Discharge (2)

Grab Sample Misc Waste Filter Inlet Grab Sample Misc Waste Filter Discharge (2)

Grab Sample Primary System Makeup Water Pump Discharge Grab Sample Utility Water Transfer Pump Discharge Grab Sample Spurt Resin Storage Tank Gas Bomb Waste Gas Decay Tanks (3)

Bomb Radwaste Evaporator Distillate (2)

Grab Sample

6.

Containment Hydrogen Monitor Containment Atmosphere (2)

% Hydrogen

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 1 of 14 1.1 General CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Normal Letdown Flow 40 gpm Normal Purification Flow Rate 40 gpm Normal Charging Flow 44 gpm Primary Coolant Pump Controlled Bleedoff (4 Pumps) 4 gpm Normal Letdown Temperature at Loop 547.8F Normal Charging Temperature at Loop 425F Ion Exchanger Operating Temperature 120F 1.2 Regenerative Heat Exchanger - E-56 Quantity 1

Type Shell and Tube, Vertical Normal Heat Transfer 6.6 x 106 Btu/h Code ASME B&PV Code,Section III, Class C, 1965 Shell Side (Charging)

Fluid Primary Coolant, 1 Wt % Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design)

Design Pressure 2,735 psig Design Temperature 650F Material Stainless Steel

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 2 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Tube Side (Letdown)

Fluid Primary Coolant, 1 Wt %

Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design)

Design Pressure 2,485 psig Design Temperature 650F Material Stainless Steel Operating Parameters - Regenerative Heat Exchanger Maximum Unbalanced Maximum Charging With Maximum Unbalanced Normal Heat Transfer Purification Letdown Tube Side (Letdown)

Flow - gpm 53 53 160 160 Inlet Temp - F 547.8 547.8 547.8 547.8 Outlet Temp - F 251 160 319 449 Shell Side (Charging)

Flow - gpm 43 133 123 33 Inlet Temp - F 120 120 120 120 Outlet Temp - F 416 246 367 523 Heat Transfer - Btu/h 6.3 x 106 7.9 x 106 14.9 x 106 6.9 x 106

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 3 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.3 Letdown Orifice - RO-2003, RO-2004 and RO-2005 Quantity 3

Capacity (Each) 40 gpm Design Pressure 2,485 psia Design Temperature 650F Normal Temperature of Fluid 250F Maximum Temperature of Fluid 450F Normal Downstream Pressure 425 psia Normal Upstream Pressure 1,970 psia Material Stainless Steel Fluid Primary Coolant, 1 Wt %

Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design) 1.4 Letdown Heat Exchanger - E-58 Quantity 1

Type Shell and Tube, Horizontal Design Heat Transfer 19.1 x 106 Btu/h Code ASME B&PV Code,Section III, Class C Tube Side (Letdown)

Fluid Primary Coolant, 1 Wt %

Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design)

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 4 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Pressure 650 psig Design Temperature 550F Material Stainless Steel Shell Side (Cooling Water)

Fluid Component Cooling Water Design Pressure 150 psig Design Temperature 250F Material Carbon Steel Operating Parameters - Letdown Heat Exchanger Maximum Unbalanced Maximum Charging With Maximum Unbalanced Normal Letdown Purification Letdown Tube Side (Letdown)

Flow - gpm 42 40 130 143 Inlet Temp - F 251 160 319 449 Outlet Temp - F 120 120 120 139 Heat Transfer - Btu/h 2.6 x 106

.79 x 106 11.9 x 106 19.1 x 106 Shell Sides (Cooling Water)

Flow - gpm 66 - 111 23 - 40 500 - 1,000 591 - 960 Inlet Temp - F 65 - 90 65 - 90 65 - 90 65 - 90

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 5 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Outlet Temp - F 144-137 133-130 113 - 114 130-130 1.5 Process Radiation Monitor - Element RE-0202 Quantity 1

Design Pressure 200 psig Design Temperature 250F Normal Operating Pressure 20 psig Normal Operating Temperature 120F Normal Flow Rate 0.5 gpm Code ASA B31.1 1.6 Ion Exchangers - T-51A, T-51B and T-52 Quantity 3

Type Flushable Design Pressure 200 psig Design Temperature 250F Normal Operating Pressure 20 psig Normal Operating Temperature 120F Resin Volume 32 ft3 Normal Flow Rate 40 gpm Maximum Flow Rate 120 gpm Decontamination Factor, Minimum 10 Retention Screen 80 US Mesh

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 6 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Code for Vessel ASME B&PV Code,Section III, Class C Material Stainless Steel Fluid 1 Wt % Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design) 1.7 Purification Filters - F-54A and F-54B Quantity 2

Type of Elements Synthetic Fiber Retention 0.05 to 6.0 Micron Absolute; 1.0 Micron Nominal (or finer)

Design Pressure 200 psig Design Temperature 250F Design Flow 120 gpm Normal Flow 40 gpm Maximum Flow 160 gpm Code for Vessel ASME B&PV Code,Section III, Class C, 1965 Material Stainless Steel Fluid 1 Wt % Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design) 1.8 Volume Control Tank - T-54 Quantity 1

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 7 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Type Vertical, Cylindrical Design Pressure, Internal 75 psig Design Pressure, External 15 psig Design Temperature 250F Internal Volume, Minimum 4,170 gal Operating Pressure Range 0 to 75 psig Normal Operating Pressure 10 psig Normal Operating Temperature 120F Normal Spray Flow 40 gpm Blanket Gas Hydrogen or Nitrogen Code ASME B&PV Code,Section III, Class C, 1965 Fluid 1 Wt % Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design)

Material Stainless Steel 1.9 Spray Nozzle (Volume Control Tank)

Quantity 1

Type Medium Angle, Full Cone Design Pressure 200 psig Design Temperature 250F Normal Spray Flow 40 gpm

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 8 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Maximum Spray Flow 120 gpm Fluid 1 Wt % Boric Acid, Nominal; 15,000 ppm Boric Acid, Maximum (Design)

Material Stainless Steel 1.10 Variable Speed Charging Pump - P-55A Quantity 1

Type Positive Displacement Design Pressure 2,735 psig Design Temperature 250F Flow Rate Range 33 to 53 gpm Normal Flow Rate 44 gpm Normal Discharge Pressure 2,200 psig Normal Temperature of Pumped Fluid 120F Maximum Discharge Pressure (Short Term) 2,900 psig NPSH Required 7.65 ft (Ref. 25)

NPSH Available 30.39 ft (Ref. 25)

(Normal Suction From VCT)

Maximum Pressure Pump Starts Against 2,485 psig Driver Rating 100 hp Type Variable Capacity Device Fluid Drive

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 9 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Fluid Drive and Pump 22 gpm, 15F Rise Cooling Water Requirements Materials in Contact With Pumped Stainless Steel or Equivalent Fluid Corrosion Resistance Fluid 1 Wt % Boric Acid, Nominal; 12 Wt% Boric Acid, Maximum (Design) 1.11 Constant Speed Charging Pumps - P-55B and P-55C Quantity 2

Type Positive Displacement Design Pressure 2,735 psig Design Temperature 250F Flow Rate 40 gpm Normal Discharge Pressure 2,200 psig Normal Temperature of Pumped Fluid 120F Maximum Discharge Pressure (Short Term) 3,010 psig NPSH Required 7.41 ft (Ref. 25)

NPSH Available P-55B/C 28.22/28.18 ft (Ref. 25)

(Normal Suction From VCT)

Maximum Pressure Pump Starts Against 2,500psig Driver Rating 75 hp Pump Cooling Water Requirements 5 gpm, 15F Rise

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 10 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Materials in Contact With Stainless Steel or Equivalent Pumped Fluid Corrosion Resistance Fluid 1 Wt % Boric Acid, Nominal; 12 Wt % Boric Acid, Maximum (Design) 1.12 Boric Acid Batching Tank - T-77 Quantity 1

Internal Volume 580 gal Useful Volume 457.4 gal Design Pressure Atmospheric Design Temperature 200F Normal Operating Temperature 150F Type Heater Electric Immersion Heater Capacity 31.5 kw Minimum Code ASME B&PV Code,Section VIII Fluid 6-1/4 Wt % Boric Acid, Normal; 12 Wt % Boric Acid, Maximum (Design)

Material Stainless Steel 1.13 Boric Acid Strainer - F-10 (YS-0224)

Quantity 1

Type Basket Design Pressure 125 psig

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 11 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Temperature 250F Screen Size 100 x 100 US Mesh Design Flow 50 gpm Material Stainless Steel Fluid 6-1/4 Wt % Boric Acid, Normal; 12 Wt % Boric Acid, Maximum (Design) 1.14 Concentrated Boric Acid Storage Tanks - T-53A and T-53B Quantity 2

Internal Volume 6,550 gal Design Pressure Atmospheric Design Temperature 200F Normal Operating Temperature 140F to 170°F Type Heater Electrical, Dry Well Installation Heater Capacity Two Independent 4 kW Banks per Tank Fluid 6-1/4 Wt % Boric Acid, Normal; 12 Wt % Boric Acid, Maximum (Design)

Material Stainless Steel Code ASME B&PV Code,Section III, Class C, 1965 1.15 Boric Acid Pumps - P-56A and P-56B

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 12 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Quantity 2

Type Centrifugal Design Pressure 150 psig Design Temperature 250F Design Head 225 ft Design Flow 143 gpm Minimum Flow 10 gpm Normal Operating Temperature 160F NPSH Required 7.50 ft (Ref. 25)

NPSH Available P-56A/B 25.06/25.23 (Ref. 25)

Horsepower 30 Fluid 6-1/4 Wt % Boric Acid, Normal; 12 Wt % Boric Acid, Maximum (Design)

Material in Contact With Liquid Stainless Steel 1.16 Boric Acid Filter - F-9 Quantity 1

Type Elements Synthetic Fiber Retention of 5 Micron Particles 98%

Design Pressure 150 psig Design Temperature 250F

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 13 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Flow 140 gpm Material Stainless Steel Liquid 6-1/4 Wt % Boric Acid, Normal; 12 Wt % Boric Acid, Maximum (Design)

Code ASME B&PV Code,Section III, Class C, 1965 1.17 Chemical Addition Tank - T-56 Quantity 1

Capacity 10.5 gal Design Pressure Atmospheric Design Temperature 200F Normal Operating Temperature Ambient Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH Code ASME B&PV Code,Section VIII 1.18 Chemical Addition Strainer - F-58 Quantity 1

Type Basket Design Pressure 100 psig Design Temperature 250F Screen Size 60 US Mesh

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 35 Page 14 of 14 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Flow 30 gph Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH 1.19 Metering Pump - P-57 Quantity 1

Type Air Operated Double Diaphragm Design Pressure 120 psig Design Temperature 190F Design Flow Rate 0 to 35 gpm Design Air Consumption 0 to 50 scfm Normal Fluid Temperature 75F Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-19 Revision 24 Page 1 of 1 FUEL HANDLING DATA

1.

New Fuel Storage Rack Core Storage Capacity 1/6 Equivalent Fuel Assemblies 36 Center-to-Center Spacing of Assemblies 11 in

2.

Spent Fuel Storage Pool Core Storage Capacity 4.3 Equivalent Fuel Assemblies 892 Number of Space Accommodations for Spent Fuel Shipping Casks 1

Center-to-Center Spacing of Assemblies Region 1 10-1/4 in Region 2 9.17 in Maximum keff With Unborated Water Less Than 1.0

3.

Miscellaneous Details Wall Thickness for Spent Fuel Storage Pool 4 ft to 6-1/2 ft Weight of Fuel Assembly 1,500 lb Capacity of Refueling Water Storage Tank 285,000 gal Quantity of Water Required for Refueling 250,000 gal

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-20 Revision 33 Page 1 of 2 FUEL BUILDING CRANE Main Hoist 3 ft/min at Full Load (3 Steps), 25 hp at 900 r/min Main Hoist Brake Capacity 179 ft-lb Auxiliary Hoist 25 ft/min at Full Load (Stepless), 25 hp at 900 r/min Trolley 25 ft/min at Full Load (3 Steps), 3 hp at 1,800 r/min

  • Bridge 25 ft/min at Full Load (3 Steps), 5 hp at 1,800 r/min
  • Service Class Class A, Electric Overhead Crane Institute Specification 70 Lift Main Hoist 54 ft 0 in Lift Auxiliary Hoist 108 ft 5 in Span 44 ft 10 in Center-to-Center Rails Bridge Travel Approximately 100 ft Lifting Tackle Main Hoist - Rope 16 Parts 13/4-Inch SS, Drum 521/2-Inch Pitch Diameter, Sheaves 28-Inch Pitch Diameter Auxiliary Hoist - Rope 4 Parts 3/4-Inch SS, Drum 15-Inch Pitch Diameter, Sheaves 13-Inch Pitch Diameter Girders Welded Box Section Runway Rail 100 lbs ASCE Trolley Rail 175 lbs USS Bridge Drive Direct Drive Arrangement With Oiltight Center Gear Case Trolley Drive Direct Drive Arrangement With Oiltight Center Gear Case
  • Single failure proof mode of operation only

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-20 Revision 33 Page 2 of 2 FUEL BUILDING CRANE Capacity in Net Tons Bridge 110 Tons, Main Hoist 110 Tons, Auxiliary Hoist 15 Tons Wheels Bridge Has Eight 21-Inch Steel Hardened Treads Trolley Has Four 21-Inch Diameter Steel Hardened Treads Bridge End Assembly Rotating Axle Bumpers Rubber Bearings Antifriction Throughout Gearing Helical Gearing Heat-Treated Steel Throughout Except Trolley Traverse. All Gearing in Oiltight Casing

FSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-21 Revision 35 Page 1 of 1

POWER BLOCK STRUCTURE Building Fire Area Description Auxiliary 1

Control Room Complex Auxiliary 2

Cable Spreading Room Auxiliary 3

1D Switchgear Room & North Cableway Auxiliary 4

1C Switchgear Room Auxiliary 5

1-1 Diesel Generator Room Auxiliary 6

1-2 Diesel Generator Room Auxiliary 7

Diesel Generator 1-1 Fuel Oil Day Tank Auxiliary 8

Diesel Generator 1-2 Fuel Oil Day Tank Auxiliary 10 East Engineered Safeguards Room Auxiliary 11 Battery Room #2 Auxiliary 12 Battery Room #1 Auxiliary 13 Auxiliary Building - Miscellaneous Auxiliary 15 Engineered Safeguards Panel Room & Stairway Auxiliary 16 Component Cooling Pump Room Auxiliary 17 Refueling & Spent Fuel Pool Room Auxiliary 18 Demineralizer Rooms Auxiliary 19 Track Alley Auxiliary 21 Electrical Equipment Room Auxiliary 27 Radwaste Addition - VRS Auxiliary 28 West Engineered Safeguards Room Auxiliary 29 Center Mechanical Equipment Room Auxiliary 30 East Mechanical Equipment Room Auxiliary 31 West Mechanical Equipment Room Auxiliary 32 SIRW Tank & CCW Roof Area Auxiliary 33 Technical Support Center Auxiliary 34 Man Hole #1 Auxiliary 35 Man Hole #2 Auxiliary 36 Man Hole #3 Auxiliary 26 Southwest Cable Penetration Room Reactor 14 Reactor Containment Building Turbine 9

Intake Structure Turbine 22 Turbine Lube Oil Room Turbine 23 Turbine Building Turbine 24 Auxiliary Feedwater Pump Room Turbine 25 Heating Boiler Rooms Turbine 56 Diesel Fire Pump Fuel Oil Day Tank Room Feedwater Purity 39 Feedwater Purity Building Yard 41 Outside Area within Protected Area & Transformer Area Switchyard 40 Switchyard Enclosure 59 Diesel - Driven AFW Pump P-8D Enclosure