FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-1 Revision 23 Page 1 of 1 TURBINE CASING PROPERTIES Tensile Strength, psi, Min 70,000 Yield Strength, psi, Min 36,000 Elongation in 2 Inches, %, Min 22 Reduction of Area, %, Min 35

FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-2 Revision 23 Page 1 of 1 STUD MECHANICAL PROPERTIES Size, Inches 2-1/2 Over 2-1/2 Over 4 and Less to 4 to 7 Tensile Strength, psi, Min 125,000 115,000 110,000 Yield Strength, psi, Min (0.2% Offset) 105,000 95,000 85,000 Elongation in 2 Inches, %, Min 16 16 16 Reduction of Area, %, Min 50 50 45

FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-3 Revision 28 Page 1 of 1 SIGNAL SYSTEM OPERATING CONDITIONS

1. Hydrogen Purity - High or Low
2. Hydrogen Pressure - High or Low
3. Hydrogen Supply Pressure - Low
4. Water Detection - High
5. Hydrogen Temperature High / Generator Condition Monitor
6. Defoaming Tank Level - High
7. Seal Oil System Trouble
8. Loss of Alarm DC Power
9. Air Side Seal Oil Backup Pump Running
10. +24 VDC Power - Off (Alarm Panel)
11. Main Seal Oil Pump - Off
12. Seal Oil Drain Tank Level - Error
13. Seal Oil Drain Tank Level - High
14. Seal Oil Drain Tank Level - Low
15. Seal Oil Drain Tank Level - Very Low
16. Seal Oil Pressure - Low
17. Seal Oil Turbine Backup Supply Pressure - Low
18. TE or EE Seal Oil Pressure - Low
19. Seal Oil Filter Differential - High
20. PLC Failure
21. Recirc Sol Valve Backup Mode - On
22. Both Recirc Sol Valves - Closed
23. 125 VDC Power Supply Failure

FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-4 Revision 34 Page 1 of 2 COOLING TOWER DESIGN

SUMMARY

(SPX MARLEY TOWER E-30A)

Number of Towers 1 Number of Cells 16/Tower Type Induced/Cross Flow Performance at Design Point Hot Water Flow, gpm 185,000 Approach Temperature, °F 112.77 Range, °F 32 Cold Water Temperature, °F 80.77 Fan Brake Horsepower, bhp 166 Pumping Head Above Sill, ft 90 Fans and Fan Motors Number of Fans 16 Number of Blades 9 Blade Diameter, ft 28 Blade Material Fiberglass Reinforced Vinyl Ester Tip Speed, ft/s 196 Fan Speed, r/min 134 Rated hp/Voltage 200/460V

FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-4 Revision 34 Page 2 of 2 COOLING TOWER DESIGN

SUMMARY

(SPX MARLEY TOWER E-30B)

Number of Towers 1 Number of Cells 18/Tower Type Induced/Cross Flow Performance at Design Point Hot Water Flow, gpm 185,000 Approach Temperature, °F 110.9 Range, °F 32 Cold Water Temperature, °F 78.9 Fan Brake Horsepower, bhp 166 Pumping Head Above Sill, ft 90 Fans and Fan Motors Number of Fans 18 Number of Blades 9 Blade Diameter, ft 28 Blade Material Fiberglass Reinforced Vinyl Ester Tip Speed, ft/s 196 Fan Speed, r/min 134 Rated hp/Voltage 200/460V

FSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-5 Revision 23 Page 1 of 1 COOLING TOWER PUMPS Number of Pumps 2 Type Vertical, Wet Pit Design Flow, gpm 164,000 Design Head, ft 87 Design NPSH, ft 29 Pump Speed, r/min 253 Motor Type Induction Horsepower, hp 7,000 Voltage 4,160