Forwards Issue 3 of Fire Protection Operability Requirements 13 & 15 Re Insp of Both Sides of Penetration & Functional Testing of Fusible Link Dampers,Respectively,Per Generic Ltr 86-10
ML20247F625
Person / Time
Site: Fort Saint Vrain 
Issue date: 03/27/1989
From: Robert Williams
PUBLIC SERVICE CO. OF COLORADO
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20247F630 List:
References
GL-86-10, P-89094, TAC-66508, NUDOCS 8904030493
Download: ML20247F625 (5)


Text

..,_. ___ _ _ _.. _ - _ _ _ _ _ _ - - _ _.. _ _ _ _. _ _ _ _ _ _

O Public Service-

,.. e...

Company of Colorado P.O. Box 840 Denver, CO 80201 0840 Fort St. Vrain R.O. WILLIAMS, JR.

Unit No. 1 SENIOR VICE PRESloENT NUCLEAR OPE RATIONS P-89094 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C.

20555 Docket No. 50-267

SUBJECT:

FPOR-13 and FPOR-15, Issue 3

REFERENCE:

NRC Generic Letter 86-10, dated April 24, 1986 (G-86227)

Gentlemen:

Enclosed is one signed original and ten additional copies of Issue 3 of the Fire Protection Operability Requirements (FPORs) 13 and 15.

The FPORs are contained in Section FP.6.1 of the Fort St Vrain (FSV)

Fire Protection Program Plan (FPPP).

Issue 3 of FPOR-13 and FPOR-15 is being submitted under the same requirements as 10 CFR 50.71(e).

Per the Reference, the FPPP is not required to be submitted under this regulation until the NRC has approved the FSV Fire Protection Program.

The attachment to this letter is a summary of the changes to the FPORs. A 10 CFR 50.59 safety evaluation was performed on Issue 3 of FPOR-13 and FPOR-15.

The evaluation determined that the revisions were safety-related, but were not safety significant and did not involve or create an unreviewed safety question. The revisions do not require changes to the FSV Technical Specifications.

1 OC ok0 27 h

av o

P-89094 Page 2 March 27, 1989 If you have any questions or comments, please contact Mr. M. H.

Holmes at (303) 480-6960.

Very truly yours,

~

u R. O. Williams, Jr.

Senior Vice President, Nuclear Operations R0W/BRD:tmk Attachment Enclosure cc: Regional Administrator, Region IV Attention: Mr. T. F. Westerman, Chief Projects Section B (with one copy of Issue 3 of FPOR-13 and TPOR-15)

Mr. R. E. Farrell Senior Resident Inspector Fort St. Vrain (Issue 3 of FPOR-13 and FPOR-15 previously delivered) h-

_m._.m____-__m________.

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter Public Service Company of Colorado

)

Docket No. 50-267 Fort St. Vrain Unit No. 1

)

AFFIDAVIT R.

O.

Williams, Jr. being first duly sworn, deposes and says:

That he is Senior Vice President, Nuclear Operations, of Public Service Company of Colorado, the Licensee herein, that he has read the information presented in the attached letter and knows the contents thereof, and that the statements and matters set forth therein are true and corrett to the best of his knowledge, information and belief, f

R. O. Williams, JF.

Senior Vice President Nuclear Operations STATE OF W

COUNTY OF pa-w Subscribe and sworn to before me, a Notary Public on this 7t%

day of M

, 1987.

I

~ des-Notary ublic l

l 191/

My consnission expires leM+ w

, 1C E_______-_--.

~ -

P-89094 Page 1

SUMMARY

OF CHANGES FPOR-13 FPOR-13 surveillance-requirement is revised to include inspection of both sides of a pentration when both. sides are accessible.

Many new penetration seals have been added as a result of plant walkdowns. These seals are addressed in CN-2616 and CN-2345 and their reissues.

Several' seals (see attached list) have been deleted. TABLE FPOR-13-1 has been updated accordingly.

FPOR-15 The ACTION statement has been reworded to clarify that a fire watch is posted on one side of the " barrier containing the affected damper", as opposed to one side of the affected damper.

For consistency between the ACTION Statement NOTE and the BASIS, the words " fire watch patrol" are no longer capitalized.

NOTE (1) of the Surveillance Requirements is revised to indicate that fusible link dampers are functionally testeo when accessible. The Basis is revised accordingly.

Table FPOR-15-1 has been revised to add one damper to 'he Control Room / Electric Equipment Room list, one damper te the 4SO Volt room list,-and add the HYDROGEN BOTTLE STORAGE ROOM list (two dampers).

P-89094 Page 2 SEALS TO BE DELETED FROM SURVEILLANCE SR-FP-13a-A SEAL #

COMMENTS TRC-38 TRANSFORMER IN BOX DOES NCT PENETRATE WALL TPC-39 TRANSFORMER IN BOX DOES NOT PENETRATE WALL TRC-66 GROUTED SEWER LINE BT-37 DUPLICATENUMBER(BT-34)

BT-38 DUPLICATE NUMBER (BT-35)

BT-39 DUPLICATE NUMBER (BT-36)

ICB9 GROUTED GROUNDING CABLE, USED TO BE A FIRE SEAL 2CWO3 GROUTED EXTERNAL SEAL, NUMBER NOT NEEDED.

NOT SHOWN ON ANY PLANT DRAWING.

B153 DELETE FROM SURV., NO INTERNAL SEAL d693 BOX DOES NOT PENETRATE WALL, JUST TERM. BOARDS INSIDE JB175 B0X DOES NOT PENETRATE WALL, JUST TERM. BOARDS INSIDE TPC-43 SEAL DOES NOT EXIST PER FIELD WALKDOWN AND DELETED PER DR TRC-44 SEAL DOES NOT EXIST PER FIELD WALKDOWN AND DELETED PER DR TRC-45 SEAL DOES NOT EXIST PER FIELD WALKDOWN AND DELETED PER DR TRC-46 SEAL DOES NOT EXIST PER FIELD WALKDOWN AND DELETED PER DR

_ _ _ _ _ _ _ _