Text

..

LCA 124 Page 3 of 21 CONTAINMENT SYSTEMS CONTAINMENT LEAKAGEb LIMITING CONDITION FOR OPERATION 3.6.1.2 Containment leakage rates shall be limited to:

a.

An overall integrated leakage rate of:

1.

-SLa (defined as 0.10 percent by weight of the containment air per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at Pa, 60 psig), or 2.

SLt (defined as 0.07 percent by weight of the containment air per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at a reduced pressure of P, 30 psig).

t i

b.

A combined leakage rate of 50.60 La for all penetrations and valves subject to Type B and C tests when pressurized.to Pa-APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION:

With either: (a) the measured overall integrated containment leakage rate exceeding 0.75 La or 0.75 L, as applicable, or (b).with the measured t

combined leakage rate for all penetrations and valves subject to Types B and C tests exceeding 0.60 La, restore the leakage rate (s) to within the limit (s) prior to increasing the Reactor Coolant System temperature above 200*F.

SURVEILLANCE REQUIREMENTS 4.6.1.2 The containment leakage rates shall be demonstrated at the following test schedule and shall be determined in conformance with the criteria specified in Appendix J of 10 CFR 50 using the methods and provisions of ANSI N45.4-1972:

a.

Three Type A tests (Overall Integrated Containment Leakage Rate) shall be conducted at 40 10 month intervals during shutdown at either Pa (60 psig) or at Pt (30 psig) during each 10-year service period. The third test of each set shall be conducted during the shutdown for the 10-year plant inservice inspection.

N 5

4 P

l l TROJAN-UNIT 1 3/4 6-2 Amendment No.

-4 TABLE 3.6-1 5

4 g

CONTAINMENT-ISOLATION VALVES Zi TESTABLE DURING

' ISOLATION TINE VALVE NUMBER FUNCTION PLANT OPERATION (seconds)

A.

Automatic Containment Isolation Valves l

MO 5658*

PRZ steam sample - Inside yes 10 CV 5659*

PRZ steam sample - Outside yes 10 MO 5656*

PRZ water sample - Inside yes-10 i

CV 5657*

PRZ water sample - Outside yes 10 MO 5653*

Reactor Coolant Loop Sample - Inside yes 10 MO 5654*

Reactor Coolant Loop Sample - Inside yes 10 4

l CV 5655*

Reactor Coolant Loop Sample - Outside yes 10' i

MO 5651 A*

Accumulator "A" Sample - Inside yes 10 MO 5651B*

Accumulator "B" Sample - Inside yes 10 i

w MO 5651C*

Accumulator "C" Sample - Inside yes 10 I'

M0 5651D*

Accumulator "D" Sample - Inside yes 10 e

CV 5652*

Accumulators' Sample - Outside yes 10 l

MO 5674 Containment atmosphere sample l

2 supply - inside yes 10 MO 5675 Containment atmosphere sample l

supply - outside yes 10 j

M0 5672 Containment atmosphere sample return - inside yes 10 MO 5676 Containment atmosphere sample return - outside yes 10 MO 5671 Containment atmosphere sample supply - outside yes 10 MO 5673 Containment atmosphere sample return - inside yes 10 MO 5663 Containment atmosphere sample

?RE L;

5 return - outside yes 10

'S g

  • l E

CV 8026 Pressurizer relief tank gas co 9 0 1

5 analyzer - inside yes 10 o2" A

'E 3

j 5

.4-TABLE 3.6-1 g

CONTAINMENT ISOLATION VALVES i

i TESTABLE DURING ISOLATION TIME VALVE NUMBER FUNCTION PLANT OPERATION' (seconds)

A.

Automatic Containment Isolation Valves (Continued) l CV 8025 Pressurizer relief tank gas analyzer - outside yes.

10 MO 5660 RCDT gas analyzer.inside yes 10 CV 5661 RCDT gas analyzer - outside yes 10 CV 4000 RCDT N2 supply - outside yes 10 M0 4005 RCDT discharge - inside yes 10 CV 4006 RCDT discharge - outside yes 10 CV 8028 Pressurizer relief tank makeup - outside yes 10 g

MO 5677 Containment atmosphere sample supply - outside yes 10 e

m MO 5678 Containment atmosphere sample 1

return - outside yes 10 CV 8033 Pressurizer relief tank N2 supply - outside yes 10 CV 8880 Accumulator N2 supply - outside yes 10 MO 4300 Gas collection header - inside' yes 10 CV 4301 Gas collection header outside yes 10 MO 10016 Chilled water supply - inside yes 5

CV 10015 Chilled water supply - outside yes 3

MO 10013 Chilled. water return - inside yes 5

CV 10014 Chilled water return - outside yes 3

MO 4180 Containment sump discharge -

inside yes 10

[

CV 4181 Containment sump discharge -

1RE g

outside yes 10

%g>

g CV 8871 SIS test line - inside yes 10 w 9. C m

CV 8964 SIS test line - outside yes 10 og" CV 8888 SIS test line - outside yes 10

  • 3,

,o S _.

+

TABLE 3.6-1 y

O h

CONTAINMENT ISOLATION VALVES Iii 7

TESTABLE DURING ISOLATION TIME VALVE NUMBER FUNCTION PLANT OPERATION (seconds) l f

A.

Automatic Containment Isolation Valves (Continued)

CV 8149A CVCS letdown - inside yes 10 i

CV 81498 CVCS letdown - inside yes 10 CV 8149C CVCS letdown - inside yes 10 CV 8152 CVCS letdown - outside yes 10' MO 8112 RC Pump seal water return -

inside no 10 MO 8100 RC Pump seal water return -

outside no 10 g

SV 5642 Containment atmosphere sample supply drain - inside yes 3

e p

SV 5643 Containment atmosphere sample supply drain - inside yes 3

SV 5679 Containment atmosphere sample return - inside yes 3

MO 8105#Y CVCS charging - outside yes 10 l

CV 4470 Service air supply - outside yes 10 CV 4471 Instrument air supply - outside no 10 SV 6991*

93-ft airlock test line - outside yes 3

SV 6992*

93-ft airlock test line - outside yes 3

B.

Automatic Containment Ventilation Isolation Valves l

MO 10002**

Containment purge supply - inside no 5

CV 10001**

Containment purge supply - outside no 3

7RG l

MO 10003**

Containment purge exhaust - inside no 5

$U#

o-CV 10004**

Containment purge exhaust - outside no 3

9-C l

MO 10005***

Hydrogen vent supply - outside yes 5

5" MO 10006***

Hydrogen vent supply - outside yes 5

SS r+

5 C2~

g TABLE 3.6-1 o

CONTAINMENT ISOLATION VALVES 7

TESTABLE DURING ISOLATION TIME VALVE NUMBER FUNCTION PLANT OPERATION (seconds)

B.

Automatic Containment Ventilation Isolation Valves (Continued)

MO 10011***

Hydrogen vent exhaust - outside yes 5

MO 10012***

Hydrogen vent exhaust - outside yes 5

HD 10007***

Hydrogen vent supply - inside yes 5

-M0 10008***

Hydrogen vent supply - inside yes 5

MO 10009***

Hydrogen vent exhaust - inside yes 5

MO 10010***

Hydrogen vent exhaust - inside yes 5

C.

Non-Automatic Power Operated Isolation Valves MO 3291#

CCW train "A" supply - outside no N.A.

u D

MO 3292#

CCW train "A" discharge - outside no N.A.

m M0 3346#

CCW train "B" supply - outside no N.A.

E MO 3290#

CCW train "B" discharge - outside no N.A.

M0 2053A#

Containment Spray Pump A discharge - outside yes N.A.

MO 2053Bf Containment Spray Pump B discharge - outside yes N.A.

MO 8702#$

RHR normal suction inside no N.A.

l MO 8701#4 RHR normal suction inside no N.A.

CV 8825#

RHR hot leg recirculation - inside no N.A.

MO 8703#

RHR hot leg recirculation - outside no N.A.

MO 8835#

SIS discharge line - outside no N.A.

(cold leg)

MO 8809A#

RHR pump "A" discharge - outside no N.A.

l MO 88098#

RHR pump "B" discharge - outside no N.A.

,,r g

M0 2069A#

Sump Recirculation Train "A" yes N.A.

g r+ g a

inside am A

MO 2069B#

Sump Recirculation Train "B"

S5 ol g

inside yes N.A.

% v4

4 y

TABLE 3.6-1 5y CONTAINMENT ISOLATION /ALVES

?

E TESTABLE DURING ISOLATION TIME VALVE NUMBER FUNCTION PLANT OPERATION (seconds)

C.

Non-Automatic Power Operated Isolation Valves (Continued)

MO 2052A SIS Recirculation Train "A" - outside yes N.A.

MO 8811A SIS Recirculation Train "A" - outside yes N.A.

M0 20528 SIS Recirculation Train "B" - outside yes N.A.

MO 8811B SIS Recirculation Train "B" - outside yes N.A.

I CV 8843#

BIT Discharge - inside no N.A.

MO 8802A#

SIS discharge Train "A" - outside no N.A.

MO 88028#

SIS discharge Train "B" - outside no N.A.

CV 8881#

SIS discharge Train "A" - inside yes N.A.

CV 8824#

SIS discharge Train "B" - inside yes N.A.

l D.

Manual Valves l

T$

8090A*

(RCS) Deadweight Tester - outside N.A.

N.A.

8090B*

(RCS) Deadweight Tester - outside N.A.

N.A.

SF080 Refueling cavity recirculation -

inside N.A.

N.A.

SF046 Refueling cavity recirculation -

outside N.A.

N.A.

SF073 Refueling cavity drain - inside N.A.

N.A.

3 l

SF074 Refueling cavity drain - outside N.A.

N.A.

]

SF063 Refueling cavity skimming - inside N.A.

N.A.

i SF062 Refueling cavity skiming - outside N.A.

N.A.

MD059*

Demin water washdown - outside N.A.

N.A.

10610A ILRT Instrument Line - outside N.A.

N.A.

m > r-y3S 10610B ILRT Instrument Line - inside N.A.

N.A.

2 10611A ILRT Instrument Line - outside N.A.

N.A.

n-1 106118 ILRT Instrument Line - inside N.A.

N.A.

CIS R

LD00l*

45-ft airlock test line - outside N.A.

N.A.

oE LD003*

45-ft airlock test line - outside N.A.

N.A.

[_

5

~

I

R y

TABLE 3.6-1 eg CONTAINMENT ISOLATION VALVES e5 TESTABLE DURING ISOLATION TIME VALVE NUMBER FUNCTION PLANT OPERATION (seconds)

E.

Check Valves l

8047 PRT N2 Supply - inside no N.A.

8046 PMU Water to PRT - inside no N.A.

l 8180 RCP Seal Water Rtrn. - inside no

.N.A.

8968 N2 to Accumulators - inside no N.A.

Check valve Demin. Water to Washdown (3" HCB-3)

Sta. - inside no N.A.

Check valve RCDT N2 Supply - inside no N.A-.

(1" GBB-1)

Check valve downstream Service Air - inside no N.A.

R of CV 4470 Check valve downstream Instrument Air - inside no N.A.

T of CV 4471 M

F.

Relief Valves l

PSV-8117 CVCS Letdown - inside no N.A.

PSV-8708#

RHR Pump Suction - inside no N.A.

G.

Steamline Isolationt g

CV 2811#

S. G. "A" Sample - Outside yes N.A.

CV 2880#

S. G.

"B" Sample - Outside yes N.A.

CV 2814#

S. G. "C" Sample - Outside yes N.A.

?

CV 2809#

S. G.

"D" Sample - Outside yes N.A.

S 2RE

%2" ci5 y

e-

~

~

TABLE 3.6-1 g

g CONTAINMENT ISOLATION VALVES a

i I

H TESTABLE DURING ISOLATION TIME 5

VALVE NUMBER FUNCTION PLANT OPERATION (seconds) i i

G.

Steamline Isolationt (Continued)

MO 6716#

S. G. "A" bldwdown - Outside yes N.A.

i MO 2808#

MO 6717#

S. G. "B" blowdown - Outside yes N.A.

M0 2810#

j MO 6718#

S. G.

"C" blowdown - Outside yes N.A.

j MO 2812#

1 MO 6719#

S. G.

"D" blowdown - Outside yes N.A.

MO 2813#

CV 2277#-

Main Steam Isolation Bypass Line yes N.A.

w) 2280#

2 j

CV 2294#-

Main Steam Line Steam Trap yes N.A.

m i

4 2297#

CV 2210#

Main Steam Power Operated l

Reliefs (no isolation signal) no N.A.

j CV 2230#

Main Steam Power Operated 1

Reliefs (no isolation signal) no.

N.A.

1 CV 2250#

Main Steam Power Operated j

Reliefs (no isolation signal) no.

N.A.

CV 2270#

Main Steam Power Operated Reliefs (no isolation signal) no N.A.

I MO 2218#

Main Steam Supply to Auxiliary FW i

Pump Turbine Driver no N.A.

MO 2228#

Main Steam Supply to Auxiliary FW j

Pump Turbine Driver, no N.A.

l E

$%9 2

aR_

i i

I[%

l 5

,I E

i

l'.

l D

^,

is TABLE 3.6-1 4

8 l

3E CONTAINMENT ISOLATION VALVES TESTABLE DURING ISOLATION TIME

~

VALVE NUMBER FUNCTION PLANT OPERATION (seconds) 1-G.

Steamline Isolationt (Continued)

)

MO 2238#

Nain Steam Supply to Auxiliary FW 3

Pump Turbine Driver no.

N.A.

J M0 2248#

Nain Steam Supply to Auxiliary FW Pump Turbine Driver.

no N.A.

1 FWO79#-FWO86#

Feedwater Line Drains no N.A.

MS013#-MS016#*

Main Steam Line Drains no N.A.

i ki a,

i' t

i i

  • May be opened on an intermittent basis under administrative control.

i

    • The Containment. purge supply and exhaust valves shall be made inoperable (electric power or air supplies removed from their respective operators) dur!ng Modes 1 through 4.
      • The Hydrogen vent supply and exhaust valves shall be normally closed, and opened only when and for the j

duration of time actually necessary.

  1. Not subject to Type C leakage tests.

l

, Closes on an SIS signal only.

2

+ May be open during Mode 4.

g ;g ;

il t The Steamline Isolation Valves are listed for table completeness only.

The requirements of Specifica-

~

y _,

a j

R tion 3.6.3 do not apply.

Instead, the requirements of Specification 3.3.2 and 3.7.1.6 apply to the Main

7 y' o,,e!.

A Steam Isolation Valves, and Specification 3.3.2 applies to the Main Feedwater Isolation Valves.

z i

_