This refers to A=endment 2, dated June 1, 1967, to your applica-tion for a provisional operating license for the Nine Mile Point Nuclear Station located in the town of Scriba, New York.
O Our review of Amendment 2 indicates that additional information g
on the facility electrical systen, instrument air syste=s and l
the actuation signals for the engineered safety features is necessary to enable us to continua our review of these matters.
f A list of specific comments illustrating the kind of information
{
needed is enclosed.
We will be available to discuss and clarify any of the specific Co ents.
Sincerely yours, h
1 ef. r -- -. ff
\\
i n;, W lM4%
Peter A. Morris, Director Division of Reactor Licensing
'I
Enclosure:
List of Comments c.c:
Arvin E. Upton, Esquire LeBoeuf, Lamb,Teiby & Mac.-e f
f 3
ninI@ J A
JW L
i 8904210369 890413 i
EDJJOy
c.
=
4
(
l ADDITIONAL INFORMATION REOUIRED 1
NIAGARA MOHAWK POWER CORPORATION 8'
NINE MILE POINT PLANT l
I.
DOCKET NO. 50-220 l
5 o
1.
Evaluate the ability of the offsite power system to provide power for i
1 engineered safety feature and safe shutdown loads with a fault in the outside system. This discussion should include (1) loss of one or more 345 KV transmission lines, (2) sudden loss of the NMP generating capacity, and (3) sudden loss of the largest generating plant in the Niagara Mohawk grid.
2.
Evaluate the ability of the offsite power design to satisfy Criterion 39 in view of the two-minute time delay required before the 115 KV disconnect switch can be opened following a fault on one half of the 4
l 115 KV system.
'f' 3.
"he FSAR does not discuss the use of d.c. power for circuit breaker operation in the switchyard. Describe how d.c. power is supplied to j
(
the switchyard and evaluate the ability of the switchyard to operate a
.-l properly with a single failure in the d.c. system.
4.
A recent electrical fire in a nuclear power station has emphasized the i
importance of the design of electrical penetrations and cable runs.
Dascribe and evaluate the designs being utilized for the cable runs g
and electrical penetrations in the Kine Mile Point Station. This dis-
'}
j cussion should include, but not be limited to, the types of cables being used, the design and spacing of cable trays and electrical penetrations, j
derating, and circuit overload protection.
h 5.
Describe and evaluate the consequences of co=plete loss of station air
' lp j and/or vital instrument air. This discussion should include, but not be limited to, the failure modes of pneumatic instruments and valves 1-4 under the following conditions:
a l
1.
Post-shutdown from full power operation.
i j
i 2.
Post accident.
l l
t 1
6.
The diesel generators are started upon loss of voltage at the essential j
buses.
Evaluate the need for starting the diesel generators on signals I
other than loss of voltage (e.g., coolant injection).
}