i TENNESSEE VALLEY AUTHORITY.

SEQUOYAH NUCLEAR PLANT FUNCTION RESTORATION GUIDELINES FR-3.2 RESPONSE TO CONTAINMENT FLOODING .

t Revision 0_ ,

PREPARED BY: G ./St rickland RESPONSIBLE SECTION: erations // //

REVISED'BY:

,,,( SUBMITTED BY:

8/M/

Res'ponsib/

/ -

l~e Sje " l'on Supervicor AUG 2'11985 PORC' REVIEW DATE:

APPROVED BY: Ty,ud ifR4 %

Pladt Manager DATE APPROVED: AUG 211985 l

Reason for revision (include all Instruction Change F5rm Nos.):

New Instruction written per commitment to NUREG 0737.

The last page of this instruction is number: 2 g81{0g 87

.P

SEQUOYAH NUCLEAR PLANT

. PLANT INSTRUCTION REVISION LOG FUNCTION RESTORATION GUIDELINES FR-Z.2 REVISION Date Pages REASON FOR REVISION (INCLUDE COMMIT-LEVEL Approved Affected MENTS AND ALL ICF FORM NUMBERS)

New instruction written per commitment 0 A JG 211985 All to NUREG 0737

=

I

.,k ,

0239L/jlp L_ _ _ _ -__ _ _ i

e -

, SQNP FR-Z. 2 Unit 1 or 2 Page 1 of 2 Rev. O

\'

~

RESPONSE TO CONTAINMENT FLOODING

, A. . PURPOSE

. This guideline provides ections to respond to containment flooding j.

B. SYMPTOMS Cntmt sump level greater than 95%

g C. TRANSITION FROM OTHER INSTRUCTIONS _

Status Tree 1

l l

l

- j 1

l l

l

)

i

bW '

SQNp

[;.M-;V

a. a , ,s e, '

FR-Z.2. ' Unit 1 or 2 7 ,

. pgg, g og 9

,; . Rev. O V

JT %1 "

RdbPONSE TO' C'ONTAINMENT FLOODING

,7 ,

STEP - ], ACTION / EXPECTED RESPONSE RESPONSE NOT OBTAINED q .

i 1 , ' Attempt To Identify Unexpected E Source Of. Water To Sump .

r.>

a. ERCW s
b. CCS .

f

, c. High pressure fire prot' ection m, .

P' ' d '. Primary water -

e. .. Refer to SOI-88 as required ,

, .2  : Check Cntmt Su' mp ' Activity e a. ' Notify chem lab to sample entmt sump y -(. '

o p'

_. b . IF RHR suction aligned to b. E RHR NOT aligned

<. cntmt sump, to entmt sump, THEN sample: from' RHR THEN consult TSC p; system to evaluate sampling s entmt sump p,

3 Consult With TSC

a. Notify TSC to evaluate following: ,
1) Stopping. leakage into j

' cntmt sump 4 l

2) . Operational problems }

with equipment located ~

i below cntmt water level )

l 3) If water should be f transferred from entmt to Aux Bldg Return To Instruction In Effect 4

l

- END - l n __._ --------____ _ _ _ o