Changes to Proposed Tech Specs Including Change Request 126, Rev 2
ML20214K037
Person / Time
Site: Beaver Valley
Issue date: 05/14/1987
From:
DUQUESNE LIGHT CO.
To:
Shared Package
ML20214H604 List:
References
NUDOCS 8705280296
Download: ML20214K037 (3)


Text

.

PLANT SYSTEMS 3/4.7.7 CONTROL ROOM EMERGENCY HABITABIITY SYSTEMS LIMITING CONDITION FOR OPERATION i

c. With one open series normal air intake or exhaust isolation damper inoperable and not capable of closing, restore all series dampers to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

col With both series normal air intake or exhaust isolation dampers inoperable and not capable of being closed, the requirements of 3.0.3 are applicable and movement of. irradiated fuel or movement of loads over irradiated fuel shall be suspended.

d. With the control room air temperature >88"F but i 105*F, return the temperature to 188'F in 7 days or be in at least HOT STANDBY within' the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

d.1 With the control room air temperature > 105*F, be in at least HOT STANDBY within the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

l l

j 8705280296 870514 PDR ADOCK 05000334 P PDR 1, BEAVER VALLEY - UNIT 1 3/4 7-16A PROPOSED WORDING

1 l

e PLANT SYSTEMS T

SURVEILLANCE REQUIREMENTS,-(continued)-

4. Verifying that one emergency ventilation subsystem.

maintains the. control . room at a. positive' pressure of' 11/8 inch Water Gauge relative .to. the. outside )

atmosphere during system operation. j

5. Verifying that- the heaters dissipate 5 +-0.5-kw when .

tested in accordance with. ANSI N510-1980.

4.7.7.2 The bottled air pressurization system.shall be demonstrated OPERABLE:

a. At least once per 31 days by verifying that the-system l contains a minimum of 10 bottles of air each l pressurized to at least 1825 psig and-by verifying that

'the system solenoid operated valves are powered from an operable emergency bus.

b. At least once per 18 months be verifying that: l
1. A chlorine / control room high radiation / containment phase B isolation ' test signal'from either Unit
  • will initiate system operation.
2. Upon a partial discharge test using four out'of five bottled air subsystems the system will supply 1 1000 cfm of air and pressurize the control room to 11/8 inch Water Gauge relative to the.outside atmosphere during system operation.**

l 1

l

  • Input from Unit 2 is not applicable until prior to initial' entry.

into MODE 4.

    • A one-time one-hour discharge test has been' performed utilizing four out of five bottled air subsystems demonstrating the bottled air pressurization system will maintain the combined control' room at a positive pressure of 11/8 inch Water Gauge relative to the ,

outside atmosphere.

BEAVER VALLEY UNIT 1 3/4 7-18b PROPOSED WORDING

e 4

PLANT SYSTEMS LIMITING CONDITION FOR OPERATION c.1 With both series normal air intake or exhaust isolation dampers inoperable # and not capable of being closed, suspend all operations involving movement of irradiated fuel or movement of loads over irradiated fuel.

SURVEILLANCE REQUIREMENTS 4.9.15.1 The emergency ventilation subsystems and the bottled air pressurization system shall be demonstrated OPERABLE in accordance with Specifications 4.7.7.1.1, 4.7.7.1.2 and 4.7.7.2 with the following exception:

a. Automatic operation upon receipt of a containment phase B isolation signal is not required.

i

  1. Emergency backup power not required for any 1 of 2 series dampers.

BEAVER VALLEY - UNIT 1 3/4 9-17 PROPOSED WORDING