ML20155J016

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Page 3/4 1-15,re Reactivity Control Sys
ML20155J016
Person / Time
Site: Beaver Valley
Issue date: 11/03/1998
From:
DUQUESNE LIGHT CO.
To:
Shared Package
ML20155J015 List:
References
NUDOCS 9811100403
Download: ML20155J016 (2)


Text

-

... -. ~... -... ~ - -.... -.... -

NPF-73 l

3.

REACTIVITY CONTROL SYSTEMS BORATED WATER SOURCES - OPERATING 1

LIMITING CONDITION FOR OPERATION 3.1.2.8 As a minimum, the following borated water source (s) shall j

i.

be OPERABLE as required by Specification 3.1.2.2.

i j

a.

A boric acid storage system with:

1.

A minimum usable volume of 13,390 gallons, l

)

i i

2.

Between 7000 and 7700 ppm of boron, and j

j 3.

A minimum solution temperature of 65'F.

]~

1 b.

The refueling water storage tank with:

1.

A minimum usable volume of 859,248 gallons, l

1-2.

A boron concentration between 2000 and 2100 ppm, and i

j 3.

A solution temperature of 2 45'F and s 50*F.

APPLICABILITY:

MODES 1, 2,

3 & 4.

ACTION:.

a.

With the boric acid storage system inoperable, restore the i

storage-system to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY and borated to a SHUTDOWN MARGIN equivalent to at least 14 Ak/k at 200*F within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore the boric acid storage system to OPERABLE status within the next 7 days or be in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the refueling water storage tank incperable, restore the tank to OPERABLE status within one hour or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.1.2.8 Each borated water source shall be demonstrated OPERABLE:

9811100403 981103 M

PDR ADOCK 05000412 ^-

P PDR a

BEAVER VALLEY - UNIT 2 3/4 1-15 Amendment No.

ATTACHMENT B Change Summary License Amendment Unit Reauest Tvoed Pages Editorial Channes 2

130 3/41-15 Added License Number "NPF-73" to upper left corner of page.

.--