OPERATING DATA REPORT 4

DOCKET NO.- 50-341 COMPLETED BY L. P. Bregni

-DATE March 13, 1987 TELEPHONE (313)586-1617 OPERATING STATUS 1.

UNIT NAME:

Fermi 2 l Notes l

2.

REPORTING PERIOD: January l

l 3

LICENSED THERMAL POWER (MWt): 3292 l

l 4.

NAMEPLATE RATING (GROSS MWe):

1215 l

I 5

DESIGN ELECT RATING (Net W e): 1093

_ l I

6.

MAX DEPENDABLE CAP (GROSS MWe):

l l

J 7

MAX DEPENDABLE CAP (Net MWe):

l l

8.

IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS: None 9

POWER LEVEL TO WHICH RESTRICTED, IF ANY (MWe Net):

218.6

10. REASONS FOR RESTRICTION, IF ANY: Fermi 2 is in the startup test phase and is currently authorized to operate not in excess of 20% of rated thermal-power.

(Ref. J. G. Keppler letter of September 12, 1986)

THIS MONTH YR '!O DATE CUMULATIVE

11. HRS IN REPORTING PERIOD 744 744 3178.9
12. HRS REACTOR WAS CRITICAL 361.7 361.7 1,231.5 i
13. REACTOR RESERVE SHUTDOWN HRS 0

0 0

i

14. HOURS GENERATOR ON-LINE 54.1 54.1 183.6

)

15. UNIT RESERVE SHUTDOWN HOURS 0

0 0

16. GROSS THERMAL ENERGY GEN (HWH) 124,128 124,128 347,376
17. GROSS ELECT ENERGY GEN (MWH) 5,620 5,620 16,070
18. NET ELECT ENERGY GEN (MWH)

-7,695

-7,695

-33,654 i

19. UNIT SERVICE FACTOR N/A N/A N/A
20. UNIT AVAILABILITY FACTOR N/A N/A N/A 21.~ UNIT CAP FACTOR (USING MDC NET)

N/A N/A N/A

22. UNIT CAP FACTOR (USING DER NET)

N/A N/A N/A

23. UNIT FORCED OUTAGE RATE N/A N/A N/A l
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, DURATION OF EACH) l Maintenance Modification Outage, Completion of Test Condition 2, 14 days l-
25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: N/A
26. UNITS IN TEST STATUS (PRIGH TO COMMERCIAL OPERATION):

FORECAST ACHIEVED INITIAL CRITICALITY 06/20/85 06/21/85 INITIAL ELECTRICITY 10/01/86 09/21/86 COMERCIAL OPERATION 05/01/87 8703$90 b Y O Sh PDR ADOCK 05000341 R

P5R

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50-341 UNIT FERMI 2 DATE March 13, 1987 COMPLETED BY L. P. Bregni TELEPHONE (313) 586-1617 MONTH January DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1 95 17 0

2 81 18 0

3 0

19 0

4 0

20-0 5

60 21 0

6 0

22 0

7 0

23 0

8 0

24 0

9 0

25 0

10 0

26 0

11 0

27 0

12 0

28 0

13 0

29 0

14 0

30 0

15 0

31 68 16 0

l I

I 1

UNIT SHUTDONNS AND POWER REDUCTIONS I

DOCKET NO.

50-341 DATE March 13. 1987 l

(

UNIT NAME Fermi 2 COMPLETED BY L.

P.

Brenni l

TELEPHONE (313)S86-1617 REPORT MONTH January I

l l

METHOD OF LER SYS COMP CAUSE & CORRECTIVE NO.

DATE TYPE DUR REASON SHUTTING DOWN NO.

CODE CODE ACTION TO PREVENT (1)

(HRS)

(2)

THE REACTOR (4)

(5)

RECURRENCE (3) 87-01 870102 F

71.3 A

9 N/A CC PIPEXXA Reactor was not shut down.

The l

turDine-generator was shut down I

after three small steam leaks were i

\\

detected. The leaks were from l

broken spare instrument lines located between the turbine l

l control valves and the turbine -

I generator. Steam is being directed to the main condenser.

l j

87-02 ( 870105 F

618.6 A

2 N/A CC PIPEXxA On January 5 testing was completed I

on automatic voltage regulator A while the turbine generator was on line.

Shut down to inspect and repair welds on instrument taps attached to the main steam lines.

Outage scope was expanded to in-c1ude work on the Control Center HVAC Chiller.

1 (1) F: FORCED (2) REASON:

(3) METHOD:

(4) EXHIBIT G - INSTRUCTIONS S: SCHEDULED A - EOUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE OR TEST 2 - MANUAL SCRAM ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOMATIC SCRAM EVENT REPORT (LER) FILE D - REGULATORY RESTRICTION 4 - CONTINUED (NUREG-0161)

E - OPERATOR TRAINING & LICENSE EXAMINATION 5 - REDUCED LOAD i

F - ADMINISTRATIVE 9 - OTHER i

G.- OPERATIONAL ERROR (EXPLAIN)

H - OTHER (EXPLAIN)

(5) EKH1 BIT I - SAME SOURCE l

,