ML20132G982
ML20132G982 | |
Person / Time | |
---|---|
Site: | Wolf Creek |
Issue date: | 12/20/1996 |
From: | Muench R WOLF CREEK NUCLEAR OPERATING CORP. |
To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
Shared Package | |
ML20132G984 | List: |
References | |
ET-96-0106, ET-96-106, NUDOCS 9612270102 | |
Download: ML20132G982 (2) | |
Similar Documents at Wolf Creek | |
---|---|
Category:OPERATING LICENSES-APPLIATION TO AMEND-RENEW EXISTING
MONTHYEARML20212F8831999-09-21021 September 1999
[Table view]Application for Amend to License NPF-42,proposing to Modify Effective Full Implementation Date for Amend 120 from 991231 to 000630 ML20209D3561999-07-0808 July 1999 Application for Amend to License NPF-42 to Revise Allowable Value for CTS Table 3.3-4,functional Unit 8.a.,4 Kv Undervoltage - Loss of Voltage & Functional Unit 8.b.,4 Kv Undervoltage - Grid Degraded Voltage.Se & Nshc,Encl ML20209C2001999-06-30030 June 1999 Application for Amend to License NPF-42 for Temporary Change to CTS Without Action to Reduce Power ML20195G0211999-06-11011 June 1999 Application for Amend to License NPF-42,revising TS 3.7.1.6 & Associated Bases.Proposed Change Would Modify LCO to Require Four ARVs to Be Operable;Eliminate Use of Required in Action Statements;Add New Action for Three or More ARVs ML20195F7801999-06-10010 June 1999 Application for Amend to License NPF-42,proposing to Revise Z,S & Allowable Value Terms for Current TS Table 3.3-4, Functional Unit 7.b,automatic Switchover to Containment Sump (RWST Level - Low-Low) ML20207L0401999-03-0505 March 1999 Suppl 1 to 970515 Application for Amend to License NPF-42 Incorporating Changes to WCGS TSs & Adding License Conditions to Address Surveillance Requirements.Suppl Submits Mods Submitted to NRC During Review Process ML20199G7211999-01-15015 January 1999 Application for Request of Partial Issuance of Amend to License NPF-42,proposing TS SR Be Revised to Delete During SD Requirement & Reflect Appropriate Plant Conditions in Associated 3/4.7.3 Bases ML20199F4411999-01-12012 January 1999 Application for Amend to License NPF-42,to Revise TS 3/4.7.5 by Adding New Action Statement Requiring Verification of Operability of Two RHR Trains,Or Initiation of Power Reduction with Only One RHR Train Operable ML20198P1161998-12-29029 December 1998 Application for Amend to License NPF-42,revising Tech Specs to Incorporate Revised RCS Heatup & Cooldown Limit Curves & Revised Cold Overpressure Mitigation Sys (COMS) PORV Setpoint Limit Curve ML20195E5421998-11-10010 November 1998 Suppl Application for Amend to License NPF-42,transferring Control of Kg&E & Kansas Power & Light Possessory Ownership Interests to Westar Energy,Inc ML20155C4481998-10-26026 October 1998 Application for Amend to License NPF-42,transferring Kansas Gas & Electric Co & Kansas City Power & Light Co Interest in Operating Subject License for WCGS & Reflecting Transfer of Ownership ML20154S5651998-10-23023 October 1998 Application for Amend to License NPF-42,revising TS 3.5.1 by Increasing AOT in Action B. to 24 Hours in Lieu of Current AOT of One Hour ML20236R4711998-07-17017 July 1998 Application for Emergency Amend to License NPF-42 Revising TS 3/4.7.5, UHS, by Adding New Action Statement ML20247F8551998-05-0808 May 1998 Application for Amend to License NPF-42,revising TS 3/4.3.2, Table 3.3-3,ESF Actuation Sys Instrumentation ML20216J8151998-03-20020 March 1998 Application for Amend to License NPF-42,increasing Spent Fuel Storage Capacity & Max Nominal Fuel Enrichment to 5.0 W/O (Nominal Weight Percent) U-235.Proprietary & non-proprietary Holtec Repts,Encl.Proprietary Encl Withheld ML20202D1171998-02-0404 February 1998 Application for Amend to License NPF-42,revising TS 3/4.2.4, Quadrant Power Tilt Ratio & Associated Bases, to Clarify Required Actions for Limiting LCO & Other Change Consistents W/Ts Conversion Application Previously Submitted ML20202C4501998-02-0404 February 1998 Application for Amend to License NPF-42,revising Tech Specs 3/4.3, Changes to ESFAS Functional Units 6.f,8.a & 8.b ML20199H3431998-01-28028 January 1998 Application for Amend to License NPF-42,revising TS 6.3 & 6.12 to Reflect Position Change within Organization ML20198Q4321997-11-0606 November 1997 Application for Amend to License NPF-42,revising TS Sections 3/4.8.1,3/4.8.2 & 3/4.8.3 Re Installation of Spare Battery Chargers ML20217K2121997-10-17017 October 1997 Application for Amend to License NPF-42,revising TS Surveillance Requirements 4.5.2b & Associated Bases Re Requirement to Vent ECCS Pump Casings ML20216F7121997-09-0606 September 1997 Application for Amend to License NPF-42,alleviating Need for Enforcement Discretion Granted by NRC on 970905 ML20216D1471997-09-0202 September 1997 Application for Amend to License NPF-42,adding Requirements for Essential Svc Water Flowpaths to Turbine-Driven Auxiliary Feedwater Pump ML20196J3991997-07-29029 July 1997 Application for Amend to License NPF-42,revising Wording of Action Statement 5a to TS Table 3.3-1, Reactor Trip Sys Instrumentation ML20141G7641997-07-0303 July 1997 Application for Amend to License NPF-42,incorporating Addl Info Into TS 6.9.1.9, Colr ML20141F4361997-05-15015 May 1997 Application for Amend to License NPF-42,requesting Approval of Full Conversion of TS from Current to Set Based Upon Improved Std Ts,Per NUREG-1431 ML20138B9011997-04-23023 April 1997 Application for Amend to License NPF-42,revising TS 3/4.9.4, Containment Bldg Penetrations & Associated Bases Section to Allow Selected Containment Isolation Valves to Be Opened Under Administrative Controls During Core Alterations ML20137X3211997-04-15015 April 1997 Suppl to Application for Amend to License NPF-42,requesting TS 6.8.5.b, Reactor Coolant Pump Flywheel Insp Program ML20147F8121997-03-21021 March 1997 Application for Amend to License NPF-42,revising Tech Specs 6.8.5b Re Reactor Coolant Pump Flywheel Insp Program to Provide Exception to Exam Requirements in Reg Guide 1.14,Rev 1, Reactor Coolant Pump Flywheel Integrity ML20137B9311997-03-18018 March 1997 Application for Amend to License NPF-42,revising TS Section 5.3.1,fuel Assemblies to Allow Use of Alternate Zr Based Fuel Cladding Matl ZIRLO ML20137B8971997-03-18018 March 1997 Application for Amend to License NPF-42,revising TS SR 4.5.2.c to Clarify When Containment Entry Visual Insp Is Required ML20134Q0701997-02-17017 February 1997 Application for Amend to License NPF-42,revising TS 1.7, Containment Integrity, TS 3/4.6.1, Containment Integrity & TS 3/4.6.3, Containment Isolation Valves ML20132G9821996-12-20020 December 1996 Application for Amend to License NPF-42,requesting Rev to Bases for TS 3.8.1.1 Re Electrical Power Systems - AC Sources ML20135D8411996-12-0303 December 1996 Application for Amend to License NPF-42,requesting Rev to TS 6.8.5b Re Reactor Coolant Pump Insp Program ML20135D9781996-12-0303 December 1996 Application for Amend to License NPF-42,changing TS Table 3.3-3 to Correct Ref to Applicable Action Statement for Item 7.b,RWST Level - Low-Low Coincident W/Safety Injection ML20112A5471996-05-16016 May 1996 Application for Amend to License NPF-42,revising Tech Spec Surveillance Requirements 4.7.6.e.4 to Reflect Proposed Design Change to Output Rating of Charcoal Filter Adsorber Unit Heater in Pressurization Sys Portion CREVS ML20108C8191996-05-0101 May 1996 Application for Amend to License NPF-42,revising TS Section 6.0 to Reflect Position Title Changes within WCNOC Organization ML20101B0201996-03-0808 March 1996 Application for Amend to License NFP-42,revising TS Figure 2.1-1, Reactor Core Safety Limit - Four Loops in Operation, Table 2.2-1, RTS Instrumentation Setpoints, & Table 3.2-1, DNB Parameters ML20097D3281996-02-0808 February 1996 Application for Amend to License NPF-42,revising TS 3/4.6.1.1, Containment Integrity, TS 6.8.4i, Containment Air Locks & Adding TS 6.8.4i, Containment Leakage Rate Testing Program ML20097D3081996-02-0808 February 1996 Application for Amend to License NPF-42,revising TS 3.9.4 Re Containment Bldg Penetrations ML20099L7061995-12-20020 December 1995 Application for Amend to License NPF-42,revising TSs 3/4.6.1.1 & 3/4.6.1.3 to Incorporate Option B of 10CFR50,App J ML20095F8711995-12-13013 December 1995 Application for Amend to License NPF-42,revising TS Surveillance Requirement 4.1.3.1.3 to Delete Requirement for Performing Control Rod Drop Surveillance Test W/Tavg Greater than 551 F.Proprietary SE Encl.Se Withheld ML20095F0071995-12-13013 December 1995 Application for Amend to License NPF-42,revising Minimum & Maximum Flow Requirements for Centrifugal Charging & SI Pumps Specified in TS SR 4.5.2.h ML20095F9371995-12-13013 December 1995 Application for Amend to License NPF-42,revising TSs 3/4.8.2.1,3/4.8.2.2,3/4.8.3.1 & 3/4.8.3.2 Re Electrical Power Sys Dc Sources & Onsite Power Distribution ML20094P0591995-11-22022 November 1995 Application for Amend to License NPF-42,revising TS 3/4.3.1 to Reflect Deletion of Boron Dilution Mitigation Sys ML20094P0691995-11-22022 November 1995 Application for Amend to License NPF-42,revising TS 3.9.4 & Bases Section to Allow Containment Personnel Airlock Doors to Be Open During Core Alterations & Movement of Irradiated Fuel in Containment & TS 4.9.4 ML20094B3661995-10-24024 October 1995 Application for Amend to License NPF-42,revising TS SR 4.7.6.c,d & E to Reflect Proposed Design Change to Output Rating of Charcoal Filter Adsorber Unit Heater in Pressurization Sys of CR Emergency Ventilation Sys ML20093K6491995-10-18018 October 1995 Application for Amend to License NPF-42,replacing Current Fuel Oil Vol Requirement in EDG Day Tank in TS 3.8.1.1.b.1 & 3.8.1.2.b.1 W/ Fuel Oil Level Requirement ML20092J4071995-09-15015 September 1995 Application for Amend to License NPF-42,revising TS 3/4.8.1, Electrical Power Sys - AC Sources & Associated Bases, Proposing That Guidance of RG 1.9,Rev 3,GL 93-05 & 94-01 Be Adopted ML20092F5831995-09-14014 September 1995 Application for Amend to License NPF-42,revising TS 3/4.5.5, ECCS - RWST to Increase AOT of RWST for Adjustment of Boron Concentration from One H to Eight H ML20091K7851995-08-22022 August 1995 Application for Amend to License NPF-42,revising TS to Relocate Instrumentation Response Time Limits 1999-09-21 Category:TEXT-LICENSE APPLICATIONS & PERMITS MONTHYEARML20217D9751999-10-12012 October 1999
[Table view]Amend 128 to License NPF-42,increasing Allowable Values for Engineered Safety Features Actuation Sys loss-of-power 4 Kv Undervoltage Trips in Table 3.3-4 & in SR 3.3.5.3 ML20212F8831999-09-21021 September 1999 Application for Amend to License NPF-42,proposing to Modify Effective Full Implementation Date for Amend 120 from 991231 to 000630 ML20210T0271999-08-12012 August 1999 Amend 127 to License NPF-42,revising TS 3.7.1.6,SG Atmospheric Relief Valves & Associated Bases to Require Four Atmospheric Relief Valves to Be Operable ML20210T0001999-08-0909 August 1999 Amend 126 to License NPF-42,revising TS Table 3.3-4, Functional Unit 7,b.,Automatic Switchover to Containment Sump to Reflect Results of Calculations Performed for Associated Instrumentation Setpoints ML20209G2771999-07-0808 July 1999 Amend 125 to License NPF-42,revising TS 3/4.7.5 by Adding New Action Statement to Be Used in Event That Plant Water Temp Exceeds 90 Degrees ML20209D3561999-07-0808 July 1999 Application for Amend to License NPF-42 to Revise Allowable Value for CTS Table 3.3-4,functional Unit 8.a.,4 Kv Undervoltage - Loss of Voltage & Functional Unit 8.b.,4 Kv Undervoltage - Grid Degraded Voltage.Se & Nshc,Encl ML20209C2001999-06-30030 June 1999 Application for Amend to License NPF-42 for Temporary Change to CTS Without Action to Reduce Power ML20195G0211999-06-11011 June 1999 Application for Amend to License NPF-42,revising TS 3.7.1.6 & Associated Bases.Proposed Change Would Modify LCO to Require Four ARVs to Be Operable;Eliminate Use of Required in Action Statements;Add New Action for Three or More ARVs ML20195F7801999-06-10010 June 1999 Application for Amend to License NPF-42,proposing to Revise Z,S & Allowable Value Terms for Current TS Table 3.3-4, Functional Unit 7.b,automatic Switchover to Containment Sump (RWST Level - Low-Low) ML20206D4421999-04-27027 April 1999 Amend 124 to License NPF-42,revising TS 3/4.5.1, ECCS - Accumulators, by Increasing Allowed Outage Time with One Accumulator Inoperable for Reasons Other than Boron Concentration Deficiencies from 1 Hour to 24 Hours ML20205G1541999-03-31031 March 1999 Amend 123 to License NPF-42,converting CTSs for WCGS to Itss.Overall Objective of Proposed Amend Was to Rewrite, Reformat & Streamline CTS to Improve Safety & Understanding of Bases Underlying TSs ML20205B7671999-03-23023 March 1999 Amend 121 to License NPF-42,revising TS Tables 3.3-3,3.3-4 & 4.3-2 Requirements by Establishing Separate Requirements for Analog & Digital Portions of Associated Circuit ML20205B7001999-03-23023 March 1999 Amends 122 to License NPF-42,revising TS 4.7.3b, Plant Sys - Component Cooling Water Sys - Srs, by Deleting Requirement to Perform Specified Surveillances During Shutdown ML20205B8161999-03-22022 March 1999 Amend 120 to License NPF-42,revising TS to Support Mod to Plant to Increase Nominal Fuel Enrichment to 5% Percent Weight Percent U-235 ML20207L0401999-03-0505 March 1999 Suppl 1 to 970515 Application for Amend to License NPF-42 Incorporating Changes to WCGS TSs & Adding License Conditions to Address Surveillance Requirements.Suppl Submits Mods Submitted to NRC During Review Process ML20199G7211999-01-15015 January 1999 Application for Request of Partial Issuance of Amend to License NPF-42,proposing TS SR Be Revised to Delete During SD Requirement & Reflect Appropriate Plant Conditions in Associated 3/4.7.3 Bases ML20199F4411999-01-12012 January 1999 Application for Amend to License NPF-42,to Revise TS 3/4.7.5 by Adding New Action Statement Requiring Verification of Operability of Two RHR Trains,Or Initiation of Power Reduction with Only One RHR Train Operable ML20198P1161998-12-29029 December 1998 Application for Amend to License NPF-42,revising Tech Specs to Incorporate Revised RCS Heatup & Cooldown Limit Curves & Revised Cold Overpressure Mitigation Sys (COMS) PORV Setpoint Limit Curve ML20195E5421998-11-10010 November 1998 Suppl Application for Amend to License NPF-42,transferring Control of Kg&E & Kansas Power & Light Possessory Ownership Interests to Westar Energy,Inc ML20155C4481998-10-26026 October 1998 Application for Amend to License NPF-42,transferring Kansas Gas & Electric Co & Kansas City Power & Light Co Interest in Operating Subject License for WCGS & Reflecting Transfer of Ownership ML20154S5651998-10-23023 October 1998 Application for Amend to License NPF-42,revising TS 3.5.1 by Increasing AOT in Action B. to 24 Hours in Lieu of Current AOT of One Hour ML20151U0181998-08-31031 August 1998 Errata to Amend 119 to License NPF-42.Overleaf Page B 3/4 5- 2 Did Not Reflect Most Current Amend,Due to Administrative Error.Overleaf Page Also Provided to Maintain Document Completeness ML20236U8061998-07-21021 July 1998 Amend 119 to License NPF-42,adding New Action Statement to TS 3.5.1 Which Provides 72-hr AOT for One Accumulator to Be Inoperable Because Boron Concentration Did Not Meet 2300-2500 Parts Per Million Band ML20236S2071998-07-18018 July 1998 Amend 118 to License NPF-42,revising TS 3/4.7.5, Ultimate Heat Sink by Adding New Action Statement to Be Used in Event That Plant Inlet Water Temp Exceeded 90 F ML20236R4711998-07-17017 July 1998 Application for Emergency Amend to License NPF-42 Revising TS 3/4.7.5, UHS, by Adding New Action Statement ML20248D3841998-05-28028 May 1998 Amend 117 to License NPF-42,adding New Action Statement to TS 3/4.3.2,Table 3.3-3,Functional Unit 7.b., Refueling Water Storage Tank Level - Low-Low Coincident W/Safety Injection ML20247F8551998-05-0808 May 1998 Application for Amend to License NPF-42,revising TS 3/4.3.2, Table 3.3-3,ESF Actuation Sys Instrumentation ML20217K7991998-04-27027 April 1998 Amend 116 to License NPF-42,revising TS 3.2.4 & Associated Bases Re Quadrant Power Tilt Ratio ML20217J9801998-03-30030 March 1998 Amend 115 to License NPF-42,revising TS Sections 6.3 & 6.12 to Reflect Merger for Positions of Superintendent Radiation Protection & Superintendent Chemistry Into One New Position, Manager Chemistry/Radiation Protection ML20216J8151998-03-20020 March 1998 Application for Amend to License NPF-42,increasing Spent Fuel Storage Capacity & Max Nominal Fuel Enrichment to 5.0 W/O (Nominal Weight Percent) U-235.Proprietary & non-proprietary Holtec Repts,Encl.Proprietary Encl Withheld ML20203M6001998-02-27027 February 1998 Corrected Amend 101 to License NPF-42.Rev Due to Administrative Error Consisting of Omitted Sentence from TS Pp 6-18b That Should Have Been Included as Part of Amend 89 ML20202D1171998-02-0404 February 1998 Application for Amend to License NPF-42,revising TS 3/4.2.4, Quadrant Power Tilt Ratio & Associated Bases, to Clarify Required Actions for Limiting LCO & Other Change Consistents W/Ts Conversion Application Previously Submitted ML20202C4501998-02-0404 February 1998 Application for Amend to License NPF-42,revising Tech Specs 3/4.3, Changes to ESFAS Functional Units 6.f,8.a & 8.b ML20199H3431998-01-28028 January 1998 Application for Amend to License NPF-42,revising TS 6.3 & 6.12 to Reflect Position Change within Organization ML20198Q4321997-11-0606 November 1997 Application for Amend to License NPF-42,revising TS Sections 3/4.8.1,3/4.8.2 & 3/4.8.3 Re Installation of Spare Battery Chargers ML20199B1931997-11-0303 November 1997 Amend 114 to License NPF-42,revising TS 4.5.2b & Associated Bases to Eliminate Requirement to Vent Centrifugal Charging Pump Casings ML20212F5311997-10-20020 October 1997 Amend 113 to License NPF-42,revising Surveillance Requirements 4.3.1.2 & 4.3.2.2,TS 3/4.3.1 & 3/4.3.2 & Associated Bases of Sections B 3/4.3.1 & B 3/4.3.2 to Eliminate Periodic Response Time Testing Requirements ML20217K2121997-10-17017 October 1997 Application for Amend to License NPF-42,revising TS Surveillance Requirements 4.5.2b & Associated Bases Re Requirement to Vent ECCS Pump Casings ML20217G7041997-10-0707 October 1997 Amend 112 to License NPF-42,allowing Test of Certain Contacts in EDG Load Sequencer to Be Done W/Unit at Power (Mode I) & Providing Addl 24 Hrs to Time Allowed by TS 4.0.3 to Complete Testing ML20217D9161997-09-29029 September 1997 Amend 111 to License NPF-42,changing Wording of Action Statement 5a to TS Table 3.3-1, Reactor Trip Sys Instrumentation ML20217E3121997-09-22022 September 1997 Amend 110 to License NPF-42,modifying TSs 5.3.1, Fuel Assemblies, & 6.1.9.6, COLR, to Add ZIRLO as Fuel Matl & Use of Limited Zirconium Alloy Filler Rods in Place of Fuel Rods ML20216F7121997-09-0606 September 1997 Application for Amend to License NPF-42,alleviating Need for Enforcement Discretion Granted by NRC on 970905 ML20216D1471997-09-0202 September 1997 Application for Amend to License NPF-42,adding Requirements for Essential Svc Water Flowpaths to Turbine-Driven Auxiliary Feedwater Pump ML20196J3991997-07-29029 July 1997 Application for Amend to License NPF-42,revising Wording of Action Statement 5a to TS Table 3.3-1, Reactor Trip Sys Instrumentation ML20149E8631997-07-11011 July 1997 Amend 107 to License NPF-42 Revising TS to Allow Svc Air & Breathing Air Containment Penetrations to Remain Open Under Administrative Control During Periods of Core Alterations or Movement of Irradiated Fuel Inside Containment ML20141G7641997-07-0303 July 1997 Application for Amend to License NPF-42,incorporating Addl Info Into TS 6.9.1.9, Colr ML20141D9741997-06-24024 June 1997 Amend 106 to License NPF-42,revising TS 6.8.5.b to Provide Exception to Exam Requirements of RG 1.14,rev 1, RCP Flywheel Integrity, & Delays Insp of D RCP Flywheel to Fall 1997 Refueling Outage ML20148E0111997-05-28028 May 1997 Amend 105 to License NPF-42,reducing Containment Visual Insp Frequency,When Containment Integrity Is Required,From Every Entry to Once Per Day & During Final Entry ML20141F4361997-05-15015 May 1997 Application for Amend to License NPF-42,requesting Approval of Full Conversion of TS from Current to Set Based Upon Improved Std Ts,Per NUREG-1431 ML20138B9011997-04-23023 April 1997 Application for Amend to License NPF-42,revising TS 3/4.9.4, Containment Bldg Penetrations & Associated Bases Section to Allow Selected Containment Isolation Valves to Be Opened Under Administrative Controls During Core Alterations 1999-09-21 |
Text
. _
D
?
.c O,.
A Wf#LF CREEK NUCLEAR OPERATING CORPORATION Richard A. Muench Vice President Engineering i
December 20, 1996 t
ET 96-0106 U. S. Nuc2 ear Regulatory Commission i
ATTN: Document Control Desk Mail Station P1-137 Washington, D. C.
20555
Reference:
Letter dated August 9, 1996, from USNRC, to N.
S.
- Carns, WCNOC
Subject:
Change to Bases for Technical Specification 3.8.1.1,
" Electrical Power Systems - A. C. Sources" Gentlemen:
The Reference issued Amendment No.
101 to Facility Operating License No.
)
NPF-42 for Wolf Creek Generating Station (WCGS).
Amendment No. 101 revised i
Technical Specification 3/4.8.1, ' Electrical Power Systems-A. C. Sources," and its associated Bases to achieve an overall improvement in emergency diesel generator reliability and availability.
1 WCGS Technical Specification 3.8.1.1, Action b and Action c specify the required actions to be taken with inoperable A.
C.
electrical power sources.
Action b specifies the required actions to be taken within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> with one inoperable diesel generator.
Action c specifies the required actions to be taken within eight hours with one inoperable diesel generator and one offsite power circuit inoperable.
Review of the Bases, issued by the Reference, has identified that the second paragraph of Bases page B 3/4 8-2 should be revised to better define the time restraints associated with Technical Specification 3.8.1.1, Actions b and c.
The verbiage, which had been revised by Wolf Creek Nuclear Operating Corporation (WCNOC) in the Bases, does not make a distinction between the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> requirements of Action b and the eight hour requirements of Action c.
WCNOC is providing the revised Bases change to reflect this difference and i
requests that the NRC issue the revised Bases page change.
I
\\
9612270102 961220
}
PDR ADOCK 05000482 P
PDR P.O. Box 411/ Burhngton, KS 66839 i Phone: (316) 364-8831 An Equal Opporturuty Employer M FHCVET
I l
ET 96-0107 Page 2 of 2 If you should have any questions regarding this response, please contact me at (316) 354-8831, extension 4034, or Mr. Terry S. Morrill at extension 8707.
1 i
very truly yours, M44/
Richard A. Muench RAM /jad Attachment cc: L. -J. Callan (NRC), w/a j
W. D.
Johnson (NRC), w/a j
J.
F. Ringwald (NRC), w/a J. C.
Stone (NRC), w/a f