Other: ML19338D069, ML19338D073, ML19338F796, ML19338F800, ML19340B623, ML19340B933, ML19340C062, ML19345B102, ML20002B327, ML20003E180, ML20010G148, ML20037D564, ML20041B812, ML20054L849, ML20094B833, ML20099D014, ML20101Q590, ML20108D862, ML20112H308, ML20125E193, ML20126J293, ML20126L925, ML20137E998, ML20137T681, ML20141M903
|
MONTHYEARML19338D0691980-08-29029 August 1980 Forwards Order Requiring Info Supporting Environ Qualification of safety-related Electrical Equipment. Requests Submittal of Info by 801101 Project stage: Other ML19338D0731980-08-29029 August 1980 Order for Mod of License DPR-54 to Add Info Which Fully Responds to NRC Request for Info Re Environ Qualification of safety-related Electrical Equipment.Info Should Be Submitted by 801101 Project stage: Other ML19338F7961980-09-19019 September 1980 Forwards Revised Order for Mod of License Which Requires Submission of Info to Support Environ Qualification of safety-related Electrical Equipment Project stage: Other ML19338F8001980-09-19019 September 1980 Revised Order for Mod of License Requiring Timely Submission of Info Previously Requested Re Environ Qualification of safety-related Electrical Equipment Project stage: Other ML19340B6231980-10-24024 October 1980 Revised Tech Spec Pages Per 801024 Order for Mod of License Re Environ Qualification of safety-related Electrical Equipment Project stage: Other ML19340C0621980-10-31031 October 1980 Forwards Final Response to IE Bulletin 79-01B & Suppls 1-3, Environ Qualification of Class IE Equipment. All Outstanding Items Identified Will Be Reviewed by 820630 Project stage: Other ML19340B9331980-11-0505 November 1980 RO 80-44:providing Addl Info on Inability to Obtain Qualification Documentation for Meletron Pressure Switches. Review Concluded Two Credible Failure Modes,Short & Ground, Would Not Produce Malfunction.Interim Operation Justified Project stage: Other ML19345B1021980-11-12012 November 1980 Forwards Response to IE Bulletin 79-01B, Environ Qualification of Class IE Equipment Project stage: Other ML20002B3271980-12-0505 December 1980 Requests,On Behalf of Util,Extension Until 810108 to Request Hearing Re NRC 801118 Order for Mod to License.Requested Extension Would Allow for Better Understanding of Order Requirements Project stage: Other ML20126L9251980-12-15015 December 1980 Technical Evaluation Rept, Environ Qualification of Safety- Related Electrical Equipment to Harsh Environs Project stage: Other ML19347D4811981-03-17017 March 1981 Forwards Preliminary Results of NRC Review of Environ Qualification of safety-related Electrical Equipment at Facility.Identified Deficiencies & Ramifications Should Be Reviewed & Overall Findings Submitted Project stage: Approval ML20003E1801981-03-27027 March 1981 Advises of Safe Operation of Facility Re Equipment Function, Qualification & Environ Conditions for Electrical Equipment, Per Conditions Identified in 801031 Response to IE Bulletin 79-01B,in Response to NRC Project stage: Other ML18086B7001981-05-29029 May 1981 Forwards Safety Evaluation Re Environ Qualification of safety-related Electrical Equipment & Technical Evaluation Rept, Environ Qualification of Safety-Related Electrical Equipment to Harsh Environs Project stage: Approval ML20126L9191981-05-29029 May 1981 Safety Evaluation Re Environ Qualification of safety-related Electrical Equipment.No Outstanding Items Requiring Immediate Corrective Action.Completion of Corrective Actions by 820630 Will Ensure Compliance W/Nrc 800523 Memorandum Project stage: Approval ML20004F9921981-06-12012 June 1981 Requests Notification within 90 Days of Receipt of Safety Evaluation Re Intention to Pursue Hearing Request Project stage: Approval ML20037D5641981-08-14014 August 1981 Informs of NRC 810731 Recommendation to Extend 820630 Deadline for Hearing Re Environ Qualification of safety- Related Equipment to 830630 W/Limited Provisions for Further Extensions.Response Requested by 810901 Project stage: Other ML20010E6161981-09-0101 September 1981 Affirms NRC Proposing That Util Request for Extension of Time to Request Hearing Be Held in Abeyance for Up to 30 Days After Commission Has Completed Action on Petition to Extend 820630 Deadline for Environ Actions Project stage: Request ML20010G1481981-09-0808 September 1981 Forwards Info Re Environ Qualification of safety-related Electrical Equipment,In Response to NRC .Sys Component Evaluation Worksheets Revised by Encl Info Will Be Submitted by 811101 Project stage: Other ML20039B7301981-12-21021 December 1981 Request for Addl Info Re Equipment Environ Qualification Review of Licensees Resolution of Outstanding Issues from NRC Equipment Environ Qualification Safety Evaluation Repts & TMI Action Plan Installed Equipment Project stage: Request ML20041B8121982-02-17017 February 1982 Responds to NRC Requesting Info Re Pipe Breaks Outside Containment.Calculations for Determining Temp Profiles Encl.Util Not Aware of Beta Attenuation Calculation,However,Beta Dose Calculation Has Been Included Project stage: Other ML20054L8491982-07-0101 July 1982 Forwards Current Schedule for Installation of Qualified Electrical Equipment.Evaluation Worksheets & Test Repts Have Not Been Sent for Item II.D.3, Valve Position Indication, Since Five of Six Units Tested Failed Project stage: Other ML20085J3351983-10-10010 October 1983 Discusses 831013 Meeting to Resolve Deficiencies Noted in Franklin Research Ctr Technical Evaluation Rept Re Environ Qualification of safety-related Electrical Equipment.Agenda & Supporting Documentation Encl Project stage: Meeting ML19306E5041984-03-23023 March 1984 Notification of 840516 Meeting W/Util in Bethesda,Md to Discuss & Resolve All Outstanding Equipment Environ Qualification Issues for Facility.List of Attendees & Viewgraphs Encl Project stage: Meeting ML20094B8331984-08-0202 August 1984 Requests Extension of Qualification Program Completion Schedule to End of June 1985 Refueling Outage for Crosby Lift Indicating Switch Assemblies & Veam Thermocouple Connectors Project stage: Other ML20099D0141984-10-30030 October 1984 Notice of Environ Assessment & Finding of No Significant Impact Re 840802 Request for Extension of Deadline for Final Environ Qualification of Certain Electrical Equipment Important to Safety Project stage: Other ML20099D9351984-11-15015 November 1984 Submits Addl Info Re 841109 Tech Spec Change Request 102 Concerning Overpower & Overtemp Delta Temp Compensation Project stage: Request ML20101A2221984-12-13013 December 1984 Forwards Manufacturer Response Time Test Results to Suppl Info Provided in Re Overtemp & Overtemp delta-T Lag Compensation Project stage: Request ML20101Q5901984-12-28028 December 1984 Forwards Fee for Extension of Deadline for 840802 Environ Qualifications Per .Fee Paid Project stage: Other ML20108D8621985-03-0101 March 1985 Requests Further Extension of 850331 outage-based Equipment Qualification Deadline for Hydrogen/Oxygen Analyzers.Revised Schedule for Completion of Qualification Testing on Hydrogen/Oxygen Analyzers Encl Project stage: Other ML20112H3081985-03-27027 March 1985 Requests Expedited Relief from Current 850331 Equipment Qualification Deadline for Facility Drywell & Oxygen Analyzers Until 851130 Due to Recent Change in Schedule for Upcoming Refueling Outage Project stage: Other ML20112H1641985-03-28028 March 1985 Forwards Rev 2 to Inservice Testing Program,Point Beach Nuclear Plant Units 1 & 2, as Part of Pump Relief Request 9.Requests That NRC Grant Interim Approval for Pump Relief Request Project stage: Request ML20100L0171985-04-0909 April 1985 Forwards Application Fee,Per NRC ,To Cover 850301 Request for Extension of 10CFR50.49 Equipment Qualification Deadline for Drywell Hydrogen & Oxygen Analyzers Currently Installed at Facility Project stage: Request ML20125E1931985-06-0505 June 1985 Advises of Fees Due for 841111 & 850502 Applications for Amends to Licenses DPR-24 & DPR-27 Re Environ Qualification of Water Regulating Valves & Lift Indicating Assemblies.Fees Due Irrespective of NRC Disposition of Application Project stage: Other ML20126J2931985-06-11011 June 1985 Authorizes Implementation of Proposed ASME Code Pump & Valve Inservice Testing Programs to Be Completed No Later than 850801,per 850328 Request for Relief from Requirements Project stage: Other ML20128A0391985-06-28028 June 1985 Submits Supplemental Info Re Questions Raised During Equipment Qualification (EQ) Insp During Wk of 850520. T-drains on Limitorque Motor Operators Replaced W/Plugs.All EQ Procedures Approved & Ready for Use Project stage: Supplement ML20137E9981985-08-16016 August 1985 Notifies of Problems That May Necessitate Extension of Equipment Qualification Deadline for Primary Containment Hydrogen & Oxygen Gas Analyzers,Per 10CFR50.49(h).Revised Testing Schedule for Analyzers Encl Project stage: Other ML20137T6811985-11-27027 November 1985 Provides Status of Environ Qualification Effort for Drywell Hydrogen & Oxygen analyzers.Architect-engineer Determined Equipment Located in Mild Environ Will Remain Operable During & for at Least 180 Days Following LOCA Project stage: Other ML20141M9031986-02-24024 February 1986 Requests Commitment of Necessary Resources to Address Policy Issues Delaying Resolution of Inservice Testing Program Matters.Interim Relief for Several Inservice Testing Requirements Due to Delay Also Requested Project stage: Other 1982-07-01
[Table View] |
Text
WISCONSIN Electnc rowra coursur 231 W. MICHIGAN, P.O. BOX 2046. MILWAUKEE, WI 53201 March 28, 1985 Mr.
H.
R. Denton, Director Office of Nuclear Reactor Regulation U.
S. NUCLEAR REGULATORY COMMISSION Washington, D.
C.
20555 Attention:
Mr. J.
R. Miller, Chief Operating Reactors, Branch 3 Gentlemen:
DOCKET NOS. 50-266 AND 50-301 INSERVICE TESTING PROGRAMS FOR PUMPS AND VALVES POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 By letter dated January 16, 1984, Wisconsin Electric Power Company (Licensee) submitted the Point Beach Nuclear Plant, Units 1 and 2, pump and valve inservice test programs and associated relief requests.
Subsequent to the above submittal, we have determined that one additional pump relief request is necessary to allow for an optimum testing program.
Thus, we are hereby submitting pump relief request No. 9 for your review and approval.
Pump relief request No. 9 is submitted in addition to the relief requests submitted in January 1984.
All of the relief requests submitted January 1984 are still valid.
In a letter dated February 29, 1984 we committed to adding the reactor coolant vent system to the inservice test program and to providing you with an amended program.
Thus, in view of our commitment, we have revised the program to include the applicable valves of the reactor coolant gas vent system and have attached the revised programs.
This Revision 2 also includes minor changes of an editorial nature.
These changes include correcting typographical errors and updating piping and instrumentation diagram coordinate locations to reflect current drawing revisions.
The attached inservice testing programs for Point Beach Units 1 and 2 were developed in compliance with the rules and regulations of 10 CFR 50.55a and Section XI of the ASME Boiler and Pressure Vessel Code, 1977 Edition through Summer 1979 Addenda.
These programs are for the 120-month interval, as stipulated in 10 CFR 50.55a (g) (4) (ii).
These programs are to replace in their entirety the previous submittals for pump and valve testing for 8504020161 850320
~1-i PDR ADOCK 05000266 P
PDR
7
/
Mr.
H. R. Denton March 28, 1985 both units.
These new programs are submitted for your review.
The requested reliefs are submitted for your review and approval.
The reliefs requested and the bases for the reliefs are presented in Appendices " A" and "B"
for the pump and valve testing programs, respectively.
As discussed in the basis for each relief requested, we believe that conformance with the specific code requirement is impractical for the Point Beach facility and that pursuant to 10 CFR 50.55a(g) (6) the Commission is authorized to grant such relief.
On February 12, 1979, the Commission published in the Federal Register a notice concerning a revision to 10 CFR 50.55a which changed the basis for inservice inspection and testing requirements for safety class components of nuclear power plants.
The revised regulation requires that all nuclear power facilities meet, to the extent practical, the inservice inspection and testing requirements of Section XI of the ASME Boiler and Pressure Vessel Code, as specified in 10 CFR 50.55a(b).
Licensees were required at that time to update their inservice testing programs every 20 months.
Wisconsin Electric filed License Amendment Request Nos.
42 and 58 on February 17, 1977 and November 27, 1978 for Point Beach Nuclear Plant, Units 1 and 2, respectively, for Technical Specification changes necessitated by the revised inservice testing requirements, as required by the Code of Federal Regulations.
To date, only certain portions of the requested license amendments have been reviewed and approved by the NRC.
The Technical Specification changes previously referenced stand in agreement with these revised programs and should be expedited.
As we have previously stated, it is our position that approval of these outstanding Technical Specification change requests need to be completed prior to implementation of these new inservice testing programs.
However, pursuant to your order transmitted by letter dated March 4, 1985, the subject inservice testing programs will be implemented in conjunction with the existing Technical Specification testing requirements.
Previously, we have estimated that program implementation could be accommodated within 90 days.
This estimate was based upon receiving your approval of the relief requests and Technical Specification changes.
However, without receiving approval of the Technical Specification changes, a significant amount of additional manpower is required to establish interim testing The schedule impact of this additional effort is programs.
magnified by the n.anpower requirements associated with the Unit 1 Refueling 12 outage.
This outage is concurrent with a large portion of the implementation period and represents a
I F*
la Mr.
H.'R. Denton March 28, 1985-major in-house effort due to the associated activities, including control rod guide tube split pin replacement.
Thus, we'are requesting that you extend the implementation period to accommodate an August 1, 1985 implementation deadline.
During our review, it is possible that additional instrumentation may be needed to meet some requirements of the combined Technical Specification and inservice testing program.
These instrumentation. requirements should be identified early in the review process.
If any instrumentation additions will delay the full implementation schedule, you will be notified as soon as this information becomes available.
. In view of your requirement for implementation based on preliminary review, we are also requesting that interim approval for pump relief request No. 9 submitted with this letter also be granted.
Should you have any questions regarding the attached programs or require additional clarification or details, please contact us.
Very truly yours, h/
dd a Vice President-Nuclear Power C. W. Fay Enclosures Copy to NRC Resident Inspector
.J