(([ hofessional Loss Control, Inc.

I I

STRUCTURAL STEEL ANALYSIS for LIMERICK GENERATING STATION l

UNIT 1 Reactor Building El. 253' Main Steam &,Feedwater Pipe Tunnel Fire Zone 46 December 20, 1983

! I i

8401090698 840104 DR ADOCK 05000 P. O. Box 446 e Oak Ridge, Tennessee 37830 e (615) 482-3541 n

,e p

,-s

-ee

V T

a

(

LIMERICK GENERATING STATION 1.

AREA DESCRIPTION The area under consideration is the Main Steam and Feedwater Pipe Tunnel on the 253' elevation o'f the Unit 1 Reactor Building (Fire Area 46). The bound-ing walls in the area are of reinforced concrete with an average thickness j

of 3.5 feet.

The total surface arca for heat transfer is approximately 5858 l

ft, (See Attachment A for a sketch of the area under consideration and a 2

calculation of areas).

2.

COMBUSTIBLE LOADING All caoling in this area is routed in conduit, there are no cable trays.

There are no combustible liquids in this area.

2 3.

VENTILATION PARAMETERS There is one 3' wide by 5'10" high door serving this area.

4.

CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.

5.

RESULTS Tne structural steel in this area will not fail due to a fire as there are no fixed combustibles in the area to support a fire.

i l

4 6

1 i

O N

I 1.

t 4

6 i

f j

,7 Unit 1 Reactor Building El. 253' Main Steam and Feednater Pipe Tunnel Fire Zone 46 Surface Area Calculation Walls Nortn wall (40' x 29')

1160 ft2 East wall (40' x 33')

1320 ft2 South wall (40' x 30')

1200 ft2 West wall (10' x 33')

1320 ft2 5000 ft2 Ceiling Area 1 (30' x 30') - [(3.5' x 3.5') + (10' x 3')]

857.75 ft2 r tal Surface Area for Heat Transfer 5857.75 ft2 o

ATTACHMENT A

- -. -.