Structural Steel Analysis for Limerick Generating Station, Unit 1 Reactor Bldg Elevation 177-Ft Sump Room 115,Fire Area 39
ML20083H839
Person / Time
Site: Limerick 
Issue date: 12/20/1983
From:
PROFESSIONAL LOSS CONTROL, INC.
To:
Shared Package
ML20083H823 List:
References
NUDOCS 8401090485
Download: ML20083H839 (5)


Text

_

ATTAcnMlHT

\\lC s.

}(( Professional Loss Control Inc.

[Q ft GLC STRUCTURAL STEEL ANALYSIS for LIMERICK GENERATING STATION Unit 1 Reactor Building El.177' Sump Room, Room 115 Fire Area 39 December 20, 1983 8401090485 840104 PDR ADOCK 05000352 E

PDR P. O. Box 446 e Oak I?idge. Tennessec 3"S30 e (615) 43%3MI

._,_~.-y.%__m--.

4m--.

---e*-=y

LIMERICK GENERATING STATION 1.

AREA DESCRIPTION The area under consideration is tne Sump Room, Room 115, on the 177' eleva-tion of the Ur.it 1 Reactor Building (Fire Area 39). The bounding walls of the area are of reinforced concrete construction with an average thickness of 2.5 ft.

Tne total surface area for heat transfer is 2595 f t2 (see Attachment A for sketch and calculation of surface areas).

2.

COMBUSTIBLE LOADING The combustible loading in tnis area consists of cable insulation in cable trays. The total surface area of the cable trays is 96 ft2 with an average combustible loading of 1.5 lbs/ft2 of cable tray surface area. There are no combustible liquids in the area.

3.

VENTILATION PARAMETERS This room is open to tne Corridor Passageway, Roca 118. Tnere are two doors which enter into the Sump Room..One door measuring 3' wide by 5'10" high is located in the east wall, and one door measuring 3' wide by 7' high is located at the entrance to the stairwell.

4.

CASES EXAMINED Witn the lignt comoustible loading in this area, the assumption tnat all cables are burning simultaneously would present the worst case. With all cables burning siceltaneously, a surface area of 96 ft2 would be involved.

This corresponds to a heat output of approximately 1700 kW.

With all combustibles assumed to oe burning simultaneously, the duration of the fire would be 1.5 lbs/ft2 +.1 lb = 15 minutes.

min /ft2 5.

RESULTS With all the cable trays in the area assumed to be burning simultaneously and a 3' wide by 5'10" door open, the resulting fire was fuel controlled.

A gas temperature of 356'F was acnieved after 15 minutes, which is below the critical temperature for the structural steel (see Attachment 3),

1

+n w

n

- n,

,,e

.n--wwg y

---v--

The location of the cable trays relative to structural steel members was examined jn the area. No cable trays were positioned so as to present a localized neating exposure to the structural steel.

l l

2

r O

t O

p, W

- r.

Unit 1 Reactor Building El. 177' Sump Room 115 Surface Area Calculation Walls

' ~ North wall (24' x 23')

552 ft2 East wall (24' x 23' 552 ft2 South wall (21'x~23' 483 ft2 West wall (24' x 23')

552 ft2 2139 ft2 Ceiling (24' x 25') - (18' x 8')

456 ft2 Total Surface Area for Heat Transfer 2595 ft2 ATTACHMENT A e

4 S

, m-o a

'N yie wW wes y

g.pp

~y gg-ge in-

+g-w ce,.

p y

yea-,myw y-M4& w -gppgwgog19-,-

---i--

9gm-u-~,e%

vg.

-.e yu.

r gy-w y g,me w.--p-p--vg-w--,

  • wgc

C'ASE' NutiBER :

1 BUILDING:

UNIT 1 REACTOR DUILDING ELEVATION AND AREA DESCRIPTION:

177' SUMP ROOM FIRE 20tlE 39 CASE DESCRIPTION; ONE DOOR OPEN ALL CADLES BURNING X GMMW X X X X M XX X X MKM X X X MX X X X XM X X X X X X-X

  • X X X% XWX X X X X X X WW EM-X X 4XW X X XX X X X > X X XX% XM CEILING / WALL CEILING / WALL Ao Ho Aw Q

THICKNESS MATERIAL

'ft)

(ft2)

(f t)

(Pt2)

(ku) g g y..x. X X X K X X K X W M -X M M X W -X X X M X 4 X X X X X M X X X X X X X X -X X X u k X X X X X X X X X X X X X X M X X X X.t X X X X X W A 4 2.5 CONCRETE 17.5 5.3 2595 1700 FIRE IS FUEL CONTROLLED FIRE DURATION GAS TEMPERATURE (nin)

(deg,F) 1 147 2

177 3

200 4

219 5

237 6

252 7

266 8

200 9

292 10

~

304 11 315 12 326 13 337 14 346 15 356 ATTACHMEtiT B l

. _ _ _ _ _ _ - _ _ _ _ _.