ML20083J107

From kanterella
Jump to navigation Jump to search
Structural Steel Analysis for Limerick Generating Station, Unit 1 Reactor Bldg Elevation 177-Ft Corridor - Room 111, Fire Area 40
ML20083J107
Person / Time
Site: Limerick Constellation icon.png
Issue date: 12/20/1983
From:
PROFESSIONAL LOSS CONTROL, INC.
To:
Shared Package
ML20083H823 List:
References
NUDOCS 8401090681
Download: ML20083J107 (3)


Text

--

I , . _ _ . _ .

D(( Professional Loss Control, Inc.

t i

t 2

1 STRUCTURAL STEEL ANALYSIS l for

LIMERICK GENERATING STATION 1-UNIT 1 Unit 1 Reactor Guilding El .177' Corridor - Room 111 Fire Area 40 l

I i l

l 4 i

i i

December 20, 1983 l

i l

8401090681 840104 PDR ADOCK 050003S2 E PDR i

l P. O. Box 446

( .l

. . - - - . . . . ~

\b i

2 LIMERICK GENERATING STATION

1. AREA DESCRIPTION i The area under consideration is the Corridor (Room 111) on the 177' eleva-i tion of the Unit 1 Reactor Building (Fire Area 40) and contains the safety related HPCI pump discharge flow transmitters. The bounding walls of the
area are of reinforced concrete construction with an average thickness of 2 ft. The total surface area for heat transfer is 3953 ft 2. (SeeAttachment A for sketch and calculations of the area.)

I

2. COMBUSTIBLE LOADING There are no cable trays or combustible liquid: located in this area.

a

3. VENTILATION PARAMETERS Access doors connect to the stairwell, elevator shaf t, and Core pump spray rooms.
4. CASES EXAMINED ,,

With no exposed combustible cabling and no combustible liquids in the corridor, there is no fuel in the area to support a fire.

5. RESULTS The structural steel in this area will not fail since there are no fixed combustibles in the area to support a fire, i

I l

1 l

t 1

)

l

(

1 s

~

' I;. . b i _,

1

(_.

t i

,', ]br1 Unit 1 Reactor Building El. 177' Corridor - Room 111

, -Surfade Arei Calculation ^;

Walls North wall (24' x 23') 552 ft2 East wall- (51' x 23' 1173 ft2 South wall (24' x 23' 552 ft2

. West wall m (51' x 23') 1173 ft2 3450 ft2 Ceiling - (33' x 7') + (16' x 14') + (8' x 6') 503 ft2 Total Surface Area for Heat Transfer 3953 ft2 l

ATTACHMENT A

.' sL _ _ _ _ . . _ - . _ . . . . - . _ . , _ , - _. . . . . _ _ , _ . . _

_ , _ _ - . . . _ , _ . . _ _ . _ . _ , . . _ _ _ _ .