(([ Professional Loss Control, Inc.
STRilCTURAL STEEL ANALYSIS for LIMERICK GENERATING STATION f Unit 1 Reactor Building El. 177' Corridor Room 118 i
Fire Area 39 l
I 1
1 December 20, 1983 8401090490 840104 gDRADOCK05000 P. O. Box 446 e Oak Ridge. Tennessec 37830 e (615) 482 3541
m%
i LIMERICK GENERATING STATION 1.-
AREA DESCRIPTION The area under consideration is the Corridor and Passageway, Room 118, on
+he 177' elevation of the Unit 1 Reactor Building (Fire Area 39). The bounding walls of the area are of reinforced concrete construction with an average thickness of 2.5 ft.
The total surface area for heat transfer is 4976 ft2 (see Attachment A for sketch and surface area calculations).
2.
COMBUSTIBLE LOADING All cabling in this area is routed in conduit, there are no cable trays.
There are no combustible liquids in this area.
3.
VENTILATION PARAMETERS This room is open to the Sump Room, Room 115. There are also two doors, each measuring 3' wide by 5'10" high, located in the west wall of the area.
4.
CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.
5.
RESULTS The structural steel in the area will not fail due to a fire as there are no fixed combustibles in the area to support a fire, t
~!
A 1
j_
A
~ *.
v t
tL
(~
i t
1 b
/
I'
~
/
h i
n L_
l
.-,2 IJ.
Unit 1 Reactor Building El. 177' Corridor & Passageway Room 118 Surface Area Calculation Area 1 (Corridor)
Walls East wall (29' x 23')
667 ft2 West wall (29' x 23')
667 ft2 il' 1334 ft2 Ceiling (29' x 6')
174 ft2 Area.2 (Room 118) l Walls North wall (22' x 23')
506 ft2 l
East wall (31' x 23')
713 ft2 1
South wall (32' x 23')
736 ft2 West wall (31' x 23')
713 ft2 2668 ft2 Ceiling 800 ft2 l
Total Surface Area for Heat Transfer 4976 ft2 ATTACHMENT A i