e y(( IVofissional Loss Contrd, Inc.
1 STRUCTURAL STEEL ANALYSIS for LIMERICK GENERATING STATION Control Structure El. 332' Standby Gas Treatment System Filter Compartment Room 624 Fire Area 288 l
[
Oecember 20, 1983 8401090695 840104
{DRADOCK05000 P. O. Box 446
- Oak Ridge, Tennessee 37830 * (615) 482-3541
~
~
~ ~ ~ ~ ~ ^
LIMERICK GENERATING STATION 1.
AREA DESCRIPTION
- The area under consideration 1: the Standby Gas Treatment System Filter Compartment, Room 624, on the 332' elevation of the Control Structure (Fire Area 288). The bounding walls of the area are of reinforced concrete con-struction with an average thickness of 2 ft.
The total surface area for heat transfer is 5564 ft2 (see Attachment A for sketch and calculation of surface areas).
2.
COMBUSTIBLE LOADING All cabling in this area is routed in conduit, there are no cable trays.
There are no combustible liquids in this area.
3.
VENTILATION PARAMETERS There are three doors which enter this area. Two 3' wide by 7' high doors are located in the east wall and a 6' wide by 8' high double door is locatd in the west wall.
4.
CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.
5.
RESULTS The structural steel in this area will not fail due to a fire as there are no fixed combustibles in the area to support a fire.
1 1
j
?.
9 I
~
7 Control Structure El. 313' Standby Gas Treatment System Filter Compartment Surface Area Calculation Wall s North wall (78' x 17')
1326 ft2 South wall (78' x 17')
1326 t:2 East wall (26'x17')
442 ft2 West wall (26' x 17')
442 ft2 3536 ftc Ceiling (78' x 26')
2028 ft2 Total Surface Area for Heat Transfer 5564 ft2 ATTACHMENT A l