}(( Professional Loss Control, Inc.

1 STRUCTURAL STEEL ANALYSIS for LIMERICK GENERATING STATION Unit 1 Reactor Building El. 313'

. Reactor Vent Supply Fan Room Room 607 Fire Area 49 V

December 20, 1983 0401090665 040104 PDR ADOCK 05000352 E PDR P. O. Box 446 e Oak Ridge, Tennessec 37830 * (615) 482-3511

- .- - ~,-- ....- - __,

. LIMERICK GENERATING STATION

1. AREA DESCRIPTION

[ The area under consideration is the Reactor Vent Supply Fan Room, Room 607, on the 313' elevation of the Unit 1 Reactor Building (Fire Area 49). The

! bounding walls of the area are of reinforced concrete construction with an average thickness of 2 ft. The majority of the south wall is louvers open to the outside. The total surface area for heat transfer is 7720 ft? (see Attachment A for sketch Snd Calculatidn of surface areas).

2. COMBUSTIBLE LOADING Combustible loading in the area consists of the cable insulation located in cable trays. The total cable tray surface area is 89 ft2 with an average combustible loading of 3.5 lbs/ft2 of cable tray surface area. There are no combustible liquids in the area.
3. VENTILATION PARAMETERS The south wall of the area contains louvers whicn measure 16' high by 75' wide and are open to the outside.
4. CASES EXAMINED With the light combustible loading in the area, the assumption that all cable trays were burning simultaneously would present tne worst case. Witn all cables burning, a cable tray surface area of 89 ft2 would be involved.

This corresponds to a heat output of 1575 kW. With all combustibles burning simultaneously the fire duration would be 3.5 lbs/ft2 + .1 lbs = 35 minutes.

min /ft2

5. RESULTS With all cable trays in the area burning simultaneously and the large area of louvers, tne resulting fire was fuel controlled. A gas temperature of ,

207'F would be acnieved after 35 minutes, which is below the critical temperature for the structural steel (see Attachment B).

The position of tne cable trays relative to structrual steel members were examined in the area. No cable trays were positioned so as to present a localized heating exposure to the structural steel.

1

_ _ _ _ _ __.______-___-m_ _ _ _ _ _ _ _

o ---

, 6 e}=

_.Y -

N ,

l LOUVERS) -

I! nit 1 Reactor Building El. 313' Reactor Vent Supply Fan Room Room 607 Surface Area Calculation Walls North wall 111' x 16') 1776 ft2 South wall 38' x 16') 608 ft2 ,

East wall 40' x 16') 640 ft2 West wall 40' x 16') 640 ft2 Ceiling (111' x 40') - (12' x 16') airlock 4056 ft2 Total Surface Area for Heat Transfer 7720 ft2 ATTACHMENT A

, . s CASE NUMBER: 1 BUILDING: UNIT 1 REACTOR BUILDING ELEVATION A!4D AREA DESCRIPTION: 313' REACTOR VENT SUPPLY FAN ROOM CASE DESCRIPTION: LOUVERS OPEN ALL CABLES BURNING oce******x********************x*************************xx******xx******

CEILING / WALL CEILING / WALL Ao Ho Aw Q THICKNESS MATERIAL (ft) (ft2) (ft) (ft2) (kW) ocm*****************************x**********************************x****

2.O CONCRETE 1200 16.0 7720 1575 FIRE IS FUEL CONTROLLED FIRE DURATION GAS TEMPERATURE (nin) (deg.F) 5 123 10 144 15 160 20 174 25 186 30 197 35 207 O

e b

ATTACHMENT B

. _ _ _ _ _.