Application for Amend to License NPF-4,revising Tech Specs Re ESF Actuation Sys Instrumentation Surveillance Requirements to Conform to STS & Provide Consistency W/Unit 2 Tech Specs
ML20082A939
Person / Time
Site: North Anna Dominion icon.png
Issue date: 11/15/1983
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Harold Denton, John Miller
Office of Nuclear Reactor Regulation
Shared Package
ML20082A942 List:
References
646, NUDOCS 8311180304
Download: ML20082A939 (3)


Text

._

C, .

VInoINIA ELECTRIC AND Powsu COMPANY Rscitwoxo,VinorxrA 23261 W. L. Srawurr vaca P.smtonst wecm. o,.. mon. November 15, 1983 1

Mr. Harold R. Denton, Director Serial No. 646 Office of Nuclear Reactor Regulation N0/JHL:acm Attn: Mr. James R. Miller, Chief Docket No. 50-338 Operating Reactors Branch No. 3 License No. NPF-4 Division of Licensing U. S. Nuclear Regulatory Commissian Washington, D. C. 20555

';entlemen:

VIRGINIA ELECTRIC AND POWER COMPAhi NORTH ANNA POWER STATION UNIT NO. 1 PROPOSED TECHNICAL SPECIFICATION CHANGES Pursuant to 10CFR50.90, the Virginia Electric and Power Company requests an amendment, in the form of changes to the Technical Specifications, to Operating License No. NPF-4, for North Anna Unit No. 1.

North Anna Unit No. 1 Technical Specification Table 3.3-3 requires operability in MODES 1, 2 and 3 for the auxiliary feelwater pump actuation signals from Steam Generator Water Level-Low Low and Station Blackout. In contrast, Table 4.3-2 requires surveillance to be performed in MODES 1, 2, 3 and 4. The North Anna Unit No. 2 Technical Specifications and the Standardized Technical Specifications for Westinghouse Pressurized Water Reactors have surveillance required in MODES 1, 2 and 3 for these actuation signals. The proposed changes would therefore make the North Anna 1 Technical Specifications conform to changes in the approved Standardized rechnical Specifications and provide consistency with the North Anna 2 Technical Specifications. The proposed Technical Specification changes are provided in Attachment 1. A discussion of the proposed Technical Specification changes is provided in Attachment 2.

This request has been reviewed and approved by the Station Nuclear Safety and Operating Committee and the Safety Evaluation and Control Staff. It has been determined that this request does not pose an unreviewed safety question as defined in 10CFR50.59 or a significant hazards consideration as defined in 10CFR50.92.

We have reviewed this request in accordance with the criteria in 10CFR170.22.

Since this request involves a safety issue which the Staff should be able to determine does not involve a significant hazards consideration for Unit 1, a Class III license amendment fee is required. A check in the amount of $4,000 is enclosed in payment of the required fee. \

8311180304 831115 Very truly yours' i PDR ADOCK 05000338 - I 1

P PDR '

. . W .

W. L. Stewart

& ff -

G *

.s

.vsastuu Es.actasc Awn Powsu CourAwr To Harold R. Denton Attachments:

~1. ' Proposed Techtlical Specification Changes.

2. Discussion of Proposed Technical Specification Changes.

. 3. Voucher Check for $4,000.

cc: Mr. James P. O'Reilly Regional Administrator Region II' Mr. M. B; Shymlock NRC Resident Inspector North Anna Power Station Mr. Charles Price Department'of Health 109 Governor Street Richmond,-Virginia 23219

.J

6 CG010NWEALTH OF VIRGINIA )

)

CITY OF RICHMOND )

The foregoing document was acknowledged before me, in and for the City and '

Consnonwealth aforesaid, today by W. L. Stewart who is Vice President -

Nuclear Operations, of the Virginia Electric and Power Company. He is duly authorized to execute and file the foregoing docuuent in behalf of that Company, and the statements in the document are true to the best of his knowledge and belief.

Acknowledged before me this /f d

day of D-- . # . . , 19 33 ,

My Comission expires: 4 Jd , 19 2i ,

h <2 . Ww

' Notary Public 1

i I

(SEAL) s/001