Responds to IE Bulletin 79-01.One Solenoid Installed on safety-related Valve in Plant Containment Has Not Been Qualified for Svc in LOCA Environ.Solenoid Will Be Replaced Before Start of Cycle 3 Operation
ML20076A904
Person / Time
Site: Millstone 
Issue date: 04/18/1979
From: Counsil W
NORTHEAST UTILITIES
To: Reid R
Office of Nuclear Reactor Regulation
References
TAC-46174, NUDOCS 7904250253
Download: ML20076A904 (2)


Text

4 n6ernumrrirrn,rnus 1

l i

b oNNEC M W m c L==:==

t April 18, 1979 m

Z Docket No. 50-336 Director of Nuclear Reactor Regulation Attn:

Mr. R. Reid, Chief

' Operating Reactors Branch #4 U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Reference:

(1)

B. H. Grier letter to W. G. Counsil dated February 8,1979, forwarding I&E Bulletin 79-01.

g Gentlemen:

O Millstone Nuclear Power Station, Unit No. 2 I&E Bulletin 79-01 Environmental Qualification of Class lE Equipment In accordance with the reporting requirements of Reference (1), Northeast Nuclear Energy Company (NNECO) is advising the NRC Staff that it has been determined that one solenoid installed on a safety-related valve in the Millstone Unit No. 2 con-tainment has not been qualified for service in the LOCA environment.

The original design function of this valve, (2-CH-517), the auxiliary spray valve, is to cool the pressurizer when the pressure of the reactor coolant system is below that required to operate the reactor coolant pumps. This feature is described in FSAR Section 9.2.3.3.

Since that time, a flow path utilizing this valve was established for the hot leg injection method of precluding postulated boron precipi-tation concerns following a LOCA. The fact that this valve is now being used for an additional application, beyond the original design intent, supports NNECO's O

V mcir. icnjhat this lack of qualification is a unique situation.

1 The solenoid installed on 2-CH-517, Model Number 8302C27RF, Serial Number 22516A, will be replaced with an environmentally qualified solenoid prior to the start of Cycle 3 operation.

1 Although not reportable by the requirements of Reference (1), four other solenoids installed on safety-related valves within the Millstone Unit No. 2 containment are noted.

These solenoids are fully qualified to perform their design function in a r

LOCA environment, unless subjected to a coincident undervoltage condition, i.e.,90-100 V DC, applied to a wlenoid with a nominal voltage rating of 125 V DC.

The nominal DC vnitage level within the plant is 130 - 132 volts, and it is not a credible hypothesis to superimpose the requirements of a LOCA and a severe (less than 100 V) undervoltage condition on these solenoids.

Therefore, the current solenoids are acceptable.

However, it is the intention of NNECO to replace these four solenoids as soon as replacements are available, and during the current refueling outage, if possible.

1 f replacements cannot be procured on a schedule compatible with the start of Cycle 3 operation, replacement will be accomplished at the first suitable opportunity. A list of the specific valves, and the associated model number and serial number, is provided as follows:

2904250 2 5 3

_2_

Valve Solenoid Model No.

Serial No.

CH-518 HTX-8320A90V 77965A CH-519 HTX-8320A90V 77965A EB-91 HT-834445V 19820B EB-100 HT-834445V 19820B Because the information presented above is considered complete, the 14-day report requested in Reference (1) is not planned in this instance. Also, justification for continued operation is not applicable.

We trust the above information is responsive to your requests of Reference (1).

Very truly yours, NORTHEAST NUCLEAR ENERGY COMPANY

/

/N W. G. Counsil Vice President O

.