ND-19-1095, Emergency Action Levels and Basis

From kanterella
(Redirected from ML19284C122)
Jump to navigation Jump to search
Emergency Action Levels and Basis
ML19284C122
Person / Time
Site: Vogtle  
Issue date: 04/18/2019
From: Collings R
Southern Nuclear Operating Co
To:
Office of New Reactors
Shared Package
ML19284C114 List:
References
ND-19-1095
Download: ML19284C122 (133)


Text

Southern Nuclear Operating Company ND-19-1095 Enclosure Vogtle Electric Generating Plant (VEGP) Units 3 and 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

(This enclosure consists of 132 pages, excluding this cover page)

SNC Unit S NMP-EP-141-004 Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

VERSION 2.0 Special Considerations:

Applicable to Corporate, VEGP 3-4 PROCEDURE LEVEL OF USE CLASSIFICATION PER NMP-AP-003 CATEGORY SECTIONS Continuous None Reference None Information ALL Approval:

R. G. Collings 04/18/2019 Approved By Date EMERGENCY PREPAREDNESS Responsible Department ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 1 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 2 of 132 Printed 10/8/2019 at 13:20:31 VERSION

SUMMARY

Initial issuance of NMP as Version 1.0 PVR

2.0 DESCRIPTION

General changes to the document to correct grammar, spelling, spacing, percent signs, special characters, etc.

Added acronyms for Chemical and Volume Control System (CVS) and Component Cooling Water System (CCS).

Added clarification on RA3 for Rad Monitor readings.

Corrected the noun name of the RCS Hot Leg Level Low-1 alarm on CA1.

Added the definition for VALID to the basis of HU2.

Added Safety Evaluation Report (SER, ADAMS ML17079A292) to the Reference section.

Made NMP-EP-141-004-F01, and NMP-EP-141-004-F02 applicable to Vogtle 3&4 ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 2 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 3 of 132 Printed 10/8/2019 at 13:20:31 TABLE OF CONTENTS SECTION PAGE 1.0 PURPOSE/SCOPE/APPLICABILITY 5

2.0 DEFINITIONS 8

3.0 RESPONSIBILITIES 14 4.0 INSTRUCTION 14

5.0 REFERENCES

132 6.0 COMMITMENTS 132 ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 3 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 4 of 132 Printed 10/8/2019 at 13:20:31 RG1 SS1 HG7 FG1 CG1 RG2 SS5 HS1 FS1 CS1 RS1 SA1 HS6 FA1 CA1 RS2 SA2 HS7 CA2 RA1 SA5 HA1 CA3 RA2 SA8 HA5 CA4 RA3 SU1 HA6 CA7 RU1 SU2 HA7 CU1 RU2 SU3 HU1 CU3 SU4 HU2 CU4 SU5 HU3 CU5 SU6 HU4 CU6 SU7 HU7 ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 4 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 5 of 132 1.0 PURPOSE/SCOPE/APPLICABILITY 1.1.

PURPOSE Note:

EAL radiation monitor setpoint calculations document SV0-GSEP-N0C-900000 is Approved Pending due to future potential design change updates as Vogtle 3&4 is being constructed.

The purpose of this instruction is to provide the Initiating Conditions (IC), Emergency Action Levels (EALs) and Basis for the Vogtle 3&4 EAL Scheme which is utilized in the classification of off-normal events into one of four emergency classification levels. This instruction is used in conjunction with NMP-EP-141-004-F01, Hot Initiating Conditions Evaluation Matrix and NMP-EP-141-004-F02, Cold Initiating Conditions Evaluation.

1.2.

APPLICABILITY

1. Operating Reactors Title 10, Code of Federal Regulations (CFR), Energy, contains the U.S. Nuclear Regulatory Commission (NRC) regulations that apply to nuclear power facilities. Several of these regulations govern various aspects of an emergency classification scheme.

The relevant sections for this document are:

10 CFR § 50.47(a)(1)(i) 10 CFR § 50.47(b)(4) 10 CFR § 50.54(q) 10 CFR § 50.72(a) 10 CFR § 50, Appendix E, IV.B, Assessment Actions 10 CFR § 50, Appendix E, IV.C, Activation of Emergency Organization These regulations are supplemented by regulatory guidance documents. Documents of particular relevance to NEI 07-01 include:

NUREG-0654/FEMA-REP-1, Criteria for Preparation and Evaluation of Radiological Emergency Response Plans and Preparedness in Support of Nuclear Power Plants, October 1980. [Refer to Appendix 1, Emergency Action Level Guidelines for Nuclear Power Plants]

NUREG-1022, Event Reporting Guidelines 10 CFR § 50.72 and § 50.73 Regulatory Guide 1.101, Emergency Response Planning and Preparedness for Nuclear Power Reactors This list is not all-inclusive. It is strongly recommended that scheme developers consult with licensing and regulatory compliance personnel to identify and understand all applicable requirements and guidance. Questions also may be directed to the NEI Emergency Preparedness staff.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 5 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 6 of 132

2. Independent Spent Fuel Storage Installation (ISFSI)

Selected guidance in NEI 07-01 is applicable to licensees electing to use their 10 CFR 50 emergency plan to fulfill the requirements of 10 CFR 72.32 for a stand-alone ISFSI.

The emergency classification levels applicable to an ISFSI are consistent with the requirements of 10 CFR § 50 and the guidance in NUREG 0654/FEMA-REP-1. The initiating conditions germane to a 10 CFR § 72.32 emergency plan (as described in NUREG-1567) are contained within the classification scheme for a 10 CFR § 50.47 emergency plan.

The analysis of potential onsite and offsite consequences of accidental releases associated with the operation of an ISFSI is contained in NUREG-1140, A Regulatory Analysis on Emergency Preparedness for Fuel Cycle and Other Radioactive Material Licensees. NUREG-1140 concluded that the postulated worst-case accident involving an ISFSI has insignificant consequences to public health and safety. This evaluation shows that the maximum offsite dose to a member of the public due to an accidental release of radioactive materials would not exceed 1 rem Effective Dose Equivalent.

3. NRC Order EA-12-051 The Fukushima Daiichi accident of March 11, 2011, was the result of a tsunami that exceeded the plants design basis and flooded the sites emergency electrical power supplies and distribution systems. This caused an extended loss of power that severely compromised the key safety functions of core cooling and containment integrity, ultimately leading to core damage in three reactors. Although the loss of power also impaired the spent fuel pool cooling function, sufficient water inventory was maintained in the pools to prevent fuel damage from the loss of cooling.

Following a review of the Fukushima Daiichi accident, the NRC concluded that several measures were necessary to ensure adequate protection of public health and safety under the provisions of the backfit rule, 10 CFR 50.109(a)(4)(ii). One such measure was that each spent fuel pool be provided with reliable level instrumentation to significantly enhance the ability of key decision-makers to effectively allocate resources following a beyond design basis event. To this end, the NRC issued Order EA-12-051, Issuance of Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation, on March 12, 2012, to all U.S. nuclear plants with an operating license, construction permit, or combined construction and operating license.

NRC Order EA-12-051 states, in part, All licensees shall have a reliable indication of the water level in associated spent fuel storage pools capable of supporting identification of the following pool water level conditions by trained personnel: (1) level that is adequate to support operation of the normal fuel pool cooling system, (2) level that is adequate to provide substantial radiation shielding for a person standing on the spent fuel pool operating deck, and (3) level where fuel remains covered and actions to implement make-up water addition should no longer be deferred. All licensees must therefore provide:

A primary and back-up level instrument that will monitor water level from the normal level to the top of the used fuel rack in the pool; A display in an area accessible following a severe event; Independent electrical power to each instrument channel and an alternate remote power connection capability.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 6 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 7 of 132 NEI 12-02, Industry Guidance for Compliance with NRC Order EA-12-051, To Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation, provides guidance for complying with NRC Order EA-12-051.

NEI 07-01, Revision 0, includes three EALs that reflect the availability of the enhanced spent fuel pool level instrumentation associated with NRC Order EA-12-051. These EALs are included within existing IC RA2, and new ICs RS2 and RG2. Associated EAL notes, bases and developer notes are also provided.

It is recommended that these EALs be implemented when the enhanced spent fuel pool level instrumentation is available for use.

The regulatory process that licensees follow to make changes to their emergency plan, including non-scheme changes to EALs, is 10 CFR 50.54(q). Licensees are responsible for evaluating a proposed change and determining whether or not it results in a reduction in the plans effectiveness. Based on this determination, the licensee will either make the change or submit it to the NRC for prior review and approval in accordance with 10 CFR 50.90.

4. Organization and Presentation of Information The schemes information is organized by Recognition Category in the following order.

R - Abnormal Radiation Levels / Radiological Effluent C - Cold Shutdown / Refueling System Malfunction F - Fission Product Barrier H - Hazards and Other Conditions Affecting Plant Safety S - System Malfunction

5. IC and EAL Mode Applicability The plant modes are described in the Vogtle Unit 3 and 4 Technical Specifications. The ICs and EALs for a given Recognition Category are applicable in the identified modes.

The modes are used throughout the Vogtle EALs with no modifications from NEI 07-01.

When a unit is defueled, the Initiating Conditions designated as Mode Condition ALL or Defueled are applicable.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 7 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 8 of 132 MODE APPLICABILITY MATRIX Mode Category R

C F

H S

1 - Power Operations X

X X

X 2 - Startup X

X X

X 3 - Hot Standby X

X X

X 4 - Safe Shutdown X

X X

X 5 - Cold Shutdown X

X X

6 - Refueling X

X X

D - Defueled X

X X

2.0 DEFINITIONS

1.

General Emergency - Events are in progress or have occurred which involve actual or IMMINENT substantial core degradation or melting with potential for loss of containment integrity or HOSTILE ACTION that results in an actual loss of physical control of the facility. Releases can be reasonably expected to exceed EPA Protective Action Guideline (PAG) exposure levels offsite for more than the immediate site area.

2.

Site Area Emergency - Events are in progress or have occurred which involve actual or likely major failures of plant functions needed for protection of the public or HOSTILE ACTION that results in intentional damage or malicious acts; 1) toward site personnel or equipment that could lead to the likely failure of or; 2) that prevent effective access to, equipment needed for the protection of the public. Any releases are not expected to result in exposure levels which exceed EPA PAG exposure levels beyond the site boundarySITE BOUNDARY.

3.

Alert - Events are in progress or have occurred which involve an actual or potential substantial degradation of the level of safety of the plant or a security event that involves probable life-threatening risk to site personnel or damage to site equipment because of HOSTILE ACTION. Any releases are expected to be limited to small fractions of the EPA PAG exposure levels.

4.

Notification of Unusual Event (NOUE) - Events are in progress or have occurred which indicate a potential degradation of the level of safety of the plant or indicate a security threat to facility protection has been initiated. No releases of radioactive material requiring offsite response or monitoring are expected unless further degradation of safety systems occurs.

The following are key terms necessary for overall understanding the NEI 07-01 emergency classification scheme.

5.

Emergency Action Level (EAL) - A pre-determined, site-specific, observable threshold for an Initiating Condition that, when met or exceeded, places the plant in a given emergency classification level.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 8 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 9 of 132

6.

Emergency Classification Level (ECL) - One of a set of names or titles established by the US Nuclear Regulatory Commission (NRC) for grouping off-normal events or conditions according to (1) potential or actual effects or consequences, and (2) resulting onsite and offsite response actions. The emergency classification levels, in descending order of severity, are:

General Emergency (GE)

Site Area Emergency (SAE)

Alert Notification of Unusual Event (NOUE)

7.

Fission Product Barrier Threshold - A pre-determined, site-specific, observable threshold indicating the loss or potential loss of a fission product barrier.

8.

Initiating Condition (IC) - An event or condition that aligns with the definition of one of the four emergency classification levels by virtue of the potential or actual effects or consequences.

Selected terms used in Initiating Condition and Emergency Action Level statements are set in all capital letters (e.g., ALL CAPS). These words are defined terms that have specific meanings as used in this document. The definitions of these terms are provided below.

9. CONTAINMENT CLOSURE - Technical Specification Section 3.6 contains the meaning of containment closure for Modes 5 and 6. Containment closure means that all potential escape paths are closed or capable of being closed. Since there are no requirements for containment leak tightness, compliance with Appendix J leakage criteria and test are not required.
10. DEFUELED (mode) - All reactor fuel removed from reactor pressure vessel (full core off load during refueling or extended outage).
11. EMERGENCY DIRECTOR (ED) - A senior VEGP3/4 employee with overall responsibility for coordinating emergency response actions of the station, and the ERO with the affected state(s) and county agencies.
12. EPA PAGs - Environment Protection Agency Protective Action Guidelines. The EPA PAGs are expressed in terms of dose commitment: 1 Rem TEDE or 5 Rem CDE Thyroid. Actual or projected offsite exposures in excess of the EPA PAGs requires VEGP3/4 to recommend protective actions for the general public to offsite planning agencies.
13. EXPLOSION - A rapid, violent, and catastrophic failure of a piece of equipment due to combustion, chemical reaction, or overpressurization. A release of steam (from high energy lines or components) or an electrical component failure (caused by short circuits, grounding, arcing, etc.) should not automatically be considered an EXPLOSION. Such events require a post-event inspection to determine if the attributes of an EXPLOSION are present.
14. EXTINGUISH(ED) - Cessation of combustion and production of heat and emission of light, as determined by the Incident Commander.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 9 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 10 of 132

15. FAULTED - The term applied to a steam generator that has a steam leak on the secondary side of sufficient size to cause an uncontrolled drop in steam generator pressure or the steam generator to become completely depressurized.
16. FIRE - Combustion characterized by heat and light. Observation of flame is preferred but is not required if large quantities of smoke and heat are observed. Sources of smoke such as slipping drive belts or overheated electrical equipment do not constitute FIRES.
17. FLOODING - A condition where water is entering a room or area faster than installed equipment is capable of removal, resulting in a rise of water level within the room or area.
18. HOSTAGE - A person(s) held as leverage against the station to ensure that demands will be met by the station.
19. HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).
20. HOSTILE FORCE - One or more individuals who are engaged in a determined assault, overtly or by stealth and deception, equipped with suitable weapons capable of killing, maiming, or causing destruction.
21. IMMINENT - The trajectory of events or conditions is such that an EAL will be met within a relatively short period of time regardless of mitigation or corrective actions.
22. IMPEDE(D) - Personnel access to a room or area is hindered to an extent that extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g., requiring use of protective equipment, such as SCBAs, that is not routinely employed).
23. INTRUSION - The act of entering without authorization. Discovery of a bomb in a specified area is indication of intrusion into that area by a HOSTILE FORCE.
24. NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN - Safety-related Safe Shutdown systems are defined in UFSAR Table 7.4-1, which include PMS, PXS, PCS, IDS, Containment Isolation Valves, and control rods. Safe Cooldown additionally requires RCS, RNS and associated support SSCs (eg. the applicable portions of CCS, SWS, ECS, EDS and RNS room cooling needed to support RNS) because the RCS is not capable of being cooled to MODE 5 using only safety systems. FWS/SGS are NOT required to support Safe Cooldown because PRHR is capable of cooling the plant to RNS cut-in conditions.
25. OWNER CONTROLLED AREA (OCA) - The area owned by the licensee and located within the confines of the Site BoundarySITE BOUNDARY.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 10 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 11 of 132

26. PLANT OPERATOR - Any member of the plant staff who, by virtue of training and experience, is qualified to assess the indications or reports for validity and to compare the same to the EAL Matrix in Attachment INMP-EP-141-004-F01 and NMP-EP-141-004-F02. The PLANT OPERATOR has the authority to declare the appropriate EAL and activate the Emergency Plan. A PLANT OPERATOR does not encompass plant personnel such as chemists, radiation protection technicians, security personnel, and others whose position require they report rather than assess abnormal conditions to the Main Control Room or Technical Support Center (TSC). The PLANT OPERATOR is the Duty Shift Manager or the Emergency Director responsible for managing the emergency response.
27. PROJECTILE - An object directed toward an NPP that could cause concern for its continued operability, reliability, or personnel safety.
28. PROTECTED AREA - An area, located within the Site Exclusion Area Boundary, encompassed by physical barriers and to which access is controlled per 10 CFR 73.55.

The SNC Power Block PROTECTED AREA and the ISFSI PROTECTED AREA are two PROTECTED AREAS located within the Site OWNER CONTOLLED AREA.

29. RCS INTACT - The RCS can act as an effective pressure boundary.
30. REDUCED INVENTORY - RCS level 3 feet below the reactor vessel flange (8% wide range pressurizer level).
31. REFUELING PATHWAY - The reactor refueling cavity, spent fuel pool, and fuel transfer canal comprise the refueling pathway.
32. RUPTURE(D) - The condition of a steam generator in which primary-to-secondary leakage is of sufficient magnitude to require Safeguards actuation.
33. SECURITY CONDITION - Any security event as listed in the approved security contingency plan that constitutes a threat/compromise to site security, threat/risk to site personnel, or a potential degradation to the level of safety of the plant. A security condition does not involve a HOSTILE ACTION.
34. SITE BOUNDARY - The boundary of a reactor site beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.
35. UNISOLABLE - An open or breached system line that cannot be isolated, remotely or locally.
36. UNPLANNED - A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.
37. VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the conditions existence, or the reports accuracy is removed.

Implicit in this definition is the need for timely assessment.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 11 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 12 of 132

38. VISIBLE DAMAGE - Damage to equipment or structure that is readily observable without measurements, testing, or analysis. The visual impact of the damage is sufficient to cause concern regarding the operability or reliability of the affected equipment or structure. Damage resulting from an equipment failure and limited to the failed component (i.e., the failure did not cause damage to a structure or any other equipment) is not visible damage. VISIBLE DAMAGE requires at least limited damage to a single SSC; the extent of damage or need to determine the loss of an entire train is not required. This eliminates the need to evaluate the extent of damage and determine the functionality of entire safety system, which would likely exceed 15 minutes.

ACRONYMS/ABBREVIATIONS

°F...................................................................................................... Degrees Fahrenheit

'................................................................................................................ Feet or Minutes

"........................................................................................................... Inches or Seconds

........................................................................................................................... Gamma

........................................................................................................................... Neutron

µCi/gm............................................................................................. micro Curie per gram AC....................................................................................................... Alternating Current ADS........................................................................... Automatic Depressurization System ALWR................................................................................ Advanced Light Water Reactor ATWS...................................................................... Anticipated Transient Without Scram CCS........................................................................... Component Cooling Water System CDE...................................................................................... Committed Dose Equivalent CFR...................................................................................... Code of Federal Regulations CTMT............................................................................................................ Containment CSFST...................................................................... Critical Safety Function Status Tree CVS....................................................................... Chemical and Volume Control System DAS.......................................................................................... Diverse Actuation System DBA................................................................................................Design Basis Accident DC............................................................................................................... Direct Current DCD......................................................................................... Design Control Document DDS........................................................................ Data Display and Processing System DG.................................................................................. Non-Class 1-E Diesel Generator EAL............................................................................................. Emergency Action Level ECCS........................................................................... Emergency Core Cooling System ECL.................................................................................. Emergency Classification Level ECS............................................................................................. Main AC Power System EDS................................................................................................ Non 1-E DC and UPS EOP.............................................................................. Emergency Operating Procedure EPA.............................................................................. Environmental Protection Agency FSAR.................................................................................... Final Safety Analysis Report IC......................................................................................................... Initiating Condition IDS....................................................................... Class 1-E DC and UPS Power System ISFSI............................................................ Independent Spent Fuel Storage Installation IRWST....................................................... In-containment Refueling Water Storage Tank Keff......................................................................... Effective Neutron Multiplication Factor ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 12 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 13 of 132 LCO................................................................................. Limiting Condition for Operation LOCA......................................................................................... Loss of Coolant Accident MCR................................................................................................... Main Control Room MSSV........................................................................................ Main Steam Safety Valve mR............................................................................................................. milli-Roentgen mRem, mRem, mRem...................................................... milli-Roentgen Equivalent Man NEI.............................................................................................. Nuclear Energy Institute NRC............................................................................... Nuclear Regulatory Commission NSSS................................................................................ Nuclear Steam Supply System NOUE............................................................................... (Notification Of) Unusual Event OBE..................................................................................... Operating Basis Earthquake OCA.............................................................................................. Owner Controlled Area ODCM............................................................................ Offsite Dose Calculation Manual ORO.................................................................................. Offsite Response Organization PAG....................................................................................... Protective Action Guideline PCS........................................................................ Passive Containment Cooling System PDSP.............................................................................. Primary Dedicated Safety Panel PMS.................................................................. Protection and Safety Monitoring System PORV.................................................................................. Power Operated Relief Valve PRA/PSA...................... Probabilistic Risk Assessment / Probabilistic Safety Assessment PRHR............................................................................. Passive Residual Heat Removal PSIG............................................................................... Pounds per Square Inch Gauge PXS.................................................................................... Passive Core Cooling System R....................................................................................................................... Roentgen RCS........................................................................................... Reactor Coolant System RCDT.................................................................................... Reactor Coolant Drain Tank Rem, rem, REM....................................................................... Roentgen Equivalent Man RNS................................................................................ Normal Residual Heat Removal RPV............................................................................................ Reactor Pressure Vessel RTS.................................................................................................. Reactor Trip System SFP..........................................................................................................Spent Fuel Pool SG.......................................................................................................... Steam Generator TEDE................................................................................ Total Effective Dose Equivalent TOAF.................................................................................................... Top of Active Fuel TSC........................................................................................... Technical Support Center UFSAR................................................................... Updated Final Safety Analysis Report VBS.................................................... Nuclear Island Non-radioactive Ventilation System WRS.............................................................................. Radioactive Waste Drain System ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 13 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 14 of 132 3.0 RESPONSIBILITIES 3.1 SHIFT MANAGER The Shift Manager is responsible for evaluating off normal conditions using the guidance of this Instruction to determine if an IC has been met. The Shift Manager is responsible for determining the highest level IC applicable for a particular event and promptly declaring the appropriate ECL. Upon declaration of an ECL the Shift Manager will assume the role of Emergency Director and is responsible for performing the duties of the Emergency Director as described in the SNC Standard Emergency Plan until relieved by another qualified Emergency Director.

3.2 TSC EMERGENCY DIRECTOR The Emergency Director is responsible for evaluating changes in event conditions using the guidance of this Instruction and upgrading the ECL as appropriate. The Emergency Director is responsible for performing the duties of the TSC Emergency Director as described in the SNC Standard Emergency Plan until relieved by another qualified Emergency Director.

4.0 INSTRUCTION 4.1 GENERAL CONSIDERATIONS For any emergency classification, the emergency director must consider all information having a bearing on the proper assessment of an initiating condition (IC). This includes the emergency action level (EAL), the associated operating mode applicability, notes and the informing basis information. In the Recognition Category F matrices, EALs are referred to as Fission Product Barrier Thresholds; the thresholds serve the same function as an EAL.

NRC regulations require the licensee to establish and maintain the capability to assess, classify, and declare an emergency condition within 15 minutes after the availability of indications to plant operators that an emergency action level has been exceeded; and to promptly declare the emergency condition as soon as possible following identification of the appropriate emergency classification level. The NRC provides guidance on implementing this requirement in NSIR/DPR-ISG-01, Interim Staff Guidance, Emergency Planning for Nuclear Power Plants.

All emergency classification assessments will be based on valid indications, reports or conditions. A valid indication, report, or condition, has been verified using appropriate means, leaving no doubt regarding the indicators operability, the conditions existence, or the reports accuracy. For example, validation could be an instrument channel check, response on related or redundant indicators, or direct observation by plant personnel.

Indication will be validated in a manner that supports timely emergency declaration.

For ICs and EALs that have a stipulated time duration, the emergency director will not wait until the applicable time has elapsed, but will declare the event as soon as it is determined that the condition has exceeded, or will likely exceed, the applicable time. If an ongoing radiological release is detected and the release start time is unknown, it will be assumed that the release duration specified in the IC/EAL has been exceeded, absent data to the contrary.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 14 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 15 of 132 A planned work activity resulting in an expected event or condition that meets or exceeds an EAL does not warrant an emergency declaration provided that 1) the activity proceeds as planned and 2) the plant remains within the limits imposed by the operating license. Such activities include planned work to test, manipulate, repair, maintain or modify a system or component. In such cases, the controls associated with the planning, preparation and execution of the work will ensure compliance with the operating license is maintained provided that the activity proceeds and concludes as expected. Events or conditions of this type may be subject to the reporting requirements of 10 § CFR 50.72.

Some EALs are assessed based on the results of analyses necessary to ascertain whether a specific EAL threshold has been exceeded. The EAL and/or the associated basis discussion will identify the necessary analysis. The 15-minute declaration period starts with the availability of the analysis results that show the threshold to be exceeded (i.e., this is the time that the EAL information is first available). The NRC expects licensees to establish the capability to initiate and complete EAL-related analyses within a reasonable period of time.

Although the EALs have been developed to address a full spectrum of possible events and conditions that may warrant emergency classification, a provision for classification based on operator/management experience and judgment is still necessary. The NEI 07-01 scheme provides the emergency director with the ability to classify events and conditions based upon judgment using EALs consistent with the emergency classification level (ECL) definitions (refer to Category H). The emergency director will determine if the effects or consequences of the event or condition reasonably meet or exceed a particular ECL definition. A similar provision is incorporated into the Fission Product Barrier Tables; judgment may be used to determine the status of a fission product barrier.

4.2 CLASSIFICATION METHODOLOGY To make an emergency classification, the user will compare an event or condition (i.e., the relevant plant indications and reports) to an EAL(s) and determine if the EAL has been met or exceeded. An EAL(s) evaluation must be consistent with the related Operating Mode Applicability and Notes. If an EAL has been met or exceeded, the IC is met and the associated ECL is declared in accordance with plant procedures.

When assessing an EAL that specifies a time duration for the off-normal condition, the clock for the EAL time duration runs concurrently with the emergency classification process clock. For a full discussion of this timing requirement, refer to NSIR/DPR-ISG-01.

4.3 CLASSIFICATION OF MULTIPLE EVENTS AND CONDITIONS In the event of multiple emergencies or conditions, the user will identify all met or exceeded EALs. The highest applicable ECL identified during this review is declared. For example:

If an Alert EAL and a Site Area Emergency EAL are met, a Site Area Emergency should be declared.

There is no additive effect from multiple EALs meeting the same ECL. For example:

If two Alert EALs are met, an Alert will be declared.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 15 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 16 of 132 Related guidance for classification of rapidly escalating events or conditions is provided in Regulatory Issue Summary (RIS) 2007-02, Clarification of NRC Guidance for Emergency Notifications During Quickly Changing Events.

4.4 CONSIDERATION OF MODE CHANGES DURING CLASSIFICATION The mode in effect at the time an event or condition occurred, and prior to any plant or operator response, determines whether an IC is applicable. If an event or condition occurs, and results in a mode change before the emergency is declared, the emergency classification level is still based on the mode that existed at the time that the event or condition was initiated (and not when it was declared). Once a different mode is reached, any new event or condition, not related to the original event or condition, requiring emergency classification should be evaluated against the ICs and EALs applicable to the operating mode at the time of the new event or condition.

4.5 CLASSIFICATION OF IMMINENT CONDITIONS Although EALs provide specific thresholds, the emergency director must remain alert to events or conditions that could lead to meeting or exceeding an EAL within a relatively short period of time (i.e., a change in the ECL is IMMINENT). If, in the judgment of the emergency director, meeting an EAL is IMMINENT, the emergency classification will be made as though the EAL has been met. While applicable to all emergency classification levels, this approach is particularly important at the higher emergency classification levels since it provides additional time for implementation of protective measures.

4.6 EMERGENCY CLASSIFICATION LEVEL UPGRADING AND DOWNGRADING SNC policy is that once an emergency classification is made, it cannot be downgraded to a lower classification. Termination criteria contained in procedure NMP-EP-145, Termination and Recovery shall be completed for an event to be terminated. At termination, on an event specific basis, the site will enter either normal operating conditions or a recovery condition with a recovery organization established for turnover from the ERO. Guidance concerning classification of rapidly escalating events or conditions is provided in RIS 2007-02.

4.7 CLASSIFICATION OF SHORT-LIVED EVENTS Event-based ICs and EALs define a variety of specific occurrences that have potential or actual safety significance. By their nature, some of these events may be short-lived and end before the emergency classification assessment can be completed. If an event occurs that meets or exceeds an EAL, the associated ECL must be declared regardless of its continued presence at the time of declaration. For example, an earthquake, or failure of the reactor protection system to automatically scram/trip the reactor followed by a successful manual scram/trip.

4.8 CLASSIFICATION OF TRANSIENT CONDITIONS Many of the ICs and EALs in this document employ time-based criteria that require IC/EAL conditions be present for a defined period of time before an emergency declaration is warranted. In cases where no time-based criterion is specified, some transient conditions may cause an EAL to be met for a brief period of time. The following guidance will be applied to the classification of these conditions.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 16 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 17 of 132 EAL momentarily met during expected plant response - When an EAL is briefly met during an expected (normal) plant response, an emergency declaration is not warranted provided that associated systems and components are operating as expected, and operator actions are performed in accordance with procedures.

EAL momentarily met but the condition is corrected prior to an emergency declaration - If an operator takes prompt manual action to address a condition, and the action is successful in correcting the condition prior to the emergency declaration, then the applicable EAL is not considered met and the associated emergency declaration is not required. This example presents an illustration:

An ATWS occurs and the auxiliary feedwater system fails to automatically start. Steam generator levels rapidly decrease and the plant enters an inadequate RCS heat removal condition (a potential loss of both the fuel clad and RCS barriers). If an operator manually starts the auxiliary feedwater system in accordance with an EOP step and clears the inadequate RCS heat removal condition prior to an emergency declaration, then the classification will be based on the ATWS only.

It is important to stress that the 15-minute emergency classification assessment period is not a grace period during which a classification may be delayed to allow the performance of a corrective action that would obviate the need to classify the event; emergency classification assessments must be deliberate and timely, with no undue delays. The provision discussed above addresses only those rapidly evolving situations where an operator is able to take a successful corrective action prior to the emergency director completing the review and steps necessary to make the emergency declaration.

This provision is included to ensure that any public protective actions resulting from the emergency classification are truly warranted by the plant conditions.

4.9 AFTER-THE-FACT DISCOVERY OF AN EMERGENCY EVENT OR CONDITION In some cases, an EAL may be met but the emergency classification was not made at the time of the event or condition. Personnel could discover that an event or condition existed that met an EAL, but no emergency was declared, and the event or condition no longer exists at the time of discovery. It may be the event or condition was not recognized at the time, or there was an error in the emergency classification process.

In these cases, no emergency declaration is warranted, but the guidance in NUREG-1022 is applicable. Specifically, the event will be reported to the NRC in accordance with 10 CFR

§ 50.72 within one hour of the discovery of the undeclared event or condition. The licensee will also notify appropriate state and local agencies in accordance with the agreed upon arrangements.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 17 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 18 of 132 4.10 ABNORMAL RAD LEVELS / RADIOLOGICAL EFFLUENT ICs/EALs GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT RG1 Release of gaseous radioactivity resulting in offsite dose greater than 1,000 mRem TEDE or 5,000 mRem thyroid CDE.

Op. Modes: All RS1 Release of gaseous radioactivity resulting in offsite dose greater than 100 mRem TEDE or 500 mRem thyroid CDE.

Op. Modes: All RA1 Release of gaseous radioactivity resulting in offsite dose greater than 10 mRem TEDE or 50 mRem thyroid CDE.

Op. Modes: All RU1 Release of gaseous or liquid radioactivity greater than 2 times the ODCM limits for 60 minutes or longer.

Op. Modes: All RG2 Spent fuel pool (containing irradiated fuel) level cannot be restored to at least the top of the fuel racks for 60 minutes or longer.

Op. Modes: All RS2 Spent fuel pool (containing irradiated fuel) level at the top of the fuel racks Op. Modes: All RA2 Significant lowering of water level above, or damage to, irradiated fuel.

Op. Modes: All RU2 UNPLANNED loss of water level above irradiated fuel.

Op. Modes: All RA3 Radiation levels that IMPEDE access to equipment necessary for normal plant operations, cooldown or shutdown.

Op. Modes: All ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 18 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 19 of 132 RG1 ECL: General Emergency Initiating Condition: Release of gaseous radioactivity resulting in offsite dose greater than 1,000 mRem TEDE or 5,000 mRem thyroid CDE.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

Note 2:

If an ongoing release is detected and the release start time is unknown, assume that the release duration has exceeded the specified time limit.

Note 3:

If the effluent flow past an effluent monitor is known to have stopped, indicating that the release path is isolated, the effluent monitor reading is no longer VALID for classification purposes.

Note 4:

The pre-calculated effluent monitor values presented in EALs RA1, RS1 and RG1 should be used for emergency classification assessments until the results from a dose assessment using actual meteorology are available.

(1)

Reading on any of the following effluent radiation monitors for 15 min. (Notes 1, 2, 3, 4)

TDS-RY001 - Turbine Island Vent 1.00E+03 µCi/cc VFS-RY104A - Plant Vent 3.90E+01 µCi/cc VFS-RY104B - Plant Vent 3.90E+01 µCi/cc (2)

Dose assessment using actual meteorology indicates doses > 1000 mRem TEDE or 5000 mRem thyroid CDE at or beyond the SITE BOUNDARY (Notes 3, 4)

(3)

Field survey results indicate EITHER of the following at or beyond the SITE BOUNDARY:

Closed window dose rates > 1000 mR/hr expected to continue for 60 min.

Analyses of field survey samples indicate thyroid CDE > 5000 mRem for 60 min. of inhalation.

(Notes 1, 2)

Basis:

SITE BOUNDARY - The boundary of a reactor site beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.

VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the conditions existence, or the reports accuracy is removed. Implicit in this definition is the need for timely assessment.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 19 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 20 of 132 This IC addresses a release of gaseous radioactivity that results in projected or actual offsite doses greater than or equal to the EPA Protective Action Guides (PAGs). It includes both monitored and un-monitored releases. Releases of this magnitude will require recommendation of protective actions for the public.

Radiological effluent EALs are also included to provide a basis for classifying events and conditions that cannot be readily or appropriately classified on the basis of plant conditions alone. The inclusion of both plant condition and radiological effluent EALs more fully addresses the spectrum of possible accident events and conditions.

The TEDE dose is set at the EPA PAG of 1,000 mRem while the 5000 mRem thyroid CDE was established in consideration of the 1:5 ratio of the EPA PAG for TEDE and thyroid CDE.

Classification based on effluent monitor readings assumes that a release path to the environment is established. If the effluent flow past an effluent monitor is known to have stopped due to actions to isolate the release path, then the effluent monitor reading is no longer VALID for classification purposes.

EAL (1)

The Plant Vent Gas radiation monitors, VFS-RY104A (mid range 1.0E-4 to 1.0E+2 Ci/cc) and VFS-RY104B (hi range 1.0E-1 to 1.0E+5 Ci/cc) measures the concentration of gaseous radioactive airborne contamination being released through the plant vent, which is the only design pathway for the release of radioactive materials to the atmosphere.

The Turbine Island Vent discharge radiation monitor (TDS-RY001) measures the concentration of radioactive gases in the steam and non-condensable gases that are discharged by the condenser vacuum pumps and the gland seal steam condenser. This measurement provides early indication of leakage between the primary and secondary sides of the steam generators.

The monitor provides an alarm in the Main Control Room if concentrations exceed a predetermined setpoint. Turbine Island Vent radiation monitor includes two G-M tubes with nominal ranges of 1.0E-6 to 1.0E+0 Ci/cc (normal range) and 1.0E-1 to 1.0E+5 Ci/cc (hi range).

EAL (2)

Dose assessment may be performed using computer based methods.

EAL (3) 91303-C Field Sampling and Surveys, provides guidance for emergency or post-accident radiological environmental monitoring.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 20 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 21 of 132 RG2 ECL: General Emergency Initiating Condition: Spent fuel pool (containing irradiated fuel) level cannot be restored to at least the top of the fuel racks for 60 minutes or longer Operating Mode Applicability: All Emergency Action Levels: (1)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Spent Fuel Pool level cannot be restored to at least Level 3 (0 ft. on SFS-LT019A/B/C) for > 60 min. (Note 1)

Basis:

The VEGP3/4 spent fuel storage facility is located within the seismic Category I Auxiliary Building fuel handling area.

The SFP level instrumentation is at an elevation of 229.5', which is 0.25' above the top of the spent fuel racks. It is capable of measuring the SFP level from the spent fuel racks up to the operating deck, which is at 255.25'. The instrument range is 0' to 25.75' as a result.

Level 3 is 0 ft. above the top of the fuel racks.

This IC addresses a significant loss of Spent Fuel Pool inventory control and makeup capability leading to a prolonged uncovery of spent fuel. This condition will lead to fuel damage and a radiological release to the environment.

It is recognized that this IC would likely not be met until well after another General Emergency IC was met; however, it is included to provide classification diversity.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 21 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 22 of 132 RS1 ECL: Site Area Emergency Initiating Condition: Release of gaseous radioactivity resulting in offsite dose greater than 100 mRem TEDE or 500 mRem thyroid CDE.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

Note 2:

If an ongoing release is detected and the release start time is unknown, assume that the release duration has exceeded the specified time limit.

Note 3:

If the effluent flow past an effluent monitor is known to have stopped, indicating that the release path is isolated, the effluent monitor reading is no longer VALID for classification purposes.

Note 4:

The pre-calculated effluent monitor values presented in EALs RA1, RS1 and RG1 should be used for emergency classification assessments until the results from a dose assessment using actual meteorology are available.

(1)

Reading on any of the following effluent radiation monitors for 15 min. (Notes 1, 2, 3, 4)

TDS-RY001 - Turbine Island Vent 1.00E+02 µCi/cc VFS-RY104A - Plant Vent 3.90E+00 µCi/cc VFS-RY104B - Plant Vent 3.90E+00 µCi/cc (2)

Dose assessment using actual meteorology indicates doses > 100 mRem TEDE or 500 mRem thyroid CDE at or beyond the SITE BOUNDARY (Notes 3, 4)

(3)

Field survey results indicate EITHER of the following at or beyond the SITE BOUNDARY:

Closed window dose rates > 100 mR/hr expected to continue for 60 min.

Analyses of field survey samples indicate thyroid CDE > 500 mRem for 60 min. of inhalation.

(Notes 1, 2)

Basis:

SITE BOUNDARY - The boundary of a reactor site beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.

VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 22 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 23 of 132 conditions existence, or the reports accuracy is removed. Implicit in this definition is the need for timely assessment.

This IC addresses a release of gaseous radioactivity that results in projected or actual offsite doses greater than or equal to 10% of the EPA Protective Action Guides (PAGs). It includes both monitored and un-monitored releases. Releases of this magnitude are associated with the failure of plant systems needed for the protection of the public.

Radiological effluent EALs are also included to provide a basis for classifying events and conditions that cannot be readily or appropriately classified on the basis of plant conditions alone. The inclusion of both plant condition and radiological effluent EALs more fully addresses the spectrum of possible accident events and conditions.

The TEDE dose is set at 10% of the EPA PAG of 1,000 mRem while the 500 mRem thyroid CDE was established in consideration of the 1:5 ratio of the EPA PAG for TEDE and thyroid CDE.

Classification based on effluent monitor readings assumes that a release path to the environment is established. If the effluent flow past an effluent monitor is known to have stopped due to actions to isolate the release path, then the effluent monitor reading is no longer VALID for classification purposes.

EAL (1)

The Plant Vent Gas radiation monitors, VFS-RY104A (mid range 1.0E-4 to 1.0E+2 Ci/cc) and VFS-RY104B (hi range 1.0E-1 to 1.0E+5 Ci/cc) measures the concentration of gaseous radioactive airborne contamination being released through the plant vent, which is the only design pathway for the release of radioactive materials to the atmosphere.

The Turbine Island Vent discharge radiation monitor (TDS-RY001) measures the concentration of radioactive gases in the steam and non-condensable gases that are discharged by the condenser vacuum pumps and the gland seal steam condenser. This measurement provides early indication of leakage between the primary and secondary sides of the steam generators.

The monitor provides an alarm in the Main Control Room if concentrations exceed a predetermined setpoint. Turbine Island Vent radiation monitor includes two G-M tubes with nominal ranges of 1.0E-6 to 1.0E+0 Ci/cc (normal range) and 1.0E-1 to 1.0E+5 Ci/cc (hi range).

EAL (2)

Dose assessment may be performed using computer based methods.

EAL (3) 91303-C Field Sampling and Surveys, provides guidance for emergency or post-accident radiological environmental monitoring.

Escalation of the ECL would be via IC RG1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 23 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 24 of 132 RS2 ECL: Site Area Emergency Initiating Condition: Spent fuel pool (containing irradiated fuel) level at the top of the fuel racks Operating Mode Applicability: All Emergency Action Levels: (1)

(1) Lowering of Spent Fuel Pool level to Level 3 (0 ft. on SFS-LT019A/B/C)

Basis:

The VEGP3/4 spent fuel storage facility is located within the seismic Category I Auxiliary Building fuel handling area.

The SFP level instrumentation is at an elevation of 229.5', which is 0.25' above the top of the spent fuel racks. It is capable of measuring the SFP level from the spent fuel racks up to the operating deck, which is at 255.25'. The instrument range is 0' to 25.75' as a result.

Level 3 is 0 ft. above the top of the fuel racks.

This IC addresses a significant loss of Spent Fuel Pool inventory control and makeup capability leading to IMMINENT fuel damage. This condition entails major failures of plant functions needed for protection of the public and thus warrant a Site Area Emergency declaration.

It is recognized that this IC would likely not be met until well after another Site Area Emergency IC was met; however, it is included to provide classification diversity.

Escalation of the emergency classification level would be via IC RG1 or RG2.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 24 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 25 of 132 RA1 ECL: Alert Initiating Condition: Release of gaseous radioactivity resulting in offsite dose greater than 10 mRem TEDE or 50 mRem thyroid CDE.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

Note 2:

If an ongoing release is detected and the release start time is unknown, assume that the release duration has exceeded the specified time limit.

Note 3:

If the effluent flow past an effluent monitor is known to have stopped, indicating that the release path is isolated, the effluent monitor reading is no longer VALID for classification purposes.

Note 4:

The pre-calculated effluent monitor values presented in EALs RA1, RS1 and RG1 should be used for emergency classification assessments until the results from a dose assessment using actual meteorology are available.

(1)

Reading on any of the following effluent radiation monitors for 15 min. (Notes 1, 2, 3, 4)

TDS-RY001 - Turbine Island Vent 1.00E+01 µCi/cc VFS-RY104A - Plant Vent 3.90E-01 µCi/cc VFS-RY104B - Plant Vent 3.90E-01 µCi/cc (2)

Dose assessment using actual meteorology indicates doses > 10 mRem TEDE or 50 mRem thyroid CDE at or beyond the SITE BOUNDARY (Notes 3, 4)

(3)

Field survey results indicate EITHER of the following at or beyond the SITE BOUNDARY:

Closed window dose rates > 10 mR/hr expected to continue for 60 min.

Analyses of field survey samples indicate thyroid CDE > 50 mRem for 60 min. of inhalation.

(Notes 1, 2)

Basis:

SITE BOUNDARY - The boundary of a reactor site beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.

VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 25 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 26 of 132 conditions existence, or the reports accuracy is removed. Implicit in this definition is the need for timely assessment.

This IC addresses a release of gaseous radioactivity that results in projected or actual offsite doses greater than or equal to 1% of the EPA Protective Action Guides (PAGs). It includes both monitored and un-monitored releases. Releases of this magnitude represent an actual or potential substantial degradation of the level of safety of the plant as indicated by a radiological release that significantly exceeds regulatory limits (e.g., a significant uncontrolled release).

Radiological effluent EALs are also included to provide a basis for classifying events and conditions that cannot be readily or appropriately classified on the basis of plant conditions alone. The inclusion of both plant condition and radiological effluent EALs more fully addresses the spectrum of possible accident events and conditions.

The TEDE dose is set at 1% of the EPA PAG of 1,000 mRem while the 50 mRem thyroid CDE was established in consideration of the 1:5 ratio of the EPA PAG for TEDE and thyroid CDE.

EAL (1)

The Plant Vent Gas radiation monitors, VFS-RY104A (mid range 1.0E-4 to 1.0E+2 Ci/cc), and VFS-RY104B (hi range 1.0E-1 to 1.0E+5 Ci/cc) measures the concentration of gaseous radioactive airborne contamination being released through the plant vent, which is the only design pathway for the release of radioactive materials to the atmosphere.

The Turbine Island Vent discharge radiation monitor (TDS-RY001) measures the concentration of radioactive gases in the steam and non-condensable gases that are discharged by the condenser vacuum pumps and the gland seal steam condenser. This measurement provides early indication of leakage between the primary and secondary sides of the steam generators.

The monitor provides an alarm in the Main Control Room if concentrations exceed a predetermined setpoint. Turbine Island Vent radiation monitor includes two G-M tubes with nominal ranges of 1.0E-6 to 1.0E+0 Ci/cc (normal range) and 1.0E-1 to 1.0E+5 Ci/cc (hi range).

Classification based on effluent monitor readings assumes that a release path to the environment is established. If the effluent flow past an effluent monitor is known to have stopped due to actions to isolate the release path, then the effluent monitor reading is no longer VALID for classification purposes.

EAL (2)

Dose assessment may be performed using computer based methods.

EAL (3) 91303-C Field Sampling and Surveys, provides guidance for emergency or post-accident radiological environmental monitoring.

Escalation of the ECL would be via IC RS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 26 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 27 of 132 RA2 ECL: Alert Initiating Condition: Significant lowering of water level above, or damage to, irradiated fuel.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3)

(1)

Uncovery of irradiated fuel in the REFUELING PATHWAY (2)

Damage to irradiated fuel resulting in a release of radioactivity as indicated by a HIGH RADIATIONhigh radiation alarm or elevated reading on any of the following radiation monitors:

  • VAS-RY001 Fuel Handling Area Exhaust
  • VFS-RY001 Containment Air Filtration Exhaust
  • RMS-RY012 Fuel Handling Area Monitor
  • RMS-RY020 Fuel Handling Area Monitor
  • Refueling Bridge Portable Monitor (Refueling Mode)

(3)

Lowering of Spent Fuel Pool level to Level 2 (10 ft. on SFS-LT019A/B/C)

Basis:

REFUELING PATHWAY-The reactor refueling cavity, Spent Fuel Pool and fuel transfer canal comprise the refueling pathway.

This IC addresses events that have caused imminent or actual damage to an irradiated fuel assembly, or a significant lowering of water level within the Spent Fuel Pool. These events present radiological safety challenges to plant personnel and are precursors to a release of radioactivity to the environment. As such, they represent an actual or potential substantial degradation of the level of safety of the plant.

EAL (1)

Allowing level to decrease in the REFUELING PATHWAY could result in spent fuel being uncovered, reducing spent fuel decay heat removal, and creating an extremely hazardous radiation environment. Technical Specification LCO 3.7.5 requires at least 23 ft of water above the Spent Fuel Pool storage racks. Technical Specification LCO 3.9.4 requires at least 23 ft of water above the reactor vessel flange in the refueling cavity during refueling operations. This maintains sufficient water level in the fuel transfer canal, refueling cavity, and Spent Fuel Pool to retain iodine fission product activity in the water in the event of a fuel handling accident.

In the unlikely event of an extended loss of normal Spent Fuel Pool cooling, the water level will drop. Low Spent Fuel Pool level alarms and decreasing level indication trend in the Main Control Room will indicate to the operator the need to initiate makeup water to the pool. These alarms and indications are provided from safety-related and non-safety-related level instrumentation in the Spent Fuel Pool.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 27 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 28 of 132 This EAL escalates from RU2 in that the loss of level, in the affected portion of the REFUELING PATHWAY, is of sufficient magnitude to have resulted in uncovery of irradiated fuel. Indications of irradiated fuel uncovery may include direct or indirect visual observation (e.g., reports from personnel or camera images), as well as significant changes in water and radiation levels, or other plant parameters. Computational aids may also be used (e.g., a boil-off curve).

Classification of an event using this EAL should be based on the totality of available indications, reports and observations.

While an area radiation monitor could detect an increase in a dose rate due to a lowering of water level in some portion of the REFUELING PATHWAY, the reading may not be a reliable indication of whether or not the fuel is actually uncovered. To the degree possible, readings should be considered in combination with other available indications of inventory loss.

A drop in water level above irradiated fuel within the reactor vessel may be classified in accordance Recognition Category C during the Cold Shutdown and Refueling modes.

EAL (2)

When considering escalation, information may come from:

Radiation monitor readings Sampling and surveys Dose projections/calculations Reports from the scene regarding the extent of damage (e.g., refueling crew, health physics specialists)

Radiation monitors listed in this EAL are:

VAS-RY001 Fuel Handling Area Exhaust: The fuel handling area exhaust radiation monitor measures the concentration of radioactive materials in the exhaust air from the fuel handling area.

VFS-RY001 Containment Air Filtration Exhaust: The containment air filtration exhaust radiation monitor measures the concentration of radioactive materials in the containment purge exhaust air.

RMS-RY012 Fuel Handling Area Monitor RMS-RY020 Fuel Handling Area Monitor Refueling Bridge Portable Monitor (installed only in Refueling Mode)

This EAL addresses a release of radioactive material caused by mechanical damage to irradiated fuel. Damaging events may include the dropping, bumping or binding of an assembly, or dropping a heavy load onto an assembly. A rise in readings on radiation monitors should be considered in conjunction with in-plant reports or observations of a potential fuel damaging event (e.g., a fuel handling accident).

EAL (3)

The VEGP3/4 spent fuel storage facility is located within the seismic Category I Auxiliary Building fuel handling area.

The SFP level instrumentation is at an elevation of 229.5', which is 0.25' above the top of the spent fuel racks. It is capable of measuring the SFP level from the spent fuel racks up to the operating deck, which is at 255.25'. The instrument range is 0' to 25.75' as a result.

Level 2 is 10 ft. above the top of the fuel racks.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 28 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 29 of 132 Spent fuel pool water level at this value is within the lower end of the level range necessary to prevent significant dose consequences from direct gamma radiation to personnel performing operations in the vicinity of the Spent Fuel Pool. This condition reflects a significant loss of Spent Fuel Pool water inventory and thus it is also a precursor to a loss of the ability to adequately cool the irradiated fuel assembles stored in the pool.

Escalation of the emergency would be based on -Recognition Category R-ICs.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 29 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 30 of 132 RA3 ECL: Alert Initiating Condition: Radiation levels that IMPEDE access to equipment necessary for normal plant operations, cooldown or shutdown.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2)

Note 5:

If the equipment in the listed room or area was already inoperable or out-of-service before the event occurred, then no emergency classification is warranted.

(1)

Dose rate > 15 mR/hr in EITHER of the following areas:

Main Control Room (RMS-RY010 reads out in mrad/hr)

Central Alarm Station (by survey)

(2) An UNPLANNED event results in radiation levels that prohibit or IMPEDE access to any Table R-1 area/room (Note 5)

Table R-1 Safe Operation & Shutdown Areas/Rooms Building Room Number Room/Area Name Applicable Mode Auxiliary 12152 Primary Sample Room 3

12252 Rad Chem Lab 3

12321 Non-1E Equipment

/ Penetration Room 4

12305 Division D I&C Penetration Room 4

12304 Division B I&C Penetration Room 4

12561 CCS Valve Room 4

Annex 40503 Lower South Air Handling Equipment 4

Containment 11209 CVS Room 4

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 30 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 31 of 132 Basis:

IMPEDE(D) - Personnel access to a room or area is hindered to an extent that extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g., requiring use of protective equipment, such as SCBAs, that is not routinely employed).

UNPLANNED-. A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

This IC addresses elevated radiation levels in certain plant rooms/areas sufficient to preclude or IMPEDE personnel from performing actions necessary to maintain normal plant operation, or to perform a normal plant cooldown and shutdown. As such, it represents an actual or potential substantial degradation of the level of safety of the plant. The Emergency Director should consider the cause of the increased radiation levels and determine if another IC may be applicable.

EAL (1)

Note: Main Control Room Rad Monitor RMS-RY010 reads out in mrad/hr. For the purpose of determining EAL classification mrad/hr and mR/hr should be considered equivalent.

Main Control Room Rad Monitor RMS-RY010 reads out in mrad/hr. For the purpose of determining EAL classification mrad/hr and mR/hr should be considered equivalent.

RMS-RY010 (0.1 - 10,000 mrad/hr) is the permanently installed Main Control Room area radiation monitor and, along with local radiation surveys, may be used to assess this EAL threshold. The Central Alarm Station (CAS) does not have a permanently installed area radiation monitor and therefore local survey must be performed to assess this criteria.

This IC addresses elevated radiation levels in certain plant rooms/areas sufficient to preclude or IMPEDE personnel from performing actions necessary to maintain normal plant operation, or to perform a normal plant cooldown and shutdown. As such, it represents an actual or potential substantial degradation of the level of safety of the plant. The Emergency Director should consider the cause of the increased radiation levels and determine if another IC may be applicable.

EAL (2)

The Table R-1 safe operation and shutdown areas/rooms (with entry-related mode applicability) are those plant areas that contain equipment which require a manual/local action as specified in general operating procedures (and procedures referenced by them) used for normal plant operation, cooldown and shutdown. The list specifies the plant operating modes during which entry would be required for each area and thus specifying when a loss of access or IMPEDED access is applicable to this EAL.

Plant areas where actions of a contingent or emergency nature might be needed to be performed. (e.g., an action to address an off-normal or emergency condition such as emergency repairs, corrective measures or emergency operations) were not considered for inclusion.

Additionally, areas for which entry is required solely to perform actions of an administrative or record keeping nature (e.g., normal rounds or routine inspections) were not considered for inclusion. Refer to Attachment 3 "Safe Operation & Shutdown Areas/Rooms Tables R-1 & H-1 Bases."

If the equipment in the listed room or area was already inoperable, or out-of-service, before the ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 31 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 32 of 132 event occurred, then no emergency should be declared since the event will have no adverse impact beyond that already allowed by Technical Specifications at the time of the event.

For this EAL, an Alert declaration is warranted if entry into the affected room/area is, or may be, procedurally required during the plant operating mode in effect at the time of the elevated radiation levels. The emergency classification is not contingent upon whether entry is actually necessary at the time of the increased radiation levels. Access should be considered as IMPEDED if extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g., installing temporary shielding, requiring use of non-routine protective equipment, requesting an extension in dose limits beyond normal administrative limits).

An emergency declaration is not warranted if any of the following conditions apply:

The plant is in an operating mode different than the mode specified for the affected room/area (i.e., entry is not required during the operating mode in effect at the time of the elevated radiation levels). For example, the plant is in Mode 1 when the radiation increase occurs, and the procedures used for normal operation, cooldown and shutdown do not require entry into the affected room until Mode 4.

The increased radiation levels are a result of a planned activity that includes compensatory measures which address the temporary inaccessibility of a room or area (e.g., radiography, spent filter or resin transfer, etc.).

The action for which room/area entry is required is of an administrative or record keeping nature (e.g., normal rounds or routine inspections).

The access control measures are of a conservative or precautionary nature, and would not actually prevent or IMPEDE a required action.

If the equipment in the listed room or area was already inoperable, or out-of-service, before the event occurred, then no emergency should be declared since the event will have no adverse impact beyond that already allowed by Technical Specifications at the time of the event.

Escalation of the ECL would be via Recognition Category R, C or F ICs.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 32 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 33 of 132 RU1 ECL: Notification of Unusual Event Initiating Condition: Release of gaseous or liquid radioactivity greater than 2 times the ODCM limits for 60 minutes or longer.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

Note 2:

If an ongoing release is detected and the release start time is unknown, assume that the release duration has exceeded the specified time limit.

Note 3:

If the effluent flow past an effluent monitor is known to have stopped, indicating that the release path is isolated, the effluent monitor reading is no longer VALID for classification purposes.

(1)

Reading on any of the following effluent radiation monitors for 60 min. (Notes 1, 2, 3)

TDS-RY001 - Turbine Island Vent 2 X Hi-Rad alarm VFS-RY103 - Plant Vent 2 X Hi-Rad alarm WLS-RY229 - Liquid Radwaste 2 X Hi-Rad alarm WWS-RY021 - Waste Water 2 X Hi-Rad alarm (2)

Sample analysis for a gaseous or liquid release indicates a concentration or release rate >

2 x ODCM limits for 60 min. (Notes 1, 2)

Basis:

VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the conditions existence, or the reports accuracy is removed. Implicit in this definition is the need for timely assessment.

This IC addresses a potential decrease in the level of safety of the plant as indicated by a low-level radiological release that exceeds regulatory commitments for an extended period of time (e.g., an uncontrolled release). It includes any gaseous or liquid radiological release, monitored or un-monitored, including those for which a radioactivity discharge permit is normally prepared.

Nuclear power plants incorporate design features intended to control the release of radioactive effluents to the environment. Further, there are administrative controls established to prevent unintentional releases, and to control and monitor intentional releases. The occurrence of an extended, uncontrolled radioactive release to the environment is indicative of degradation in these features and/or controls.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 33 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 34 of 132 Radiological effluent EALs are also included to provide a basis for classifying events and conditions that cannot be readily or appropriately classified on the basis of plant conditions alone. The inclusion of both plant condition and radiological effluent EALs more fully addresses the spectrum of possible accident events and conditions.

Classification based on effluent monitor readings assumes that a release path to the environment is established. If the effluent flow past an effluent monitor is known to have stopped due to actions to isolate the release path, then the effluent monitor reading is no longer VALID for classification purposes.

Releases should not be prorated or averaged. For example, a release exceeding 4 times release limits for 30 minutes does not meet the EAL.

This EAL addresses normally occurring continuous as well as planned batch radioactivity releases from monitored gaseous or liquid effluent pathways.

EAL (1)

Gaseous Releases The Plant Vent Gas radiation monitors, VFS-RY103 (normal range 1.0E-7 to 1.0E-2 Ci/cc),

VFS-RY104A (mid range 1.0E-4 to 1.0E+2 Ci/cc) and VFS-RY104B (hi range 1.0E-1 to 1.0E+5 Ci/cc) measures the concentration of gaseous radioactive airborne contamination being released through the plant vent, which is the only design pathway for the release of radioactive materials to the atmosphere.

The Turbine Island Vent discharge radiation monitor (TDS-RY001) measures the concentration of radioactive gases in the steam and non-condensable gases that are discharged by the condenser vacuum pumps and the gland seal steam condenser. This measurement provides early indication of leakage between the primary and secondary sides of the steam generators.

The monitor provides an alarm in the Main Control Room if concentrations exceed a predetermined setpoint. Turbine Island Vent radiation monitor includes two G-M tubes with nominal ranges of 1.0E-6 to 1.0E+0 Ci/cc (normal range) and 1.0E-1 to 1.0E+5 Ci/cc (hi range).

Liquid Releases The Liquid Radwaste Discharge radiation monitor (WLS-RY229: 1.0E-6 to 1.0E-1 Ci/cc) measures the concentration of radioactive materials in liquids released to the environment. The liquid releases are made in batches that are mixed thoroughly and sampled. The samples are analyzed on site before discharge to determine that the discharge is within allowable concentration limits and within allowable totals. The Liquid Radwaste Discharge radiation monitor is an inline monitor that provides signals to isolate the discharge of liquid radwaste, stop the Liquid Radwaste System discharge pumps and alarms in the Main Control Room if the concentrations exceed a predetermined setpoint.

The Waste Water Discharge radiation monitor (WWS-RY021: 1.0E-7 to 1.0E-2 Ci/cc) measures the concentration of radioactive materials in the discharge from the Waste Water System. The Waste Water Discharge radiation monitor provides data for reports of liquid releases of radioactive materials. The Waste Water Discharge radiation monitor is an inline monitor. Upon reaching the high radiation setpoint the turbine building sump pumps stop and an alarm is initiated in the Main Control Room. Following an alarm, the operator can manually realign the discharge to the Liquid Radwaste System for processing.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 34 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 35 of 132 EAL (2)

This EAL addresses uncontrolled gaseous or liquid releases that are detected by sample analyses or environmental surveys, particularly on unmonitored pathways (e.g., spills of radioactive liquids into storm drains, heat exchanger leakage in river water systems, etc.).

Escalation of the ECL would be via IC RA1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 35 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 36 of 132 RU2 ECL: Notification of Unusual Event Initiating Condition: UNPLANNED loss of water level above irradiated fuel.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

UNPLANNED water level drop in the REFUELING PATHWAY as indicated by any of the following:

Low-2 SFP Lvl BS Trip Alarm (SFS-LT019A/B/C)

Level indication trend Visual observation AND UNPLANNED rise in area radiation levels as indicated by any of the following radiation monitors:

RMS-RY012 Fuel Handling Area Monitor RMS-RY020 Fuel Handling Area Monitor Refueling Bridge Portable Monitor (Refueling Mode)

Basis:

UNPLANNED-A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

REFUELING PATHWAY - The reactor refueling cavity, Spent Fuel Pool and fuel transfer canal comprise the refueling pathway.

Allowing level to decrease in the REFUELING PATHWAY could result in spent fuel being uncovered, reducing spent fuel decay heat removal, and creating an extremely hazardous radiation environment. Technical Specification LCO 3.7.5 requires at least 23 ft of water above the Spent Fuel Pool storage racks. Technical Specification LCO 3.9.4 requires at least 23 ft of water above the reactor vessel flange in the refueling cavity during refueling operations. This maintains sufficient water level in the fuel transfer canal, refueling cavity, and Spent Fuel Pool to retain iodine fission product activity in the water in the event of a fuel handling accident.

In the unlikely event of an extended loss of normal Spent Fuel Pool cooling, the water level will drop. Low Spent Fuel Pool level alarms and decreasing level indication trend in the Main Control Room will indicate to the operator the need to initiate makeup water to the pool. These alarms and indications are provided from safety-related and non-safety-related level instrumentation in the Spent Fuel Pool.

The SFP level instrumentation (SFS-LT019A/B/C) is at an elevation of 229.5', which is 0.25' above the top of the spent fuel racks. It is capable of measuring the SFP level from the spent fuel racks up to the operating deck, which is at 255.25'. The instrument range is 0' to 25.75' as a ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 36 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 37 of 132 result. The Low 2 Bi-Stable alarm indicates the possibility that a pipe break or leak exists in the system and that water is being lost through that break. The Low 2 Bi-Stable alarm setpoint sets the alarm at an indicated water level of 23.5' above top of the racks.

Radiation monitors that may indicate a loss of shielding above irradiated fuel include:

RMS-RY012 Fuel Handling Area Monitor RMS-RY020 Fuel Handling Area Monitor Refueling Bridge Portable Monitor (installed only in Refueling Mode)

This IC addresses a decrease in water level above irradiated fuel sufficient to cause elevated radiation levels. This condition could be a precursor to a more serious event and is also indicative of a minor loss in the ability to control radiation levels within the plant. It is therefore a potential degradation in the level of safety of the plant.

A water level decrease will be primarily determined by indications from available level instrumentation. Other sources of level indications may include reports from plant personnel (e.g., from a refueling crew) or video camera observations (if available). A significant drop in the water level may also cause an increase in the radiation levels of adjacent areas that can be detected by monitors in those locations.

The effects of planned evolutions should be considered. For example, a refueling bridge area radiation monitor reading may increase due to planned evolutions such as lifting of the reactor vessel head or movement of a fuel assembly. Note that this EAL is applicable only in cases where the elevated reading is due to an UNPLANNED loss of water level.

A drop in water level above irradiated fuel within the reactor vessel may be classified in accordance Recognition Category C during the Cold Shutdown and Refueling modes.

Escalation of the ECL would be via IC RA2.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 37 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 38 of 132 4.11 COLD SHUTDOWN / REFUELING SYSTEM MALFUNCTION ICs/EALs GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT CG1 Loss of reactor vessel/RCS inventory affecting fuel clad integrity with containment challenged.

Op. Modes: Cold Shutdown, Refueling CS1 Loss of reactor vessel/RCS inventory affecting core decay heat removal capability.

Op. Modes: Cold Shutdown, Refueling CA1 Loss of reactor vessel/RCS inventory.

Op. Modes: Cold Shutdown, Refueling CU1 Inability to restore and maintain required RCS inventory level.

Op. Modes: Cold Shutdown, Refueling CA2 Loss of all offsite and all onsite AC power to bussesbuses ECS-ES-1 and 2.

Op. Modes: Cold Shutdown, Refueling, Defueled CA3 Inability to maintain the plant in cold shutdown.

Op. Modes: Cold Shutdown, Refueling CU3 UNPLANNED increase in RCS Temperature.

Op. Modes: Cold Shutdown, Refueling CA4 Loss of all required Class 1E DC power or Class 1E UPS bus power for 15 minutes or longer.

Op. Modes: Cold Shutdown, Refueling, Defueled CU4 Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 30 minutes or longer.

Op. Modes: Cold Shutdown, Refueling, Defueled CU5 Loss of all onsite or offsite communications capabilities.

Op. Modes: Cold Shutdown, Refueling, Defueled CU6 UNPLANNED full loss of monitoring and control functions for 15 minutes or longer.

Op. Modes: Cold Shutdown, Refueling ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 38 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 39 of 132 GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT CA7 Hazardous event affecting a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode.

Op. Modes: Cold Shutdown, Refueling, Defueled ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 39 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 40 of 132 CG1 ECL: General Emergency Initiating Condition: Loss of reactor vessel/RCS inventory affecting fuel clad integrity with containment challenged.

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

Note 6:

If CONTAINMENT CLOSURE is re-established prior to exceeding the 30-minute time limit, declaration of a General Emergency is not required.

(1)

Reactor vessel/RCS level cannot be monitored for 30 min. (Note 1)

AND Core uncovery is indicated by EITHER of the following:

CTMT High Range Radiation (PXS-RY160/161/162/163) reading 100 rad/hr (High-2 alarm)

Erratic SR Excore Detector indication (RXS-NE001A/B/C/D)

AND Any of the following indications of containment challenge:

CONTAINMENT CLOSURE not established (Note 6)

CTMT H2 Concentration (VLS-AE001/002/003) > 4%

UNPLANNED increase in Containment pressure that can breach CONTAINMENT CLOSURE Basis:

CONTAINMENT CLOSURE -Technical Specification Section 3.6 contains the meaning of containment closure for Modes 5 and 6. Containment closure means that all potential escape paths are closed or capable of being closed. Since there are no requirements for containment leak tightness, compliance with Appendix J leakage criteria and test are not required.

UNPLANNED - A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

EAL (1)

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 40 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 41 of 132 The type and range of RCS/reactor vessel level instrumentation may vary during an outage as the plant moves through various operating modes and refueling evolutions, particularly for an AP1000. As appropriate to the plant design, alternate means of determining RCS/reactor vessel level are installed to assure that the ability to monitor level within the range required by operating procedures will not be interrupted. For the AP1000, the instrumentation range necessary to support implementation of operating procedures in the Cold Shutdown and Refueling modes may be different (e.g., narrower) than that required during modes higher than Cold Shutdown. The basis for this IC and associated example EALs is reactor vessel/RCS level below the top of active fuel for greater than 30 min. However, the lowest observable level on AP1000 RCS level instrumentation is the lowest observable level on the RCS Hot Leg Level Instrument. Therefore, this EAL addresses alternative indication of core uncover once reactor vessel level drops below the bottom of the Hot Leg such as erratic SR Excore Detector indications.

The Containment High Range Radiation monitors, PXS-RY160, 161, 162, and 163 have a range of 1.0E0 to 1.0E+7 rad/hr. The containment radiation High-2 alarm setpoint is 100 rad/hr. The alarm setpoint is sufficiently high to be indicative of a significant loss of shielding above the core indicating likely core uncovery.

Three indications are associated with a challenge to Containment:

CONTAINMENT CLOSURE is not established.

In the early stages of a core uncovery event, it is unlikely that hydrogen buildup due to a core uncovery could result in an explosive mixture of dissolved gases in Containment.

However, Containment monitoring and/or sampling should be performed to verify this assumption and a General Emergency declared if it is determined that an explosive mixture exists. A combustible mixture can be formed when hydrogen gas concentration in the Containment atmosphere is greater than 4% by volume.

An UNPLANNED pressurization that can breach the CONTAINMENT CLOSURE signifies a challenge to the containment pressure retaining capability which is dependent on the status of the containment. If containment integrity is established for full power operation, a breach could occur if the design Containment pressure is exceeded (59 psig). For this condition, a small UNPLANNED pressure rise above atmospheric pressure does not challenge containment. If in refueling operations, however, a breach could occur if the UNPLANNED pressure rise exceeded the capability of a temporary containment seal. This would occur at a much lower pressure than the containment design pressure. Use of the verb...can breach... instead of breaches provides the Emergency Director with the latitude to assess the magnitude and rate of the Containment pressure rise with respect to the barrier status (for the existing operating mode) and determine that the containment challenge exists due to elevated pressure either before or at the time that the actual breach of the barrier occurs.

This IC/EAL addresses the inability to restore and maintain reactor vessel level above the top of active fuel with containment challenged. This condition represents actual or IMMINENT substantial core degradation or melting with potential for loss of containment integrity. Releases can be reasonably expected to exceed EPA PAG exposure levels offsite for more than the immediate site area.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 41 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 42 of 132 Following an extended loss of core decay heat removal and inventory makeup, decay heat will cause reactor coolant boiling and a further reduction in reactor vessel/RPV level. If RCS/reactor vessel level cannot be restored, fuel damage is probable.

With CONTAINMENT CLOSURE not established, there is a high potential for a direct and unmonitored release of radioactivity to the environment. If CONTAINMENT CLOSURE is re-established prior to exceeding the 30-minute time limit, then declaration of a General Emergency is not required.

The existence of an explosive mixture means, at a minimum, that the containment atmospheric hydrogen concentration is sufficient to support a hydrogen burn (i.e., at the lower deflagration limit). A hydrogen burn will raise containment pressure and could result in collateral equipment damage leading to a loss of containment integrity. It therefore represents a challenge to Containment integrity.

In the early stages of a core uncovery event, it is unlikely that hydrogen buildup due to a core uncovery could result in an explosive gas mixture in containment. If all installed hydrogen gas monitors are out-of-service during an event leading to fuel cladding damage, it may not be possible to obtain a containment hydrogen gas concentration reading as ambient conditions within the containment will preclude personnel access. During periods when installed containment hydrogen gas monitors are out-of-service, operators may use the other indications to assess whether or not containment is challenged.

An UNPLANNED increase in containment pressure may be an indication of energy addition to the containment (RCS heatup or boiling) under conditions when the containment barrier has limited pressure retention capability challenging CONTAINMENT CLOSURE.

The 30-minute criterion is tied to a readily recognizable event start time (i.e., the total loss of ability to monitor level) and allows sufficient time to monitor, assess and correlate reactor and plant conditions to determine if core uncovery has actually occurred (i.e., to account for various accident progression and instrumentation uncertainties). The passive cooling systems should continue to function and provide a sufficient volume of water for cooling. Therefore, the 30-minute duration allows sufficient time for performance of actions to terminate leakage, recover inventory control/makeup equipment, and/or restore level monitoring.

The inability to monitor reactor vessel/ level may be caused by instrumentation and/or power failures or water level dropping below the range of available instrumentation. If water level cannot be monitored, operators may determine that core uncovery has occurred by observing the alternative indications specified.

These EALs address concerns raised by Generic Letter 88-17, Loss of Decay Heat Removal; SECY 91-283, Evaluation of Shutdown and Low Power Risk Issues; NUREG-1449, Shutdown and Low-Power Operation at Commercial Nuclear Power Plants in the United States; and NUMARC 91-06, Guidelines for Industry Actions to Assess Shutdown Management.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 42 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 43 of 132 CS1 ECL: Site Area Emergency Initiating Condition: Loss of reactor vessel/RCS inventory affecting core decay heat removal capability.

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1 or 2 or 3)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

CONTAINMENT CLOSURE not established.

AND RCS Hot Leg Level Low-4 (9.7%) on RCS-LT160 A or B (2)

CONTAINMENT CLOSURE established.

AND RCS Hot Leg Level < 0.5% on RCS-LT160 A or B (3)

Reactor vessel/RCS level cannot be monitored for 60 min. (Note 1)

AND Core uncovery is indicated by EITHER of the following:

CTMT High Range Radiation (PXS-RY160/161/162/163) reading 100 rad/hr (High-2 alarm)

Erratic SR Excore Detector indication (RXS-NE001A/B/C/D)

Basis:

CONTAINMENT CLOSURE - Containment closure means that all potential escape paths are closed or capable of being closed. Since there is no requirement for containment leak tightness, compliance with the Appendix J leakage criteria and tests are not required.

EAL (1)

This IC/EAL addresses a significant and prolonged loss of reactor vessel/ inventory control and makeup capability leading to core uncovery and IMMINENT fuel damage. The lost inventory may be due to a RCS component failure, a loss of configuration control, or prolonged boiling of reactor coolant. These conditions include major failures of plant functions needed for protection ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 43 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 44 of 132 of the public and thus warrant a Site Area Emergency declaration.

Following an extended loss of core decay heat removal and inventory makeup, decay heat will cause reactor coolant boiling and a further reduction in reactor vessel/RPV level. If RCS/reactor vessel level cannot be restored, fuel damage is probable.

These channels monitor Hot Leg levels during mid-loop operations and provide signal for IRWST injection on Low 4 level to protect the plant during shutdown operations. The range of the instruments is 0 to 100% of span. ADS 4 is actuated with a time delay coincident with RCS Loop 1 and Loop 2 Hot Leg Level Low 4. The Low-4 setpoint value is chosen to be as low as practical in the Hot Leg pipe, but with extra margin above the potential uncertainty value in order to ensure that higher than expected transmitter errors would still allow actuation within the span of the measurement range.

The difference in the specified RCS levels of EAL 1 and EAL 2 reflect the fact that with CONTAINMENT CLOSURE not established, there is a higher probability of a fission product barrier release to the environment.

EAL (2)

This IC/EAL addresses a significant and prolonged loss of reactor vessel/ inventory control and makeup capability leading to core uncovery and IMMINENT fuel damage. The lost inventory may be due to a RCS component failure, a loss of configuration control, or prolonged boiling of reactor coolant. These conditions include major failures of plant functions needed for protection of the public and thus warrant a Site Area Emergency declaration.

Following an extended loss of core decay heat removal and inventory makeup, decay heat will cause reactor coolant boiling and a further reduction in reactor vessel/RPV level. If RCS/reactor vessel level cannot be restored, fuel damage is probable.

These channels monitor Hot Leg levels during mid-loop operations. The range of the instruments is 0 to 100% of span. The minimum observable level on RCS-LT160 A and B is 0.5%.

The difference in the specified RCS levels of EAL 1 and EAL 2 reflect the fact that with CONTAINMENT CLOSURE established, there is a lower probability of a fission product barrier release to the environment.

EAL (3)

The type and range of RCS/reactor vessel level instrumentation may vary during an outage as the plant moves through various operating modes and refueling evolutions, particularly for an AP1000. As appropriate to the plant design, alternate means of determining RCS/reactor vessel level are installed to assure that the ability to monitor level within the range required by operating procedures will not be interrupted. For the AP1000, the instrumentation range necessary to support implementation of operating procedures in the Cold Shutdown and Refueling modes may be different (e.g., narrower) than that required during modes higher than Cold Shutdown. The basis for this IC and associated EALs is reactor vessel/RCS level below the top of active fuel for greater than or equal to 60 minutes. However, the lowest observable level on AP1000 RCS level instrumentation is the lowest observable level on the RCS Hot Leg Level Instrument. Therefore, this EAL addresses alternative indication of core uncover once ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 44 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 45 of 132 reactor vessel level drops below the bottom of the Hot Leg such as erratic SR Excore Detector indications.

The Containment High Range Radiation monitors, PXS-RY160, 161, 162, and 163 have a range of 1.0E0 to 1.0E+7 rad/hr. The containment radiation High-2 alarm setpoint is 100 rad/hr. The alarm setpoint is sufficiently high to be indicative of a significant loss of shielding above the core indicating likely core uncovery.

This IC/EAL addresses a significant and prolonged loss of reactor vessel/ inventory control and makeup capability leading to core uncovery and IMMINENT fuel damage. The lost inventory may be due to a RCS component failure, a loss of configuration control, or prolonged boiling of reactor coolant. These conditions include major failures of plant functions needed for protection of the public and thus warrant a Site Area Emergency declaration.

Following an extended loss of core decay heat removal and inventory makeup, decay heat will cause reactor coolant boiling and a further reduction in reactor vessel/RPV level. If RCS/reactor vessel level cannot be restored, fuel damage is probable.

The 60-minute criterion is tied to a readily recognizable event start time (i.e., the total loss of ability to monitor level), and allows sufficient time to monitor, assess, and correlate reactor and plant conditions to determine if core uncovery has actually occurred (i.e., to account for various accident progression and instrumentation uncertainties). The passive cooling systems should continue to function and provide a sufficient volume of water for cooling, therefore, 60-minute duration allows sufficient time for performance of actions to terminate leakage, recover inventory control/makeup equipment, and/or restore level monitoring.

The inability to monitor reactor vessel/RCS level may be caused by instrumentation and/or power failures or water level dropping below the range of available instrumentation. If water level cannot be monitored, operators may determine that core uncovery has occurred by observing the alternative indications specified.

These EALs address concerns raised by Generic Letter 88-17, Loss of Decay Heat Removal; SECY 91-283, Evaluation of Shutdown and Low Power Risk Issues; NUREG-1449, Shutdown and Low-Power Operation at Commercial Nuclear Power Plants in the United States; and NUMARC 91-06, Guidelines for Industry Actions to Assess Shutdown Management.

Escalation of the emergency classification level would be via IC CG1 or RG1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 45 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 46 of 132 CA1 ECL: Alert Initiating Condition: Loss of reactor vessel/RCS inventory Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1 or 2)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

RCS Hot Leg Level Low-1 (64.5%) for 15 min. (Note 1)

(2)

Reactor vessel/RCS level cannot be monitored for 30 min. (Note 1)

AND UNPLANNED increase in any Table C-1 sump or tank levels due to a loss of reactor vessel/RCS inventory Table C-1 Sumps & Tanks Visual observation of RCS leakage Containment Sump IRWST RCDT Auxiliary Building (WRS) Sump Basis:

UNPLANNED - A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

EAL (1)

An RCS Hot Leg Level indication of 64.5% corresponds to the Low-1 setpoint or approximately 20" above the inside bottom of the Hot Leg.

This IC/EAL addresses a condition that is a precursor to a loss of the ability to adequately cool irradiated fuel (i.e., a precursor to a challenge to the fuel clad barrier). This condition represents a potential substantial reduction in the level of plant safety.

For this EAL, a lowering of RCS Hot Leg Level below 64.5% for 15 minutes or longer indicates that operator actions have not been successful in restoring and maintaining reactor vessel/RCS water level. The heat-up rate of the coolant will increase as the available water inventory is reduced. A continuing decrease in water level will lead to core uncovery.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 46 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 47 of 132 Although related, this EAL is concerned with the loss of RCS inventory and not the potential concurrent effects on systems needed for decay heat removal (e.g., loss of a residual heat removal suction point). An increase in RCS temperature caused by a loss of decay heat removal capability is evaluated under IC CA3.

EAL (2)

In this condition, all RCS water level indication would be unavailable, and the reactor vessel inventory loss must be detected by sump or tank level changes (Table C-1). Plant design and procedures provide the capability to detect and assess primary system leakage.

This IC/EAL addresses a condition that is a precursor to a loss of the ability to adequately cool irradiated fuel (i.e., a precursor to a challenge to the fuel clad barrier). This condition represents a potential substantial reduction in the level of plant safety.

For this EAL, the inability to monitor reactor vessel/RCS level may be caused by instrumentation and/or power failures or water level dropping below the range of available instrumentation. If water level cannot be monitored, operators may determine that an inventory loss is occurring by observing changes in sump and/or tank levels. Sump and/or tank level changes must be evaluated against other potential sources of water flow to ensure they are indicative of leakage from the reactor vessel/RCS.

The 30-minute duration for the loss of level indication was chosen to allow CA1 EAL 2 to be an effective precursor to CS1 EAL 1. This provides time to increase makeup and isolate leakage prior to core uncovery. Whether or not the actions in progress will be effective should be apparent within 30 minutes. When in Cold Shutdown or Refueling the event can be classified as an Alert due to the significantly reduced decay heat and lower temperature and pressure.

This increases the time available to resolve the problem. Significant fuel damage is not expected to occur until after core uncovery has occurred per the analysis referenced in the CG1 basis.

If the reactor vessel/RCS inventory level continues to lower below the TOAF, then escalation to Site Area Emergency would be via IC CS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 47 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 48 of 132 CA2 ECL: Alert Initiating Condition: Loss of all offsite and all onsite AC power to bussesbuses ECS-ES-1 and 2

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling, Def - Defueled Emergency Action Levels: (1)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Loss of all offsite and all onsite AC Power to bussesbuses ECS-ES-1 and 2 for the condition duration, Table C-5 (Note 1)

Table C-5: RCS Loss of Forced Cooling Thresholds RCS Status Duration INTACT AND not at REDUCED INVENTORY 120 min Not INTACT OR at REDUCED INVENTORY 60 min Basis:

Loss of all AC power compromises all plant systems requiring electric power including heat removal, spent fuel heat removal and the active inventory makeup systems.

The event can be classified as an Alert when in cold shutdown, refueling, or defueled mode because of the significantly reduced decay heat and lower temperature and pressure, increasing the time to restore one of the bussesbuses.

The 60 minute time frame when the RCS is not intact or at reduced inventory and 120 minute time frame when the RCS is intact and not in reduced inventory were chosen based on analysis that indicates that prior to this time no challenges to passive cooling systems exist. Therefore, the times selected as the thresholds allow additional time for recovery of AC power prior to declaration of the Alert.

Escalation of the emergency classification level would be via Category R ICs/EALs.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 48 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 49 of 132 CA3 ECL: Alert Initiating Condition: Inability to maintain the plant in cold shutdown.

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1 or 2)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

UNPLANNED increase in RCS temperature to > 200°F for > the duration specified in Table C-2 (Note 1)

(2)

RCS pressure increase due to UNPLANNED RCS heatup > 80 psig (This EAL does not apply during water-solid plant conditions)

Table C-2: RCS Heat-up Duration Thresholds RCS Status Containment Closure Status Heat-up Duration INTACT AND not at REDUCED INVENTORY N/A 60 min.*

Not INTACT OR at REDUCED INVENTORY established 20 min.*

not established 0 min.

  • If an RCS heat removal system is in operation within this time frame and RCS temperature is being reduced, the EAL is not applicable.

Basis:

CONTAINMENT CLOSURE -Technical Specification Section 3.6 contains the meaning of containment closure for Modes 5 and 6. Containment closure means that all potential escape paths are closed or capable of being closed. Since there are no requirements for containment leak tightness, compliance with Appendix J leakage criteria and test are not required.

RCS INTACT - The RCS can act as an effective pressure boundary.

REDUCED INVENTORY - RCS level 3 feet below the reactor vessel flange (8% wide range pressurizer level).

UNPLANNED-. A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 49 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 50 of 132 A momentary UNPLANNED excursion above the Technical Specification cold shutdown temperature limit (200ºF) when the heat removal function is available does not warrant a classification.

EAL (1)

The RCS should be considered INTACT when the RCS pressure boundary is in its normal condition for the cold shutdown mode of operation (e.g., no freeze seals or nozzle dams).

Several instruments are capable of providing indication of RCS temperature with respect to the Technical Specification cold shutdown temperature limit (200°F). These include RCS-TICA-135A/B, two safety-related thermowell-mounted Hot Leg wide-range temperature detectors (50°F -700°F), one in each Hot Leg. The orientation of the resistance temperature detectors enables measurement of the reactor coolant fluid in the Hot Leg when in REDUCED INVENTORY conditions. Their range is selected to accommodate the low RCS temperatures that can be attained during shutdown. In addition, at least two incore thermocouple channels are available to measure the core exit temperature during mid-loop RNS operation.

This IC/EAL addresses a condition involving a loss of decay heat removal capability or an addition of heat to the RCS in excess of that which can currently be removed. Either condition represents an actual or potential substantial degradation of the level of safety of the plant.

The RCS Heat-up Duration Thresholds table addresses an increase in RCS temperature when CONTAINMENT CLOSURE is established but the RCS is not INTACT or RCS inventory is reduced. The 20-minute criterion was included to allow time for operator action to address the temperature increase.

The RCS Heat-up Duration Thresholds table also addresses an increase in RCS temperature with the RCS INTACT. The status of CONTAINMENT CLOSURE is not crucial in this condition since the INTACT RCS is providing a high pressure barrier to a fission product release. The 60-minute time frame should allow sufficient time to address the temperature increase without a substantial degradation in plant safety.

Finally, in the case where there is an increase in RCS temperature, the RCS is not INTACT or is at REDUCED INVENTORY, and CONTAINMENT CLOSURE is not established, no heat-up duration is allowed (i.e., 0 minutes). This is because 1) the evaporated reactor coolant may be released directly into the Containment atmosphere and subsequently to the environment, and/or

2) there is reduced reactor coolant inventory above the top of the irradiated fuel.

EAL (2)

The minimum readable RCS pressure increment on the wide range RCS pressure instruments (RCS-PICA140A/B/C/D) is 80 psig (0 - 3300 psig based on a 2.4% channel accuracy).

This IC/EAL addresses conditions involving a loss of decay heat removal capability or an addition of heat to the RCS in excess of that which can currently be removed. Either condition represents an actual or potential substantial degradation of the level of safety of the plant.

This EAL provides a pressure-based indication of RCS heat-up.

Escalation of the emergency classification level would be via IC CS1 or RS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 50 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 51 of 132 CA4 ECL: Alert Initiating Condition: Loss of all required Class 1E DC power or Class 1E UPS bus power for 15 minutes or longer Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling, Def - Defueled Emergency Action Levels: (1 or 2)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Indicated voltage < 210 VDC on all required Class 1E 24-hr. DC buses (IDSA/B/C/D-DS-1) for 15 min. (Note 1)

(2)

Loss of power to all 24-hr. Class 1E UPS buses (IDSA/B/C/D-EA-1) for 15 min. (Note 1)

Basis:

Load shedding strategies implemented in AOP-302 are planned actions to cope with an extended loss of AC power and therefore do not warrant classification under this IC, provided operators maintain the ability to re-energize the class 1E bussesbuses when required.

EAL (1)

Minimum Class 1E 24-hr. DC bus voltage of 210 VDC is based on a minimum of 1.75 V per battery cell.

This EAL is the cold condition equivalent of the hot condition loss of all AC power SS1 EAL1.

The purpose of this IC/EAL and its associated EALs is to recognize a loss of the Class 1E 24-hr.

DC, which provides electrical power for safety-related and vital control and monitoring instrumentation loads. This EAL is intended to be anticipatory in as much as the operating crew may not have necessary indication and control of equipment needed to respond to the loss.

Routine maintenance on a division related basis is performed during shutdown periods. It is intended that the loss of the operating (operable) divisions is to be considered. If this loss results in the inability to maintain cold shutdown, then the Alert criteria of CA3 - Inability to Maintain Plant in Cold Shutdown would also be met in addition to the CA4 Alert criteria.

The plant-specific minimum bus voltage is the minimum bus voltage necessary for the operation of safety-related instrumentation and controls. This voltage value incorporates a margin significantly longer than the allowed 15 minutes of operation before the onset of inability to operate those loads. Permanent battery cell damage begins to occur at battery voltage < 210 VDC.

EAL (2) 24-hr. Class 1E UPS buses IDSA-EA-1, IDSB-EA-1, IDSC-EA-1, and IDSD-EA-1 provide instrument and control power to Class 1E SAFETY RELATED equipment and systems.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 51 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 52 of 132 This EAL is the cold condition equivalent of the hot condition loss of power to all 24-hr Class 1E UPS buses SS1 EAL 2.

The purpose of this IC/EAL and its associated EALs is to recognize a loss of the Class 1E 24-hr.

UPS which provides electrical power for safety-related and vital control and monitoring instrumentation loads. This EAL is intended to be anticipatory in as much as the operating crew may not have necessary indication and control of equipment needed to respond to the loss.

Routine maintenance on a division related basis is performed during shutdown periods. It is intended that the loss of the operating (operable) divisions is to be considered. If this loss results in the inability to maintain cold shutdown, then the Alert criteria of CA3 - Inability to Maintain Plant in Cold Shutdown would also be met in addition to the CA4 Alert criteria.

This threshold addresses an event that results in de-energizing all Class 1E UPS control power bussesbuses. This condition would result in degraded capability to monitor and control the unit from the Main Control Room resulting in the need for additional personnel to manage the event.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 52 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 53 of 132 CA7 ECL: Alert Initiating Condition: Hazardous event affecting a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling, Def - Defueled Emergency Action Levels: (1)

(1) The occurrence of any Table C-4 hazardous event AND EITHER of the following:

Event damage has caused indications of degraded performance in at least one train of a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode The event has caused VISIBLE DAMAGE to a system, component or structure NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode Table C-4 Hazardous Events Seismic event (earthquake)

Internal or external FLOODING event High winds or tornado strike FIRE EXPLOSION Other events with similar hazard characteristics as determined by the Shift Manager Basis:

EXPLOSION - A rapid, violent, and catastrophic failure of a piece of equipment due to combustion, chemical reaction, or overpressurization. A release of steam (from high energy lines or components) or an electrical component failure (caused by short circuits, grounding, arcing, etc.) should not automatically be considered an EXPLOSION. Such events require a post-event inspection to determine if the attributes of an EXPLOSION are present.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 53 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 54 of 132 FIRE - Combustion characterized by heat and light. Sources of smoke such as slipping drive belts or overheated electrical equipment do not constitute FIRES. Observation of flame is preferred but is not required if large quantities of smoke and heat are observed.

FLOODING - A condition where water is entering a room or area faster than installed equipment is capable of removal, resulting in a rise of water level within the room or area.

VISIBLE DAMAGE - Damage to a component or structure that is readily observable without measurements, testing, or analysis. The visual impact of the damage is sufficient to cause concern regarding the operability or reliability of the affected component or structure. Damage resulting from an equipment failure and limited to the failed component (i.e., the failure did not cause damage to a structure or any other equipment) is not visible damage. VISIBLE DAMAGE requires at least limited damage to a single SSC; the extent of damage or need to determine the loss of an entire train is not required. This eliminates the need to evaluate the extent of damage and determine the functionality of entire safety system, which would likely exceed 15 minutes.

The significance of seismic events are discussed under HU2 EAL 1.

Internal FLOODING may be caused by events such as component failures, equipment misalignment, or outage activity mishaps.

Seismic Category I structures are analyzed to withstand a sustained, design wind velocity of at least 145 mph (three second gust).

UFSAR Section 1.2.3 Plant Arrangement Description to identify major plant structures containing functions and systems required for safe shutdown of the plant.

An EXPLOSION (including a steam line explosion) that degrades the performance of a safety system train or visibly damages a safety system component or structure would be classified under this EAL. The need to classify a steam line break not considered an explosion itself is considered in fission product barrier degradation monitoring (EAL Category F).

NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN - Safety-related Safe Shutdown systems are defined in UFSAR Table 7.4-1, which include PMS, PXS, PCS, IDS, Containment Isolation Valves, and control rods. Safe Cooldown additionally requires RCS, RNS and associated support SSCs (eg. the applicable portions of CCS, SWS, ECS, EDS and RNS room cooling needed to support RNS) because the RCS is not capable of being cooled to MODE 5 using only safety systems. FWS/SGS are NOT required to support Safe Cooldown because PRHR is capable of cooling the plant to RNS cut-in conditions.

This IC/EAL addresses a hazardous event that causes damage to a system, structure, or component NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN for the current operating mode. This condition significantly reduces the margin to a loss or potential loss of a fission product barrier, and therefore represents an actual or potential substantial degradation of the level of safety of the plant.

The first condition addresses damage to a system, or a structure containing system components, NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN using indications that ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 54 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 55 of 132 are readily available. The indications of degraded performance should be significant enough to cause concern regarding the operability or reliability of the system division.

The second condition addresses damage to a system, or to a structure containing system components NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN that is not readily apparent through indications alone. Operators will make this determination based on the totality of available event and damage report information. This is intended to be a brief assessment not requiring lengthy analysis or quantification of the damage.

Escalation of the ECL would be via IC CS1, RS1 or RS2.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 55 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 56 of 132 CU1 ECL: Notification of Unusual Event Initiating Condition: Inability to restore and maintain required RCS inventory level Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1 or 2)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Inability to restore and maintain RCS a required lower limit 15 min concurrent with indications of coolant leakage. (Note 1)

(2)

Reactor vessel/RCS level cannot be monitored AND UNPLANNED increase in any Table C-1 sump or tank levels due to a loss of reactor vessel/RCS inventory Table C-1 Sumps & Tanks Visual observation of RCS leakage Containment Sump IRWST RCDT Auxiliary Building (WRS) Sump Basis:

UNPLANNED - A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

EAL (1)

This EAL recognizes that the minimum required reactor vessel/RCS level can change several times during the course of a refueling outage as different plant configurations and system lineups are implemented. This EAL is met if the minimum level, specified for the current plant conditions, cannot be maintained for 15 minutes or longer. The minimum level is typically specified in the applicable operating procedure but may be specified in another controlling document.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 56 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 57 of 132 For example, with the plant in Cold Shutdown, RCS water level is normally maintained above the pressurizer Low-2 level setpoint of 10%. With the plant in Refueling mode, RCS water level is normally maintained above the reactor vessel flange.

This IC/EAL addresses the inability to restore and maintain water level to a required minimum level (or the lower limit of a level band) concurrent with indications of coolant leakage. This condition is considered to be a potential degradation of the level of safety of the plant.

Refueling evolutions that decrease RCS water inventory are carefully planned and controlled.

An UNPLANNED event that results in water level decreasing below a procedurally required limit warrants the declaration of a Notification of Unusual Event due to the reduced water inventory that is available to keep the core covered.

The 15-minute threshold duration allows sufficient time for prompt operator actions to restore and maintain the expected water level. This criterion excludes transient conditions causing a brief lowering of water level.

EAL (2)

In this EAL, all water level indication is unavailable and the reactor vessel inventory loss must be detected by sump or tank level changes (Table C-1). Plant design and procedures provide the capability to detect and assess primary system leakage.

This IC/EAL addresses the loss of the ability to monitor reactor vessel/RCS level concurrent with indications of coolant leakage. This condition is considered to be a potential degradation of the level of safety of the plant.

Refueling evolutions that decrease RCS water inventory are carefully planned and controlled.

An UNPLANNED event that results in water level decreasing below a procedurally required limit warrants the declaration of a Notification of Unusual Event due to the reduced water inventory that is available to keep the core covered.

This EAL addresses a condition where all means to determine reactor vessel/RCS level have been lost. All means include local and remote instrumentation, cameras and direct observation.

In this condition, Operators may determine that an inventory loss is occurring by observing changes in sump and/or tank levels. Sump and/or tank level changes must be evaluated against other potential sources of water flow to ensure they are indicative of leakage from the reactor vessel/RCS.

Continued loss of RCS inventory may result in escalation to the Alert emergency classification level via either IC CA1 or CA3.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 57 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 58 of 132 CU3 ECL: Notification of Unusual Event Initiating Condition: UNPLANNED increase in RCS Temperature.

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1 or 2)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

UNPLANNED increase in RCS temperature to > 200 °F (2)

Loss of all RCS temperature AND reactor vessel/RCS level indication for 15 min.

(Note 1)

Basis:

EAL 1 UNPLANNED-A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

Several instruments are capable of providing indication of RCS temperature with respect to the Technical Specification cold shutdown temperature limit (200°F). These include RCS-TICA-135A/B, two safety-related thermowell-mounted Hot Leg wide-range temperature detectors (50°F -700°F), one in each Hot Leg. The orientation of the resistance temperature detectors enables measurement of the reactor coolant fluid in the Hot Leg when in REDUCED INVENTORY conditions. Their range is selected to accommodate the low RCS temperatures that can be attained during shutdown. In addition, at least two incore thermocouple channels are available to measure the core exit temperature during mid-loop RNS operation.

This IC/EAL addresses an UNPLANNED increase in RCS temperature above the Technical Specification cold shutdown temperature limit and represents a potential degradation of the level of safety of the plant. If the RCS is not INTACT and CONTAINMENT CLOSURE is not established during this event, the Emergency Director should refer to IC CA3.

A momentary UNPLANNED excursion above the Technical Specification cold shutdown temperature limit when the heat removal function is available does not warrant a classification.

This EAL involves a loss of decay heat removal capability or an addition of heat to the RCS in excess of that which can currently be removed, such that reactor coolant temperature cannot be maintained below the cold shutdown temperature limit specified in Technical Specifications.

During this condition, there is no immediate threat of fuel damage because the core decay heat load has been reduced since the cessation of power operation.

During an outage, the level in the reactor vessel will normally be maintained above the reactor vessel flange. Refueling evolutions that lower water level below the reactor vessel flange are carefully planned and controlled. A loss of forced decay heat removal at REDUCED ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 58 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 59 of 132 INVENTORY may result in a rapid increase in reactor coolant temperature depending on the time after shutdown.

Escalation to Alert would be via IC CA1 based on an inventory loss or IC CA3 based on exceeding plant configuration-specific time criteria.

EAL 2 Several instruments are capable of providing indication of RCS temperature with respect to the Technical Specification cold shutdown temperature limit (200°F). These include RCS-TICA-135A/B, two safety-related thermowell-mounted Hot Leg wide-range temperature detectors (50°F -700°F), one in each Hot Leg. The orientation of the resistance temperature detectors enables measurement of the reactor coolant fluid in the Hot Leg when in REDUCED INVENTORY conditions. Their range is selected to accommodate the low RCS temperatures that can be attained during shutdown. In addition, at least two incore thermocouple channels are available to measure the core exit temperature during mid-loop RNS operation.

Numerous RCS level monitoring instruments are capable of providing RCS inventory status.

These include:

Pressurizer Level: An independent pressurizer level transmitter, calibrated for low temperature conditions, providing water level indication during startup, shutdown, and refueling operations in the Main Control Room and in the Remote Shutdown Workstation.

RCS Hot Leg Level: There are two safety-related RCS Hot Leg level channels, one located in each Hot Leg. These level indicators are provided primarily to monitor the RCS water level during mid-loop operation following shutdown operations.

Pressurizer Level Narrow Range This IC/EAL addresses the inability to determine RCS temperature and level and represents a potential degradation of the level of safety of the plant. If the RCS is not INTACT and CONTAINMENT CLOSURE is not established during this event, the Emergency Director should also refer to IC CA3.

This EAL reflects a condition where there has been a significant loss of instrumentation capability necessary to monitor RCS conditions and operators would be unable to monitor key parameters necessary to assure core decay heat removal. During this condition, there is no immediate threat of fuel damage because the core decay heat load has been reduced since the cessation of power operation.

Fifteen minutes was selected as a threshold to exclude transient or momentary losses of indication.

Escalation to Alert would be via IC CA1 based on an inventory loss or IC CA3 based on exceeding plant configuration-specific time criteria.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 59 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 60 of 132 CU4 ECL: Notification of Unusual Event Initiating Condition: Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 30 minutes or longer Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling, Def-Defueled Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 30 min.

(Note 1)

Basis:

Motor control centers (ECS-EC-121/221) from non-Class 1E bussesbuses ECS-ES-1 and ECS-ES-2 power the battery chargers for the Class 1E safety-related batteries. If these bussesbuses are deenergized, the safety-related batteries cannot be charged. As used in this EAL the term capability means at least one offsite or onsite standby AC power source is either currently powering a non-Class 1E bus (ECS-ES-1 or ECS-ES-2) or is capable of energizing and powering a charger on at least one non-Class 1E bus (ECS-ES-1 or ECS-ES-2) within 30 min.

This cold condition EAL is equivalent to the hot condition loss of electrical power SU1 EAL1.

The Class 1E 24-hr. DC system provides electrical power for safety-related and vital control and monitoring instrumentation loads. The offsite AC power system normally supplies power for the unit in cold shutdown, refueling, and defueled conditions. Both the normal offsite and standby onsite AC power systems are non-Class 1E with no Technical Specification requirements. All safety-related functions associated with the unit in cold shutdown and refueling are provided by the safety-related onsite Class 1E DC power systems including the 120V Vital AC power system supplied from the batteries powering the safety-related DC buses through inverters. The AP1000 also has standby diesel generators that are not safety-related. Storage batteries are the safety-related power source for Class 1E electric power. However, this non-Class 1E AC power is required to charge the safety-related DC batteries and maintain long-term safety-related DC bus voltage.

Loss of Class 1E 24-hr. DC power potentially compromises all safety-related plant systems requiring electric power. The event can be classified as an Unusual Event, because the passive design affords additional and redundant means to remove heat passively or restore power to active components.

30 minutes was chosen to allow sufficient time for plant personnel to attempt to establish a viable offsite or diesel generator AC power supply to the plant-specific AC power buses required to charge one or more Class 1E 24-hr. DC batteries.

Escalation of the emergency classification level would be via IC CA4 if the Class 1E battery voltage drops below 210 VDC.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 60 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 61 of 132 CU5 ECL: Notification of Unusual Event Initiating Condition: Loss of all onsite or offsite communications capabilities.

Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling, Def - Defueled Emergency Action Levels: (1 or 2 or 3)

(1)

Loss of all Table C-3 onsite communication methods (2)

Loss of all Table C-3 ORO communication methods (3)

Loss of all Table C-3 NRC communication methods Table C-3 Communication Methods System Onsite ORO NRC Public Address System X

In Plant Telephones X

Plant Radio Systems X

Commercial Phones X

X ENN (Emergency Notification Network)

X ENS on Federal Telecommunications System (FTS)

X Basis:

The Table C-3 list for onsite communications loss encompasses the loss of all means of routine communications (e.g., in plant telephones, page system, and radios).

The Table C-3 list for offsite response organization (ORO) communications loss encompasses the loss of all means of communications with offsite authorities (e.g., ENN and commercial telephone lines).

The Table C-3 list for NRC communications loss includes the FTS (ENS) and commercial telephone lines.

This EAL is the cold condition equivalent of the hot condition SU6 EAL1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 61 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 62 of 132 This IC addresses a significant loss of onsite or offsite communications capabilities. While not a direct challenge to plant or personnel safety, this event warrants prompt notifications to OROs and the NRC.

This IC should be assessed only when extraordinary means are being utilized to make communications possible (e.g., use of non-plant, privately owned equipment, relaying of on-site information via individuals or multiple radio transmission points, individuals being sent to offsite locations, etc.).

EAL (1)

The first EAL condition addresses a total loss of the communications methods used in support of routine plant operations.

EAL (2 and 3)

The second and third EAL conditions address a total loss of the communications methods used to notify all offsite organizations of an emergency declaration. The OROs referred to here are the States of Georgia and South Carolina; Burke, Aiken, Allendale and Barnwell Counties; Savannah River Site (SRS); and the NRC.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 62 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 63 of 132 CU6 ECL: Notification of Unusual Event Initiating Condition: UNPLANNED full loss of monitoring and control functions for 15 minutes or longer Operating Mode Applicability: 5 - Cold Shutdown, 6 - Refueling Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

UNPLANNED full loss of indicating, monitoring, and control functions from all of the following for > 15 min. (Note 1):

Protection and Monitoring System (PMS)

Plant Control System (PLS)

Diverse Actuation System (DAS)

Basis:

UNPLANNED - A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

This EAL is the cold condition equivalent of the hot condition SA2 EAL1.

This IC recognizes the difficulty associated with monitoring and controlling changing plant conditions without the use of a major portion of the control and indication systems. A Notification of Unusual Event level is considered appropriate for this loss of monitoring and control IC due to the inherently safer condition of the core when in the cold condition. The selection of 15 minutes was chosen to allow personnel sufficient time for restoration of required systems in the Main Control Room due to an inadvertent loss.

Systems that provide monitoring and control capability include:

The Protection and Monitoring System (PMS) provides the functions necessary to protect the plant during normal operations, to shut down the plant, and to maintain the plant in a safe shutdown condition.

The Plant Control System (PLS) is a non-safety-related system and includes the control functions that provide for the control of the nuclear process, conversion of nuclear energy into heat energy, and transport of the heat energy from the nuclear reactor to the main steam turbine.

The Diverse Actuation System (DAS) is a nonsafety-related system available to ensure monitoring and control capability as well as providing an alternative means of initiating a reactor trip and selected engineering safety features.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 63 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 64 of 132 4.12 FISSION PRODUCT BARRIER ICs/EALs Recognition Category F Initiating Condition Matrix GENERAL EMERGENCY FG1 Loss of any two barriers and loss or potential loss of the third barrier.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SITE AREA EMERGENCY FS1 Loss or potential loss of any two barriers.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown ALERT FA1 Any loss or any potential loss of either Fuel Clad or RCS Barrier.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown 3/3 2/3 1/2 Loss of at least 2 Barriers?

LOSS POTENTIAL LOSS FUEL CLAD LOSS POTENTIAL LOSS RCS LOSS POTENTIAL LOSS CONTAINMENT LOSS POTENTIAL LOSS FUEL CLAD LOSS POTENTIAL LOSS RCS LOSS POTENTIAL LOSS CONTAINMENT LOSS POTENTIAL LOSS FUEL CLAD LOSS POTENTIAL LOSS RCS FG1 - Loss of ANY Two Barriers AND Loss or Potential Loss of Third Barrier

-- YES --

FS1 - Loss or Potential Loss of ANY Two Barriers

-- NO --

FA1 - ANY Loss or ANY Potential Loss of EITHER Fuel Clad OR RCS ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 64 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 65 of 132 Fission Product Barrier Table Thresholds for LOSS or POTENTIAL LOSS of Barriers FG1 GENERAL EMERGENCY Loss of any two barriers and Loss or Potential Loss of the third barrier.

FS1 SITE AREA EMERGENCY Loss or Potential Loss of any two barriers.

FA1 ALERT Any Loss or any Potential Loss of either the Fuel Clad or RCS barrier.

Fuel Clad Barrier RCS Barrier Containment Barrier LOSS POTENTIAL LOSS LOSS POTENTIAL LOSS LOSS POTENTIAL LOSS

1. RCS or SG Tube Leakage
1. RCS or SG Tube Leakage
1. RCS or SG Tube Leakage NoneNot Applicable A. RCS Hot Leg Level

< 0.5%

A. An automatic or manual safeguards actuation required by EITHER:

UNISOLABLE RCS leakage SG tube RUPTURE B. Automatic or manual actuation of ADS A. Operation of a second CVS makeup pump is required by EITHER:

UNISOLABLE RCS leakage SG tube leakage B. CSFST RCS Integrity-RED path conditions met A. A leaking or RUPTURED SG is FAULTED outside of containment.

Not ApplicableNone

2. Inadequate Heat Removal
2. Inadequate Heat Removal
2. Inadequate Heat Removal A. CSFST Core Cooling-RED path conditions met A. CSFST Core Cooling-ORANGE path conditions met B. CSFST Heat Sink-RED path conditions met AND Heat sink is required Not ApplicableNone A. CSFST Heat Sink-RED path conditions met AND Heat sink is required Not ApplicableNone A.

CSFST Core Cooling-RED path conditions met AND Restoration procedures not effective within 15 min. (Note 1)

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 65 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 66 of 132 Fuel Clad Barrier RCS Barrier Containment Barrier LOSS POTENTIAL LOSS LOSS POTENTIAL LOSS LOSS POTENTIAL LOSS

3. RCS Activity / Containment Radiation
3. RCS Activity / Containment Radiation
3.

RCS Activity / Containment Radiation A. PXS-RY160/161/162/16 3 CTMT High Range Radiation >

2.80E+01 rad/hr B. Dose equivalent I-131 coolant activity > 300

µCi/gm Not ApplicableNone A. PXS-RY160/161/162/163 CTMT High Range Radiation >

1.40E+00 rad/hr Not ApplicableNone Not ApplicableNone A.

PXS-RY160/161/162/163 CTMT High Range Radiation >

9.20E+03 rad/hr

4. Containment Integrity or Bypass
4. Containment Integrity or Bypass
4.

Containment Integrity or Bypass Not ApplicableNone Not ApplicableNone Not ApplicableNone Not ApplicableNone A. Containment isolation is required AND EITHER:

Containment integrity has been lost based on ED judgment UNISOLABLE pathway from containment to the environment exists B. Indications of RCS leakage outside of containment A. CSFST Containment-RED path conditions met B. Containment hydrogen concentration (VLS-AE001/002/003) >

4%

C. Containment pressure 5.0 psig (High 2)

AND PCS flow cannot be established within 15 min. (Note 1)

5. Emergency Director Judgment
5. Emergency Director Judgment
5.

Emergency Director Judgment A. Any condition in the opinion of the Emergency Director that indicates loss of the fuel clad barrier A. Any condition in the opinion of the Emergency Director that indicates potential loss of the fuel clad barrier A. Any condition in the opinion of the Emergency Director that indicates loss of the RCS barrier A. Any condition in the opinion of the Emergency Director that indicates potential loss of the RCS barrier A. Any condition in the opinion of the Emergency Director that indicates loss of the containment barrier A. Any condition in the opinion of the Emergency Director that indicates potential loss of the containment barrier ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 66 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 67 of 132 Basis Information For Fission Product Barrier EALs FUEL CLAD BARRIER THRESHOLDS:

The Fuel Clad Barrier consists of the cladding material that contains the fuel pellets.

1.

RCS or SG Tube Leakage There is no Loss threshold associated with RCS or SG Tube Leakage.

Potential Loss 1.A The minimum observable level on the RCS Hot Leg Level instruments RCS-LICA-160A/B is 0.5%.

This reading indicates a reduction in reactor vessel water level that threatens the onset of heat-induced cladding damage.

Short duration spikes in Hot Leg levels may occur due to flow and pressure oscillations in the RCS induced by variations in break flow and injection flow. When determining if the threshold is exceeded based on Hot Leg levels being actually voided, consideration should be given to the duration of the low level condition and the indication of both Hot Leg level instruments.

2.

Inadequate Heat Removal Loss 2.A This condition indicates temperatures within the core are sufficient to cause significant superheating of reactor coolant.

Potential Loss 2.A This condition indicates a reduction in reactor vessel water level sufficient to allow the onset of heat-induced cladding damage.

Potential Loss 2.B This condition indicates an extreme challenge to the ability to remove RCS heat using the steam generators (i.e., loss of an effective secondary-side heat sink). This condition represents a potential loss of the Fuel Clad Barrier. In accordance with EOPs, there may be unusual accident conditions during which operators intentionally reduce the heat removal capability of the steam generators; during these conditions, classification using threshold is not warranted.

The phrase and heat sink required precludes the need for classification for conditions in which ADS Stage 1-3 and/or Stage 4 are actuated and feed from PXS CMTs, accumulators, and/or IRWST and bleed from ADS have been established to maintain core cooling. For this case, the passive safety systems (PXS and PCS) provide the required core cooling function and fuel clad protection. FR-H.1 Response To Loss Of Heat Sink returns the user to the procedure and step in effect if ADS Stage 1-3 actuation has occurred.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 67 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 68 of 132 Meeting this threshold results in a Site Area Emergency because this threshold is identical to RCS Barrier Potential Loss threshold 2.A; both will be met. This condition warrants a Site Area Emergency declaration because inadequate RCS heat removal may result in fuel heat-up sufficient to damage the cladding and increase RCS pressure to the point where mass will be lost from the system.

3.

RCS Activity / Containment Radiation Loss 3.A The radiation monitor reading corresponds to an instantaneous release of all reactor coolant mass into the containment, assuming that reactor coolant activity equals 300µCi/gm dose equivalent I-131. Reactor coolant activity above this level is greater than that expected for iodine spikes and corresponds to an approximate range of 2 percent to 5 percent fuel clad damage. Since this condition indicates that a significant amount of fuel clad damage has occurred, it represents a loss of the Fuel Clad Barrier.

The radiation monitor reading in this threshold is higher than that specified for RCS Barrier Loss threshold 3.A since it indicates a loss of both the Fuel Clad Barrier and the RCS Barrier. Note that a combination of the two monitor readings appropriately escalates the emergency classification level to a Site Area Emergency.

Loss 3.B This threshold indicates that RCS radioactivity concentration is greater than 300 µCi/gm dose equivalent I-131. Reactor coolant activity above this level is greater than that expected for iodine spikes and corresponds to an approximate range of 2 percent to 5 percent fuel clad damage. Since this condition indicates that a significant amount of fuel clad damage has occurred, it represents a loss of the Fuel Clad Barrier.

It is recognized that sample collection and analysis of reactor coolant with highly elevated activity levels could require several hours to complete. Nonetheless, a sample related threshold is included as a backup to other indications.

There is no Potential Loss threshold associated with RCS Activity / Containment Radiation.

4.

Containment Integrity or Bypass Not Applicable (included for numbering consistency)

5.

Emergency Director Judgment Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the fuel clad barrier is lost.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 68 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 69 of 132 Potential Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the Fuel Clad Barrier is potentially lost. The Emergency Director should also consider whether or not to declare the barrier potentially lost in the event that barrier status cannot be monitored.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 69 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 70 of 132 RCS BARRIER THRESHOLDS:

The RCS Barrier includes the RCS primary side and its connections up to and including the pressurizer safety and relief valves, and other connections up to and including the primary isolation valves.

1.

RCS or SG Tube Leakage Loss 1.A This threshold is based on an UNISOLABLE RCS leak of sufficient size to require an automatic or manual safeguards actuation. This condition clearly represents a loss of the RCS Barrier.

This threshold is applicable to unidentified and pressure boundary leakage, as well as identified leakage. It is also applicable to UNISOLABLE RCS leakage through an interfacing system. The mass loss may be into any location - inside containment, to the secondary-side (i.e., steam generator tube leakage), or outside of containment.

A steam generator with primary-to-secondary leakage of sufficient magnitude to require a safeguards actuation is considered to be RUPTURED. If a RUPTURED steam generator is also FAULTED outside of containment, the declaration escalates to a Site Area Emergency since the Containment Barrier Loss threshold 1.A will also be met.

Loss 1.B The Automatic Depressurization System (ADS) valves are part of the RCS and interface with the Passive Core Cooling System (PXS). Manual or automatic actuation of the ADS valves in response to a valid initiation setpoint initiates an RCS leak meeting the RCS Loss criteria. Inadvertent opening that can be isolated or momentary jogging of ADS valves for pressure control does not constitute a loss of RCS.

Potential Loss 1.A This threshold is based on an UNISOLABLE RCS leak that results in the inability to maintain pressurizer level within specified limits by operation of a single CVS makeup pump, but safeguards actuation has not occurred. The threshold is met when an operating procedure, or operating crew supervision, directs that a second CVS makeup pump be placed in service to restore and maintain pressurizer level. Nominal design flow rate of a single CVS makeup pump is 135 gpm.

This threshold is applicable to unidentified and pressure boundary leakage, as well as identified leakage. It is also applicable to UNISOLABLE RCS leakage through an interfacing system. The mass loss may be into any location - inside containment, to the secondary-side (i.e., steam generator tube leakage) or outside of containment.

If a leaking steam generator is also FAULTED outside of containment, the declaration escalates to a Site Area Emergency since the Containment Barrier Loss threshold 1.A will also be met.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 70 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 71 of 132 Potential Loss 1.B This condition indicates an extreme challenge to the integrity of the RCS pressure boundary due to pressurized thermal shock - a transient that causes rapid RCS cooldown while the RCS is in Mode 4 or higher (i.e., hot and pressurized).

2. Inadequate Heat Removal There is no Loss threshold associated with Inadequate Heat Removal.

Potential Loss 2.A This condition indicates an extreme challenge to the ability to remove RCS heat using the steam generators or Passive Residual Heat Removal System (PRHR) (i.e., loss of an effective secondary-side heat sink). This condition represents a potential loss of the RCS Barrier. In accordance with EOPs, there may be unusual accident conditions during which operators intentionally reduce the heat removal capability of the steam generators; during these conditions, classification using threshold is not warranted. This threshold is also not applicable to conditions where heat sink is not required (i.e. steam generator pressures are greater than RCS pressure).

The phrase and heat sink required precludes the need for classification for conditions in which ADS Stage 1-3 and/or Stage 4 are actuated and feed from PXS CMTs, accumulators, and/or IRWST and bleed from ADS have been established to maintain core cooling. For this case, the passive safety systems (PXS and PCS) provide the required core cooling function and fuel clad protection. FR-H.1 Response To Loss Of Heat Sink returns the user to the procedure and step in effect if ADS Stage 1-3 actuation has occurred.

Meeting this threshold results in a Site Area Emergency because this threshold is identical to Fuel Clad Barrier Potential Loss threshold 2.B; both will be met. This condition warrants a Site Area Emergency declaration because inadequate RCS heat removal may result in fuel heat-up sufficient to damage the cladding and increase RCS pressure to the point where mass will be lost from the system.

3.

RCS Activity / Containment Radiation Loss 3.A The radiation monitor reading corresponds to an instantaneous release of all reactor coolant mass into the containment, assuming that reactor coolant activity equals Technical Specification allowable limits. This value is lower than that specified for Fuel Clad Barrier Loss threshold 3.A since it indicates a loss of the RCS Barrier only.

There is no Potential Loss threshold associated with RCS Activity / Containment Radiation.

4.

Containment Integrity or Bypass Not Applicable (included for numbering consistency)

5.

Emergency Director Judgment ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 71 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 72 of 132 Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the RCS Barrier is lost.

Potential Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the RCS Barrier is potentially lost. The Emergency Director should also consider whether or not to declare the barrier potentially lost in the event that barrier status cannot be monitored.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 72 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 73 of 132 CONTAINMENT BARRIER THRESHOLDS:

The Containment Barrier includes the containment building and connections up to and including the outermost containment isolation valves. This barrier also includes the main steam, feedwater, and blowdown line extensions outside the containment building up to and including the outermost secondary side isolation valve. Containment Barrier thresholds are used as criteria for escalation of the ECL from Alert to a Site Area Emergency or a General Emergency.

1.

RCS or SG Tube Leakage Loss 1.A This threshold addresses a leaking or RUPTURED Steam Generator (SG) that is also FAULTED outside of containment. The condition of the SG, whether leaking or RUPTURED, is determined in accordance with the thresholds for RCS Barrier Potential Loss 1.A and Loss 1.A, respectively. This condition represents a bypass of the containment barrier.

FAULTED is a defined term; this determination is not necessarily dependent upon entry into, or diagnostic steps within, an EOP. For example, if the pressure in a steam generator is decreasing uncontrollably [part of the FAULTED definition] and the faulted steam generator isolation procedure is not entered because EOP user rules are dictating implementation of another procedure to address a higher priority condition, the steam generator is still considered FAULTED for emergency classification purposes.

The FAULTED criterion establishes an appropriate lower bound on the size of a steam release that may require an emergency classification. Steam releases of this size are readily observable with normal Main Control Room indications. The lower bound for this aspect of the containment barrier is analogous to the lower bound criteria specified in IC SU3 for the fuel clad barrier (i.e., RCS activity values) and IC SU4 for the RCS barrier (i.e., RCS leak rate values).

Steam releases associated with the expected operation of a SG Power Operated Relief Valve (PORV) or Main Steam Safety Valve (MSSV) do not meet the intent of this threshold. Such releases may occur intermittently for a short period of time following a reactor trip as operators process through emergency operating procedures to bring the plant to a stable condition and prepare to initiate a plant cooldown. Steam releases associated with the unexpected operation of a valve (e.g., a stuck-open MSSV) do meet this threshold.

Following a SG tube leak or RUPTURE, there may be minor radiological releases through a secondary-side system component (e.g., condenser vacuum pumps, gland seal exhausters, valve packing, etc.). These types of releases do not constitute a loss or potential loss of containment but should be evaluated using the Recognition Category R ICs.

The emergency classification levels resulting from primary-to-secondary leakage, with or without a steam release from the FAULTED SG, are summarized below.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 73 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 74 of 132 Affected SG is FAULTED Outside of Containment?

P-to-S Leak Rate Yes No Less than or equal to 25 gpm No classification No classification Greater than 25 gpm Notification of Unusual Event per SU4 Notification of Unusual Event per SU4 Requires an automatic or manual safeguards actuation (RCS Barrier Loss)

Site Area Emergency per FS1 Alert per FA1 Operation of a second CVS Makeup pump due to SG tube leakage (RCS Barrier Potential Loss)

Site Area Emergency per FS1 Alert per FA1 There is no Containment Potential Loss threshold associated with RCS or SG Tube Leakage.

2.

Inadequate Heat Removal There is no Loss threshold associated with Inadequate Heat Removal.

Potential Loss 2.A This condition represents an IMMINENT core melt sequence which, if not corrected, could lead to vessel failure and an increased potential for containment failure. For this condition to occur, there must already have been a loss of the RCS Barrier and the Fuel Clad Barrier. If implementation of a procedure(s) to restore adequate core cooling is not effective (successful) within 15 minutes, it is assumed that the event trajectory will likely lead to core melting and a subsequent challenge of the Containment Barrier.

The restoration procedure is considered effective if core exit thermocouple readings are decreasing and/or if reactor vessel level is increasing. Whether or not the procedure(s) will be effective should be apparent within 15 minutes. The Emergency Director should escalate the ECL to a General Emergency as soon as it is determined that the procedure(s) will not be effective.

Severe accident analyses (e.g., NUREG-1150) have concluded that function restoration procedures can arrest core degradation in a significant fraction of core damage scenarios, and that the likelihood of containment failure is very small in these events.

Given this, it is appropriate to provide 15 minutes beyond the required entry point to determine if procedural actions can reverse the core melt sequence.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 74 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 75 of 132

3.

RCS Activity / Containment Radiation There is no Loss threshold associated with RCS Activity / Containment Radiation.

Potential Loss 3.A The radiation monitor reading corresponds to an instantaneous release of all reactor coolant mass into the containment, assuming that 20% of the fuel cladding has failed.

This level of fuel clad failure is well above that used to determine the analogous Fuel Clad Barrier Loss and RCS Barrier Loss thresholds.

NUREG-1228, Source Estimations During Incident Response to Severe Nuclear Power Plant Accidents, indicates the fuel clad failure must be greater than approximately 20%

in order for there to be a major release of radioactivity requiring offsite protective actions.

For this condition to exist, there must already have been a loss of the RCS Barrier and the Fuel Clad Barrier. It is therefore prudent to treat this condition as a potential loss of containment which would then escalate the ECL to a General Emergency.

4.

Containment Integrity or Bypass Loss 4.A These thresholds address a situation where containment isolation is required and one of two conditions exists as discussed below. Users are reminded that there may be accident and release conditions that simultaneously meet both bulleted thresholds.

4.A.1 - Containment integrity has been lost, i.e., the actual containment atmospheric leak rate likely exceeds that associated with allowable leakage (or sometimes referred to as design leakage). Following the release of RCS mass into containment, containment pressure will fluctuate based on a variety of factors; a loss of containment integrity condition may (or may not) be accompanied by a noticeable drop in containment pressure. Recognizing the inherent difficulties in determining a containment leak rate during accident conditions, it is expected that the Emergency Director will assess this threshold using judgment, and with due consideration given to current plant conditions, and available operational and radiological data (e.g., containment pressure, readings on radiation monitors outside containment, operating status of containment pressure control equipment, etc.).

Refer to the middle piping run of Figure 6-F-1. Two simplified examples are provided.

One is leakage from a penetration and the other is leakage from an in-service system valve. Depending upon radiation monitor locations and sensitivities, the leakage could be detected by any of the four monitors depicted in the figure.

Another example would be a loss or potential loss of the RCS barrier, and the simultaneous occurrence of two FAULTED locations on a steam generator where one fault is located inside containment (e.g., on a steam or feedwater line) and the other outside of containment. In this case, the associated steam line provides a pathway for the containment atmosphere to escape to an area outside the containment.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 75 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 76 of 132 Following the leakage of RCS mass into containment and a rise in containment pressure, there may be minor radiological releases associated with allowable (design) containment leakage through various penetrations or system components. These releases do not constitute a loss or potential loss of containment but should be evaluated using the Recognition Category R ICs.

4.A.2 - Conditions are such that there is an UNISOLABLE pathway for the migration of radioactive material from the containment atmosphere to the environment. As used here, the term environment includes the atmosphere of a room or area, outside the containment, that may, in turn, communicate with the outside-the-plant atmosphere (e.g.,

through discharge of a ventilation system or atmospheric leakage). Depending upon a variety of factors, this condition may or may not be accompanied by a noticeable drop in containment pressure not attributable to PCS actuation.

Refer to the top piping run of Figure 6-F-1. In this simplified example, the inboard and outboard isolation valves remained open after a containment isolation was required (i.e.,

containment isolation was not successful). There is now an UNISOLABLE pathway from the containment to the environment.

The existence of a filter is not considered in the threshold assessment. Filters do not remove fission product noble gases. In addition, a filter could become ineffective due to iodine and/or particulate loading beyond design limits (i.e., retention ability has been exceeded) or water saturation from steam/high humidity in the release stream.

Leakage between two interfacing liquid systems, by itself, does not meet this threshold.

Refer to the bottom piping run of Figure 6-F-1. In this simplified example, leakage in an RCP cooler is allowing radioactive material to enter the Auxiliary Building. The radioactivity would be detected by the Process Monitor. If there is no leakage from the closed water cooling system to the Auxiliary Building, then no threshold has been met. If the pump developed a leak that allowed steam/water to enter the Auxiliary Building, then the second threshold would be met. Depending upon radiation monitor locations and sensitivities, this leakage could be detected by any of the four monitors depicted in the figure and cause the first threshold to be met as well.

Following the leakage of RCS mass into containment and a rise in containment pressure, there may be minor radiological releases associated with allowable (design) containment leakage through various penetrations or system components. Minor releases may also occur if a containment isolation valve(s) fails to close but the containment atmosphere escapes to a closed system. These releases do not constitute a loss or potential loss of containment but should be evaluated using the Recognition Category R ICs.

The status of the containment barrier during an event involving steam generator tube leakage is assessed using Loss Threshold 1.A.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 76 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 77 of 132 Loss 4.B Containment sump, temperature, pressure and/or radiation levels will increase if reactor coolant mass is leaking into the containment. If these parameters have not increased, then the reactor coolant mass may be leaking outside of containment (i.e., a containment bypass sequence). Increases in sump, temperature, pressure, flow and/or radiation level readings outside of the containment may indicate that the RCS mass is being lost outside of containment.

Unexpected elevated readings and alarms on radiation monitors with detectors outside containment should be corroborated with other available indications to confirm that the source is a loss of RCS mass outside of containment. If the fuel clad barrier has not been lost, radiation monitor readings outside of containment may not increase significantly. However, other unexpected changes in sump levels, area temperatures or pressures, flow rates, etc. should be sufficient to determine if RCS mass is being lost outside of the containment.

Refer to the middle piping run of Figure 6-F-1. In this simplified example, a leak has occurred at a reducer on a pipe carrying reactor coolant in the Auxiliary Building.

Depending upon radiation monitor locations and sensitivities, the leakage could be detected by any of the four monitors depicted in the figure and cause threshold 4.A to be met as well.

To ensure proper escalation of the emergency classification, the RCS leakage outside of containment must be related to the mass loss that is causing the RCS Loss and/or Potential Loss threshold 1.A to be met.

Potential Loss 4.A If containment pressure exceeds the design pressure, there exists a potential to lose the Containment Barrier. To reach this level, there must have been inadequate core cooling for an extended period of time. The RCS and Fuel Clad barriers have already been lost.

This would cause an upgrade of ECL from Site Area Emergency to General Emergency based on the potential loss of the third barrier.

Potential Loss 4.B The existence of an explosive mixture means, at a minimum, that the containment atmospheric hydrogen concentration is sufficient to support a hydrogen burn (i.e., at the lower deflagration limit). A hydrogen burn will raise containment pressure and could result in collateral equipment damage leading to a loss of containment integrity. It therefore represents a potential loss of the Containment Barrier.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 77 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 78 of 132 Potential Loss 4.C This threshold describes a condition where containment pressure is greater than or equal to the setpoint at which the containment energy (heat) removal system, Passive Containment Cooling System (PCS) is designed to automatically actuate, but does not actuate and perform its safety function per design. The 15-minute criterion is included to allow operators time to manually align PCS components that may not have automatically actuated, if possible. This threshold represents a potential loss of containment in that the containment heat removal/depressurization systems (not including containment venting strategies) are either lost or performing in a degraded manner.

5.

Emergency Director Judgment Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the Containment Barrier is lost.

Potential Loss 5.A This threshold addresses any other factors that may be used by the Emergency Director in determining whether the Containment Barrier is potentially lost. The Emergency Director should also consider whether or not to declare the barrier potentially lost in the event that barrier status cannot be monitored.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 78 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 79 of 132 Figure 6-F-1: Containment Integrity or Bypass Examples Inside Containment Vent Auxiliary Building Filter Closed Cooling Water System RCP External Heat Exchanger Interface leakage point Open valve Penetration Damper Damper Process Monitor Airborne Monitor Area Monitor Effluent Monitor 2nd Threshold-RCS leakage outside CNMT Open valve Open valve Open valve Open valve Open valve 2nd Threshold-Airborne release from pathway 1st Threshold-Airborne release from valve Pump 1st Threshold-Airborne release from penetration ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 79 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 80 of 132 4.13 HAZARDOUS ICS/ EALs GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT HS1 HOSTILE ACTION within the PROTECTED AREA.

Op. Modes: All HA1 HOSTILE ACTION within the OWNER CONTROLLED AREA or airborne attack threat within 30 minutes.

Op. Modes: All HU1 Confirmed SECURITY CONDITION or threat.

Op. Modes: All HU2 Seismic event greater than OBE levels.

Op. Modes: All HU3 Hazardous event.

Op. Modes: All HU4 FIRE potentially degrading the level of safety of the plant.

Op. Modes: All HA5 Gaseous release IMPEDING access to equipment necessary for normal plant operations, cooldown or shutdown.

Op. Modes: All HS6 Inability to control a key safety function from outside the Control Room.

Op. Modes: All HA6 Control Room evacuation resulting in transfer of plant control to alternate locations.

Op. Modes: All HG7 Other conditions exist which in the judgment of the Emergency Director warrant declaration of a General Emergency Op. Modes: All HS7 Other conditions exist which in the judgment of the Emergency Director warrant declaration of a Site Area Emergency Op. Modes: All HA7 Other conditions exist which in the judgment of the Emergency Director warrant declaration of an Alert Op. Modes: All HU7 Other conditions exist which in the judgment of the Emergency Director warrant declaration of a NOUE Op. Modes: All ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 80 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 81 of 132 HG7 ECL: General Emergency Initiating Condition: Other conditions exist which in the judgment of the Emergency Director warrant declaration of a General Emergency.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

Other conditions exist which in the judgment of the Emergency Director indicate that events are in progress or have occurred which involve actual or IMMINENT substantial core degradation or melting with potential for loss of containment integrity OR HOSTILE ACTION that results in an actual loss of physical control of the facility.

Releases can be reasonably expected to exceed EPA Protective Action Guideline exposure levels offsite for more than the immediate site area.

Basis:

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

IMMINENT - The trajectory of events or conditions is such that an EAL will be met within a relatively short period of time regardless of mitigation or corrective actions.

This IC addresses unanticipated conditions not addressed explicitly elsewhere but that warrant declaration of an emergency because conditions exist which are believed by the Emergency Director to fall under the ECL description for a General Emergency.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 81 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 82 of 132 HS1 ECL: Site Area Emergency Initiating Condition: HOSTILE ACTION within the PROTECTED AREA.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

A HOSTILE ACTION is occurring or has occurred within the PROTECTED AREA as reported by the Security Team Leader Basis:

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

PROTECTED AREA - An area, located within the Site Exclusion Area Boundary, encompassed by physical barriers and to which access is controlled per 10 CFR 73.55. The SNC Power Block Protected Area and the ISFSI Protected Area are two Protected Areas located within the Site Owner Controlled Area.

This IC addresses the occurrence of a HOSTILE ACTION within the PROTECTED AREA. This event will require rapid response and assistance due to the possibility for damage to plant equipment.

Timely and accurate communications between Security Team Leader and the Main Control Room is essential for proper classification of a security-related event.

Security plans and terminology are based on the guidance provided by NEI 03-12, Template for the Security Plan, Training and Qualification Plan, Safeguards Contingency Plan [and Independent Spent Fuel Storage Installation Security Program].

As time and conditions allow, these events require a heightened state of readiness by the plant staff and implementation of onsite protective measures (e.g., evacuation, dispersal or sheltering). The Site Area Emergency declaration will mobilize Offsite Response Organization (ORO) resources and have them available to develop and implement public protective actions in the unlikely event that the attack is successful in impairing multiple safety functions.

This IC does not apply to incidents that are accidental events, acts of civil disobedience, or otherwise are not a HOSTILE ACTION perpetrated by a HOSTILE FORCE. Examples include the crash of a small aircraft, shots from hunters, physical disputes between employees, etc.

Reporting of these types of events is adequately addressed by other EALs, or the requirements of 10 CFR 73.71 or 10 CFR 50.72.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 82 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 83 of 132 Emergency plans and implementing procedures are public documents; therefore, EALs should not incorporate Security-sensitive information. This includes information that may be advantageous to a potential adversary, such as the particulars concerning a specific threat or threat location. Security-sensitive information should be contained in non-public documents such as the VEGP Security Plan.

Escalation of the ECL would be based on ICs in Recognition Categories R, H, F and C.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 83 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 84 of 132 HS6 ECL: Site Area Emergency Initiating Condition: Inability to control a key safety function from outside the Control Room.

Operating Mode Applicability: All Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

An event has resulted in plant control being transferred from the Main Control Room to the Remote Shutdown Workstation AND Control of any of the following key safety functions is not reestablished within 60 min.

(Note 1):

Reactivity control Core cooling RCS heat removal Basis:

If temporary evacuation of the Main Control Room is required because of some abnormal Main Control Room condition, the operators can establish and maintain safe shutdown conditions for the plant from outside the Main Control Room through the use of controls and monitoring located at the remote shutdown workstation.

This IC addresses an evacuation of the Main Control Room that results in transfer of plant control to alternate locations, and the control of a key safety function cannot be reestablished in a timely manner. The failure to gain control of a key safety function following a transfer of plant control to alternate locations is a precursor to a challenge to one or more fission product barriers within a relatively short period of time.

The determination of whether or not control is established at the remote safe shutdown location(s) is based on Emergency Director judgment. The Emergency Director is expected to make a reasonable, informed judgment within 60 minutes whether or not the operating staff has control of key safety functions from the Remote Shutdown Room/Workstation.

Escalation of the ECL would be via IC FG1 or CG1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 84 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 85 of 132 HS7 ECL: Site Area Emergency Initiating Condition: Other conditions exist which in the judgment of the Emergency Director warrant declaration of a Site Area Emergency.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

Other conditions exist which in the judgment of the Emergency Director indicate that events are in progress or have occurred which involve actual or likely major failures of plant functions needed for protection of the public OR HOSTILE ACTION that results in intentional damage or malicious acts, (1) toward site personnel or equipment that could lead to the likely failure of or, (2) that prevent effective access to equipment needed for the protection of the public.

Any releases are NOT expected to result in exposure levels which exceed EPA Protective Action Guideline exposure levels beyond the Site BoundarySITE BOUNDARY.

Basis:

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

SITE BOUNDARY - The boundary of a reactor site beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.

This EAL addresses unanticipated conditions not addressed explicitly elsewhere but that warrant declaration of an emergency because conditions exist which are believed by the Emergency Director to fall under the ECL description for Site Area Emergency.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 85 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 86 of 132 HA1 ECL: Alert Initiating Condition: HOSTILE ACTION within the OWNER CONTROLLED AREA or airborne attack threat within 30 minutes.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2)

(1)

A HOSTILE ACTION is occurring or has occurred within the OWNER CONTROLLED AREA as reported by Security Team Leader.

(2)

A validated notification from NRC of an aircraft attack threat within 30 minutes of the site.

Basis:

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

OWNER CONTROLLED AREA -

The area owned by the licensee and located within the confines of the SITE BOUNDARY.

This IC addresses the occurrence of a HOSTILE ACTION within the OWNER CONTROLLED AREA or notification of an aircraft attack threat. This event will require rapid response and assistance due to the possibility of the attack progressing to the PROTECTED AREA or the need to prepare the plant and staff for a potential aircraft impact.

Timely and accurate communications between the Security Team Leader and the Main Control Room is essential for proper classification of a security-related event.

Security plans and terminology are based on the guidance provided by NEI 03-12, Template for the Security Plan, Training and Qualification Plan, Safeguards Contingency Plan [and Independent Spent Fuel Storage Installation Security Program].

As time and conditions allow, these events require a heightened state of readiness by the plant staff and implementation of onsite protective measures (e.g., evacuation, dispersal, or sheltering). The Alert declaration will also heighten the awareness of Offsite Response Organizations (OROs), allowing them to be better prepared should it be necessary to consider further actions.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 86 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 87 of 132 This IC does not apply to incidents that are accidental events, acts of civil disobedience, or otherwise are not a HOSTILE ACTION perpetrated by a HOSTILE FORCE. Examples include the crash of a small aircraft, shots from hunters, physical disputes between employees, etc.

Reporting of these types of events is adequately addressed by other EALs, or the requirements of 10 CFR 73.71 or 10 CFR 50.72.

EAL (1)

The first threshold is applicable for any HOSTILE ACTION occurring, or that has occurred, in the OWNER CONTROLLED AREA.

EAL (2)

The second threshold addresses the threat from the impact of an aircraft on the plant, and the anticipated arrival time is within 30 minutes. The intent of this EAL is to ensure that threat-related notifications are made in a timely manner so that plant personnel and OROs are in a heightened state of readiness. This EAL is met when the threat-related information has been validated in accordance with 3(4)-AOP-904 Security Events.

The NRC Headquarters Operations Officer (HOO) will communicate to the licensee if the threat involves an aircraft. The status and size of the plane may be provided by NORAD through the NRC.

In some cases, it may not be readily apparent if an aircraft impact within the OWNER CONTROLLED AREA was intentional (i.e., a HOSTILE ACTION). It is expected, although not certain, that notification by an appropriate Federal agency to the site would clarify this point. In this case, the appropriate federal agency is intended to be NRC, NORAD, FBI, FAA or Department of Homeland Security (DHS). The emergency declaration, including one based on other ICs/EALs, should not be unduly delayed while awaiting notification by a Federal agency.

Emergency plans and implementing procedures are public documents; therefore, EALs should not incorporate Security-sensitive information. This includes information that may be advantageous to a potential adversary, such as the particulars concerning a specific threat or threat location. Security-sensitive information should be contained in non-public documents such as the Security Plan.

Escalation of the EAL would be via IC HS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 87 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 88 of 132 HA5 ECL: Alert Initiating Condition: Gaseous release IMPEDING access to equipment necessary for normal plant operations, cooldown or shutdown.

Operating Mode Applicability: All Emergency Action Levels: (1)

Note 5: If the equipment in the listed room or area was already inoperable or out-of-service before the event occurred, then no emergency classification is warranted.

(1)

Release of a toxic, corrosive, asphyxiant or flammable gas into any Table H-1 area/room AND Entry into the area is prohibited or IMPEDED (Note 5)

Table H-1 Safe Operation & Shutdown Areas/Rooms Building Room Number Room/Area Name Applicable Mode Auxiliary 12152 Primary Sample Room 3

12252 Rad Chem Lab 3

12321 Non-1E Equipment /

Penetration Room 4

12305 Division D I&C Penetration Room 4

12304 Division B I&C Penetration Room 4

12561 CCS Valve Room 4

Annex 40503 Lower South Air Handling Equipment 4

Containment 11209 CVS Room 4

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 88 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 89 of 132 Basis:

IMPEDE(D) - Personnel access to a room or area is hindered to an extent that extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g.,

requiring use of protective equipment, such as SCBAs, that is not routinely employed).

The Table H-1 safe operation and shutdown areas/rooms (with entry-related mode applicability) are those plant areas that contain equipment which require a manual/local action as specified in general operating procedures (and procedures referenced by them) used for normal plant operation, cooldown and shutdown. The list specifies the plant operating modes during which entry would be required for each area and thus specifying when a loss of access or IMPEDED access is applicable to this EAL.

Plant areas where actions of a contingent or emergency nature might be needed to be performed. (e.g., an action to address an off-normal or emergency condition such as emergency repairs, corrective measures or emergency operations) were not considered for inclusion.

Additionally, areas for which entry is required solely to perform actions of an administrative or record keeping nature (e.g., normal rounds or routine inspections) were not considered for inclusion.

If the equipment in the listed room or area was already inoperable, or out-of-service, before the event occurred, then no emergency should be declared since the event will have no adverse impact beyond that already allowed by Technical Specifications at the time of the event.

This IC addresses an event involving a release of a hazardous gas that precludes or IMPEDES access to equipment necessary to maintain normal plant operation, or required for a normal plant cooldown and shutdown. This condition represents an actual or potential substantial degradation of the level of safety of the plant.

An Alert declaration is warranted if entry into the affected room/area is, or may be, procedurally required during the plant operating mode in effect at the time of the gaseous release. The emergency classification is not contingent upon whether entry is actually necessary at the time of the release.

Evaluation of the IC and EAL do not require atmospheric sampling; it only requires the Emergency Directors judgment that the gas concentration in the affected room/area is sufficient to preclude or significantly IMPEDE procedurally required access. This judgment may be based on a variety of factors including an existing job hazard analysis, report of ill effects on personnel, advice from a subject matter expert or operating experience with the same or similar hazards.

Access should be considered as IMPEDED if extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g., requiring use of protective equipment, such as SCBAs, that is not routinely employed).

An emergency declaration is not warranted if any of the following conditions apply:

The plant is in an operating mode different than the mode specified for the affected room/area (i.e., entry is not required during the operating mode in effect at the time of the gaseous release). For example, the plant is in Mode 1 when the gaseous release occurs, and the procedures used for normal operation, cooldown and shutdown do not require entry into the affected room until Mode 4.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 89 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 90 of 132 The gas release is a planned activity that includes compensatory measures which address the temporary inaccessibility of a room or area (e.g., fire suppression system testing).

The action for which room/area entry is required is of an administrative or record keeping nature (e.g., normal rounds or routine inspections).

The access control measures are of a conservative or precautionary nature, and would not actually prevent or IMPEDE a required action.

If the equipment in the listed room or area was already inoperable, or out-of-service, before the event occurred, then no emergency should be declared since the event will have no adverse impact beyond that already allowed by Technical Specifications at the time of the event.

An asphyxiant is a gas capable of reducing the level of oxygen in the body to dangerous levels.

Most commonly, asphyxiants work by merely displacing air in an enclosed environment. This reduces the concentration of oxygen below the normal level of around 19%, which can lead to breathing difficulties, unconsciousness or even death.

This EAL does not apply to firefighting activities that automatically or manually activate a fire suppression system in an area.

Escalation of the ECL would be via Recognition Category R, C or F ICs.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 90 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 91 of 132 HA6 ECL: Alert Initiating Condition: Control Room evacuation resulting in transfer of plant control to alternate locations.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

An event has resulted in plant control being transferred from the Main Control Room to the Remote Shutdown Workstation.

Basis:

This IC addresses an evacuation of the Main Control Room that results in transfer of plant control to alternate locations outside the Main Control Room. The loss of the ability to control the plant from the Main Control Room is considered to be a potential substantial degradation in the level of plant safety.

Following a Main Control Room evacuation, control of the plant will be transferred to alternate shutdown locations. The necessity to control a plant shutdown from outside the Main Control Room, in addition to responding to the event that required the evacuation of the Main Control Room, will present challenges to PLANT OPERATORS and other on-shift personnel. Activation of the ERO and emergency response facilities will assist in responding to these challenges.

Escalation of the ECL would be via IC HS6.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 91 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 92 of 132 HA7 ECL: Alert Initiating Condition: Other conditions exist which in the judgment of the Emergency Director warrant declaration of an Alert.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

Other conditions exist which, in the judgment of the Emergency Director, indicate that events are in progress or have occurred which involve an actual or potential substantial degradation of the level of safety of the plant OR a security event that involves probable life-threatening risk to site personnel or damage to site equipment because of HOSTILE ACTION.

Any releases are expected to be limited to small fractions of the EPA Protective Action Guideline exposure levels.

Basis:

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

This IC addresses unanticipated conditions not addressed explicitly elsewhere but that warrant declaration of an emergency because conditions exist which are believed by the Emergency Director to fall under the ECL description for an Alert.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 92 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 93 of 132 HU1 ECL: Notification of Unusual Event Initiating Condition: Confirmed SECURITY CONDITION or threat.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3)

(1)

A SECURITY CONDITION that does not involve a HOSTILE ACTION as reported by Security Team Leader.

(2)

Notification of a credible security threat directed at the site.

(3)

A validated notification from the NRC providing information of an aircraft threat.

Basis:

SECURITY CONDITION - Any security event as listed in the approved security contingency plan that constitutes a threat/compromise to site security, threat/risk to site personnel, or a potential degradation to the level of safety of the plant. A security condition does not involve a HOSTILE ACTION.

HOSTILE ACTION - An act toward VEGP or its personnel that includes the use of violent force to destroy equipment, take HOSTAGES, and/or intimidate the licensee to achieve an end. This includes attack by air, land, or water using guns, explosives, PROJECTILES, vehicles, or other devices used to deliver destructive force. Other acts that satisfy the overall intent may be included. Hostile action should not be construed to include acts of civil disobedience or felonious acts that are not part of a concerted attack on VEGP. Non-terrorism-based EALs should be used to address such activities (i.e., this may include violent acts between individuals in the OWNER CONTROLLED AREA).

If the Security Team Leader determines that a threat notification is credible, the Security Team Leader will notify the Shift Manager that a Credible Threat condition exists for VEGP.

Generally, VEGP procedures address standard practices for determining credibility. The three main criteria for determining credibility are: technical feasibility, operational feasibility, and resolve. For VEGP, a validated notification delivered by the NRC, NORAD, FBI, FAA, or Department of Homeland Security (DHS) or similar agency is treated as credible.

This IC addresses events that pose a threat to plant personnel or safety system equipment and thus represent a potential degradation in the level of plant safety. Security events which do not meet one of these EALs are adequately addressed by the requirements of 10 CFR 73.71 or 10 CFR 50.72. Security events assessed as HOSTILE ACTIONS are classifiable under ICs HA1, and HS1.

Timely and accurate communications between Security Shift Supervision and the Main Control Room is essential for proper classification of a security-related event.

Classification of these events will initiate appropriate threat-related notifications to plant personnel and Offsite Response Organizations.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 93 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 94 of 132 Security plans and terminology are based on the guidance provided by NEI 03-12, Template for the Security Plan, Training and Qualification Plan, Safeguards Contingency Plan [and Independent Spent Fuel Storage Installation Security Program].

EAL (1)

The first threshold references the Security Team Leader because these are the individuals trained to confirm that a security event is occurring or has occurred. Training on security event confirmation and classification is controlled due to the nature of Safeguards and 10 CFR 2.390 information.

EAL (2)

The second threshold addresses the receipt of a credible security threat. The credibility of the threat is assessed in accordance with the VEGP Security Plan.

EAL (3)

The third threshold addresses the threat from the impact of an aircraft on the plant. The NRC Headquarters Operations Officer (HOO) will communicate to the licensee if the threat involves an aircraft. The status and size of the plane may also be provided by NORAD through the NRC.

Validation of the threat is performed in accordance with the VEGP Security Plan.

Emergency plans and implementing procedures are public documents; therefore, EALs should not incorporate Security-sensitive information. This includes information that may be advantageous to a potential adversary, such as the particulars concerning a specific threat or threat location. Security-sensitive information should be contained in non-public documents such as the Security Plan.

Escalation of the ECL would be via IC HA1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 94 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 95 of 132 HU2 ECL: Notification of Unusual Event Initiating Condition: Seismic event greater than OBE levels.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

Seismic event greater than Operating Basis Earthquake (OBE) as indicated by VALID SJS-JS-01-ALM2 (OBE Exceedance) alarm.

Basis:

VALID - An indication, report, or condition, is considered to be valid when it is verified by (1) an instrument channel check, or (2) indications on related or redundant indicators, or (3) by direct observation by plant personnel, such that doubt related to the indicators operability, the conditions existence, or the reports accuracy is removed. Implicit in this definition is the need for timely assessment.

This IC/EAL addresses a seismic event that results in accelerations at the plant site greater than the equivalent of an Operating Basis Earthquake (OBE). For the AP1000, the OBE for shutdown equivalent is defined to be 1/3 the SSE (0.30g) ground acceleration, or 0.10 g in either the horizontal or vertical plane. Earthquakes of this magnitude should be readily felt by onsite personnel and recognized as a seismic event, also triggering the Seismic Monitoring System (SJS) recorders and the SJS-JS-01-ALM2 - OBE Exceedance alarm.

AP1000 instrumentation used to indicate a seismic event greater than the OBE includes four triaxial acceleration sensor units attached to a time-history analyzer recording and playback system. When ground acceleration is sensed above the initiation setpoint, initially set at 0.01 g, the system initiates recording, and provides alarms in the Main Control Room. Additionally, an alarm (SJS-JS-01-ALM2 - OBE Exceedance) is generated in the Main Control Room if an OBE (0.10 g) is detected. If the Seismic Monitoring System (SJS) is functional, SJS-JS-01-ALM2 provides clear indication when the EAL threshold has been exceeded.

If the SJS or its associated alarms are non-functional, then the Shift Manager or Emergency Director should seek external confirmation of the seismic event through an external source such as the USGS or internet news service if a seismic event is felt in the MCR. The verification action must not preclude a timely emergency declaration. The USGS, National Earthquake Information Center (NEIC) can confirm that an earthquake has occurred in the area of the plant.

Alternatively, near real-time seismic activity can be accessed via the NEIC website.

The NEIC can be contacted by going to the USGS NEIC website:

http://earthquake.usgs.gov/eqcenter/

or by calling (303) 273-8500 (normal hours), or (303) 273-8428 (off normal hours). Select option

  1. 1 and then option #2 and inform the analyst you wish to confirm recent seismic activity in the vicinity of Plant Vogtle. The following VEGP coordinates: 33 deg. 08 min. 30 sec. north latitude, 81 deg. 45 min. 44 sec. west longitude may be provided to gain more localized readings on the earthquake. Alternatively, near real-time seismic activity can be accessed via the NEIC website.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 95 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 96 of 132 An earthquake greater than the equivalent of an OBE but less than a Safe Shutdown Earthquake (SSE) should have no significant impact on safety-related systems, structures and components; however, some time may be required for the plant staff to ascertain the actual post-event condition of the plant (e.g., performs walk-downs and post-event inspections). Given the time necessary to perform walk-downs and inspections, and fully understand any impacts, this event represents a potential degradation of the level of safety of the plant.

Depending upon the plant mode at the time of the event, escalation of the emergency classification level would be via IC CA7 or SA8.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 96 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 97 of 132 HU3 ECL: Notification of Unusual Event Initiating Condition: Hazardous event.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3 or 4)

Note 8: This EAL does not apply to routine traffic impediments such as fog, snow, ice, or vehicle breakdowns or accidents.

(1)

A tornado strike within the PROTECTED AREA.

(2)

Internal room or area FLOODING of a magnitude sufficient to require manual or automatic electrical isolation of a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode.

(3)

Movement of personnel within the PROTECTED AREA is IMPEDED due to an offsite event involving hazardous materials (e.g., an offsite chemical spill or toxic gas release).

(4)

A hazardous event that results in onsite conditions sufficient to prohibit the plant staff from accessing the site via personal vehicles (Note 8).

Basis:

FLOODING - A condition where water is entering a room or area faster than installed equipment is capable of removal, resulting in a rise of water level within the room or area.

IMPEDE(D) - Personnel access to a room or area is hindered to an extent that extraordinary measures are necessary to facilitate entry of personnel into the affected room/area (e.g., requiring use of protective equipment, such as SCBAs, that is not routinely employed).

PROTECTED AREA - An area, located within the Site Exclusion Area Boundary, encompassed by physical barriers and to which access is controlled per 10 CFR 73.55. The SNC Power Block Protected Area and the ISFSI Protected Area are two Protected Areas located within the Site Owner Controlled Area.

NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN - Safety-related Safe Shutdown systems are defined in UFSAR Table 7.4-1, which include PMS, PXS, PCS, IDS, Containment Isolation Valves, and control rods. Safe Cooldown additionally requires RCS, RNS and associated support SSCs (eg. the applicable portions of CCS, SWS, ECS, EDS and RNS room cooling needed to support RNS) because the RCS is not capable of being cooled to MODE 5 using only safety systems. FWS/SGS are NOT required to support Safe Cooldown because PRHR is capable of cooling the plant to RNS cut-in conditions.

This IC addresses hazardous events that are considered to represent a potential degradation of the level of safety of the plant.

EAL (1)

EAL HU3 EAL 1 addresses a tornado striking (touching down) within the PROTECTED AREA.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 97 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 98 of 132 EAL (2)

Internal FLOODING may be caused by events such as component failures, equipment misalignment, or outage activity mishaps.

This IC addresses hazardous events that are considered to represent a potential degradation of the level of safety of the plant.

This EAL addresses FLOODING of a building room or area that results in operators isolating power to a system component NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN due to water level or other wetting concerns. Classification is also required if the water level or related wetting causes an automatic isolation of a system component NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN from its power source (e.g., a breaker or relay trip). To warrant classification, operability or functionality of the affected component must be required by Technical Specifications or the Technical Requirements Manual for the current operating mode.

EAL (3)

As used here the term offsite is meant to be areas external to the VEGP PROTECTED AREA.

NMP-EN-703-001 Implementation of SPCC Plan provides additional information on hazardous substances and spills.

This IC addresses hazardous events that are considered to represent a potential degradation of the level of safety of the plant.

This EAL addresses a hazardous materials event originating at an offsite location and of sufficient magnitude to IMPEDE the movement of personnel within the PROTECTED AREA.

EAL (4)

This EAL addresses a hazardous event that causes an on-site impediment to vehicle movement and significant enough to prohibit the plant staff from accessing the site using personal vehicles.

Examples of such an event include site FLOODING caused by a hurricane, heavy rains, up-river water releases, dam failure, etc., or an on-site train derailment blocking the access road.

This EAL is not intended apply to routine impediments such as fog, snow, ice, or vehicle breakdowns or accidents, but rather to more significant conditions such as the Hurricane Andrew strike on Turkey Point in 1992, the flooding around the Cooper Station during the Midwest floods of 1993, or the flooding around Ft. Calhoun Station in 2011.

Escalation of the ECL would be based on ICs in Recognition Categories R, F, S or C.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 98 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 99 of 132 HU4 ECL: Notification of Unusual Event Initiating Condition: FIRE potentially degrading the level of safety of the plant.

Operating Mode Applicability: All Emergency Action Levels: (1 or 2 or 3 or 4)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

A FIRE is not EXTINGUISHED within 15 min. of any of the following FIRE detection indications (Note 1):

Report from the field (i.e., visual observation)

Receipt of multiple (more than 1) fire alarms or indications Field verification of a single fire alarm AND The FIRE is located within any Table H-2 area Table H-2 Fire Areas Containment Building Shield Building Auxiliary Building (2) Receipt of a single fire alarm (i.e., no other indications of a FIRE)

AND The fire alarm is indicating a FIRE within any Table H-2 area AND The existence of a FIRE is not verified within 30 min. of alarm receipt (Note 1)

(3)

A FIRE within the plant PROTECTED AREA not EXTINGUISHED within 60 min. of the initial report, alarm, or indication (Note 1)

(4) A FIRE within the plant PROTECTED AREA that requires firefighting support by an offsite fire response agency to EXTINGUISH Basis:

EXTINGUISH(ED) - Cessation of combustion and production of heat and emission of light, as determined by the Incident Commander.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 99 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 100 of 132 FIRE - Combustion characterized by heat and light. Sources of smoke such as slipping drive belts or overheated electrical equipment do not constitute FIRES. Observation of flame is preferred but is not required if large quantities of smoke and heat are observed.

PROTECTED AREA - An area, located within the Site Exclusion Area Boundary, encompassed by physical barriers and to which access is controlled per 10 CFR 73.55. The SNC Power Block Protected Area and the ISFSI Protected Area are two Protected Areas located within the Site Owner Controlled Area.

This IC addresses the magnitude and extent of FIRES that may be indicative of a potential degradation of the level of safety of the plant.

EAL (1)

UFSAR Section 1.2.3 Plant Arrangement Description was used to identify areas (Table H-2) containing safety system equipment required for accident mitigation and safe shutdown of the plant.

For HU4 EAL 1 the intent of the 15-minute duration is to size the FIRE and to discriminate against small FIRES that are readily EXTINGUISHED (e.g., smoldering waste paper basket). In addition to alarms, other indications of a FIRE could be a drop in fire main pressure, automatic activation of a suppression system, etc.

Upon receipt, operators will take prompt actions to confirm the validity of fire alarms or indications. For EAL assessment purposes, the emergency declaration clock starts at the time that the initial multiple alarms or indications were received, field verification of a single alarm was received or report from the field was received, and not the time that a subsequent verification action was performed. Similarly, the fire duration clock runs concurrently with the emergency declaration clock.

Enhanced fire protection has been one of the goals of the AP1000 design. The following physical separation philosophy is used:

Outside Containment:

  • Within the nuclear island, redundant divisions of safety-related equipment outside containment are located in safety-related areas separated from each other and from other areas in the plant by fire barriers with a minimum fire resistance rating of 3-hours to provide that safe shutdown can be achieved. Since most safety-related mechanical equipment is located inside containment, this applies primarily to the protection and safety monitoring system and the Class 1E dc and UPS system.
  • Each safety-related area is provided with ventilation isolation provisions at the fire barrier boundaries to minimize the migration of smoke, hot gasses, or fire suppressant chemicals into other safety-related areas. Fiber-optic cables are used to provide communication between redundant protection and safety monitoring divisions.
  • Exceptions to the use of three-hour fire barriers outside containment are made only in cases where physical separation conflicts with other requirements or where the equipment is not clearly division oriented, such as the main control room, the remote shutdown room, the main steam tunnel, and the passive containment cooling system valve room.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 100 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 101 of 132 Inside Containment:

  • The containment is a single fire area. Separation by three-hour fire barriers inside containment is not practical due to issues of hydrogen venting, compartment pressure equalization, and during high-energy line breaks and for system functionality. To the extent practical, separation is provided between redundant safety-related equipment.
  • Separation between redundant safety-related equipment is accomplished by using existing structural walls. Where this is not possible, other methods are used, such as physical separation with no intervening combustibles.
  • To the extent practical, the containment is split into two different fire zones for the purpose of routing of protection and safety monitoring system cabling and electrical power cabling.

Divisions A and C cabling is routed below the operating deck, while Divisions B and D cabling is routed above the operating deck. Additional separation is provided by existing floors and walls and by the physical separation of cabling runs. Protection for the primary input sensors and the final actuation devices is accomplished by the physical separation of the various sensors and components using existing containment walls as barriers.

  • The in-containment fire area contains reduced combustible material due to the use of sealless reactor coolant pump motors that do not use oil lubrication and due to strict combustible material limitations.

EAL (2)

This EAL addresses receipt of a single fire alarm, and the existence of a FIRE is not verified (i.e., proved or disproved) within 30-minutes of the alarm. Upon receipt, operators will take prompt actions to confirm the validity of a single fire alarm. For EAL assessment purposes, the 30-minute clock starts at the time that the initial alarm was received, and not the time that a subsequent verification action was performed.

A single fire alarm, absent other indication(s) of a FIRE, may be indicative of equipment failure or a spurious activation, and not an actual FIRE. For this reason, additional time is allowed to verify the validity of the alarm. The 30-minute period is a reasonable amount of time to determine if an actual FIRE exists; however, after that time, and absent information to the contrary, it is assumed that an actual FIRE is in progress.

If an actual FIRE is verified by a report from the field, then HU4 EAL1 is immediately applicable, and the emergency must be declared if the FIRE is not extinguished within 15-minutes of the verification report. If the alarm is verified to be due to an equipment failure or a spurious activation, and this verification occurs within 30-minutes of the receipt of the alarm, then this EAL is not applicable and no emergency declaration is warranted.

Enhanced fire protection has been one of the goals of the AP1000 design. The following physical separation philosophy is used:

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 101 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 102 of 132 Outside Containment:

  • Within the nuclear island, redundant divisions of safety-related equipment outside containment are located in safety-related areas separated from each other and from other areas in the plant by fire barriers with a minimum fire resistance rating of 3-hours to provide that safe shutdown can be achieved. Since most safety-related mechanical equipment is located inside containment, this applies primarily to the protection and safety monitoring system and the Class 1E dc DC and UPS system.
  • Each safety-related area is provided with ventilation isolation provisions at the fire barrier boundaries to minimize the migration of smoke, hot gasses, or fire suppressant chemicals into other safety-related areas. Fiber-optic cables are used to provide communication between redundant protection and safety monitoring divisions.
  • Exceptions to the use of three-hour fire barriers outside containment are made only in cases where physical separation conflicts with other requirements or where the equipment is not clearly division oriented, such as the main control room, the remote shutdown room, the main steam tunnel, and the passive containment cooling system valve room.

Inside Containment:

  • The containment is a single fire area. Separation by three-hour fire barriers inside containment is not practical due to issues of hydrogen venting, compartment pressure equalization, and during high-energy line breaks and for system functionality. To the extent practical, separation is provided between redundant safety-related equipment.
  • Separation between redundant safety-related equipment is accomplished by using existing structural walls. Where this is not possible, other methods are used, such as physical separation with no intervening combustibles.
  • To the extent practical, the containment is split into two different fire zones for the purpose of routing of protection and safety monitoring system cabling and electrical power cabling.

Divisions A and C cabling is routed below the operating deck, while Divisions B and D cabling is routed above the operating deck. Additional separation is provided by existing floors and walls and by the physical separation of cabling runs. Protection for the primary input sensors and the final actuation devices is accomplished by the physical separation of the various sensors and components using existing containment walls as barriers.

  • The in-containment fire area contains reduced combustible material due to the use of sealless reactor coolant pump motors that do not use oil lubrication and due to strict combustible material limitations.

EAL (3)

This EAL separates itself from HU4 EAL 1 and EAL 2 by evaluating a fire anywhere within the PROTECTED AREA (not restricted to Table H-2 Areas), which may degrade the level of safety of the plant.

In addition to a FIRE addressed by HU4 EAL 1 or EAL 2, a FIRE within the plant PROTECTED AREA not extinguished within 60-minutes may also potentially degrade the level of plant safety.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 102 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 103 of 132 EAL (4)

If a FIRE within the plant PROTECTED AREA is of sufficient size to require a response by an offsite firefighting agency (e.g., a local town Fire Department), then the level of plant safety is potentially degraded. The dispatch of an offsite firefighting agency to the site requires an emergency declaration only if it is needed to actively support firefighting efforts because the FIRE is beyond the capability of the Fire Brigade to extinguish. Declaration is not necessary if the agency resources are placed on stand-by, or supporting post-extinguishment recovery or investigation actions.

Depending upon the plant mode at the time of the event, escalation of the ECL would be via IC CA7 or SA8.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 103 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 104 of 132 HU7 ECL: Notification of Unusual Event Initiating Condition: Other conditions exist which in the judgment of the Emergency Director warrant declaration of a NOUE.

Operating Mode Applicability: All Emergency Action Levels: (1)

(1)

Other conditions exist which in the judgment of the Emergency Director indicate that events are in progress or have occurred which indicate a potential degradation of the level of safety of the plant OR indicate a security threat to facility protection has been initiated.

No releases of radioactive material requiring offsite response or monitoring are expected unless further degradation of systems NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN occurs.

Basis:

NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN - Safety-related Safe Shutdown systems are defined in UFSAR Table 7.4-1, which include PMS, PXS, PCS, IDS, Containment Isolation Valves, and control rods. Safe Cooldown additionally requires RCS, RNS and associated support SSCs (eg. the applicable portions of CCS, SWS, ECS, EDS and RNS room cooling needed to support RNS) because the RCS is not capable of being cooled to MODE 5 using only safety systems. FWS/SGS are NOT required to support Safe Cooldown because PRHR is capable of cooling the plant to RNS cut-in conditions.

This IC addresses unanticipated conditions not addressed explicitly elsewhere but that warrant declaration of an emergency because conditions exist which are believed by the Emergency Director to fall under the ECL description for an Unusual Event.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 104 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 105 of 132 4.14 SYSTEM MALFUNCTION ICs/EALs GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT SS1 Loss of all required Class 1E DC power or Class 1E UPS bus power for 15 minutes or longer.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SA1 Loss of all capability to charge at least one Class 1E 24-hr.

DC battery for 60 minutes or longer.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SU1 Loss of all capability to charge at least one Class 1E 24-hr.

DC battery for 30 minutes or longer Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SA2 UNPLANNED full loss of monitoring and control functions for 15 minutes or longer.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SU2 UNPLANNED partial loss of monitoring and control functions for 30 minutes or longer.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SU3 Reactor coolant activity greater than Technical Specification allowable limits.

Op. Modes: Power Operation, Startup, Hot Standby ( 500 ºF)

SU4 RCS leakage for 15 minutes or longer.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SS5 Inability to shut down the reactor causing a challenge to core cooling or RCS heat removal.

Op. Modes: Power Operation, Startup SA5 Automatic or manual trip fails to shut down the reactor and subsequent manual actions taken at the control room workstations are not successful in shutting down the reactor.

Op. Modes: Power Operation, Startup SU5 Automatic or manual trip fails to shut down the reactor.

Op. Modes: Power Operation, Startup SU6 Loss of all onsite or offsite communications capabilities.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 105 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 106 of 132 GENERAL EMERGENCY SITE AREA EMERGENCY ALERT UNUSUAL EVENT SU7 Failure to isolate containment or loss of containment pressure control.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown SA8 Hazardous event affecting a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode.

Op. Modes: Power Operation, Startup, Hot Standby, Safe Shutdown ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 106 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 107 of 132 SS1 ECL: Site Area Emergency Initiating Condition: Loss of all required Class 1E DC power or Class 1E UPS bus power for 15 minutes or longer.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1 or 2)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded,or will likely be exceeded.

(1)

Indicated voltage < 210 VDC on all required Class 1E 24-hr. DC buses (IDSA/B/C/D-DS-1) for 15 min. (Note 1)

(2)

Loss of power to all 24-hr. Class 1E UPS buses (IDSA/B/C/D-EA-1) for 15 min. (Note 1)

Basis:

Load shedding strategies implemented in AOP-302 are planned actions to cope with an extended loss of AC power and therefore do not warrant classification under this IC, provided operators maintain the ability to re-energize the class 1E bussesbuses when required.

EAL (1)

Minimum Class 1E 24-hr. DC bus voltage of 210 VDC is based on a minimum of 1.75 V per battery cell.

This EAL is the hot condition equivalent of the cold condition Loss of Class 1E DC or UPS Power IC CA4 EAL 1.

Loss of all 24-hr. DC power compromises ability to monitor and control plant safety functions.

Prolonged loss of all DC power will cause core uncovering and loss of containment integrity when there is significant decay heat and sensible heat in the reactor system.

This IC/EAL addresses a total loss of Class 1E 24-hr. DC power that compromises the performance of all safety systems requiring electric power including those necessary for emergency core cooling, containment heat removal/pressure control, spent fuel heat removal and the ultimate heat sink. In addition, fission product barrier monitoring capabilities may be degraded under these conditions. This IC represents a condition that involves actual or likely major failures of plant functions needed for the protection of the public.

210 VDC is the minimum bus voltage necessary for the operation of safety-related instrumentation and controls. This voltage value incorporates a margin significantly longer than the allowed 15 minutes of operation before the onset of inability to operate those loads.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 107 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 108 of 132 EAL (2) 24-hr. Class 1E UPS buses IDSA-EA-1, IDSB-EA-1, IDSC-EA-1, and IDSD-EA-1 provide instrument and control power to Class 1E SAFETY RELATED equipment and systems.

This EAL is the hot condition equivalent of the cold condition Loss of Class 1E DC or UPS Power IC CA4 EAL 2.

Loss of all 24-hr. UPS power compromises ability to monitor and control plant safety functions.

Prolonged loss of all UPS power will cause core uncovering and loss of containment integrity when there is significant decay heat and sensible heat in the reactor system.

This threshold addresses an event that results in de-energizing all UPS bussesbuses. This condition would result in degraded capability to monitor and control the unit from the Main Control Room resulting in the need for additional personnel to manage the event.

Fifteen minutes was selected as a threshold to exclude transient or momentary power losses.

Escalation of the emergency classification level would be via ICs RG1 or FG1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 108 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 109 of 132 SS5 ECL: Site Area Emergency Initiating Condition: Inability to shut down the reactor causing a challenge to core cooling or RCS heat removal.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup Emergency Action Levels: (1)

(1)

An automatic or manual trip did not reduce reactor power < 5%

AND All subsequent operator actions to manually shut down the reactor are not successful as indicated by reactor power 5%

AND EITHER of the following conditions exist:

CSFST Core Cooling-RED path conditions met CSFST Heat Sink-RED path conditions met Basis:

This EAL addresses the following:

Any automatic or manual reactor trip signal followed by a manual trip that fails to shut down the reactor to an extent the reactor is producing energy in excess of the heat load for which the safety systems were designed ( 5%) (IC SA5 EAL 1), and Indications that either core cooling is extremely challenged (CSFST Core Cooling-RED path) or heat removal is extremely challenged (CSFST Heat Sink-Red path).

At the Site Area Emergency classification level additional capabilities away from the Main Control Room workstations may be considered.

Indication that core cooling is extremely challenged is manifested by entry to Critical Safety Function Status Tree (CSFST) Core Cooling-RED path. Indication that heat removal is extremely challenged is manifested by entry to CSFST Heat Sink-RED path.

This IC/EAL addresses a failure of the RTS to initiate or complete an automatic or manual reactor trip that results in a reactor shutdown, all subsequent operator actions to manually shut down the reactor are unsuccessful, and continued power generation is challenging the capability to adequately remove heat from the core and/or the RCS. This condition will lead to fuel damage if additional mitigation actions are unsuccessful and thus warrants the declaration of a Site Area Emergency.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 109 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 110 of 132 In some instances, the emergency classification resulting from this IC/EAL may be higher than that resulting from an assessment of the plant responses and symptoms against the Recognition Category F ICs/EALs. This is appropriate in that the Recognition Category F ICs/EALs do not address the additional threat posed by a failure to shut down the reactor. The inclusion of this IC and EAL ensures the timely declaration of a Site Area Emergency in response to prolonged failure to shutdown the reactor.

A reactor shutdown is determined in accordance with applicable Emergency Operating Procedure criteria.

Escalation of the emergency classification level would be via IC RG1 or FG1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 110 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 111 of 132 SA1 ECL: Alert Initiating Condition: Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 60 minutes or longer.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1)

Note 1:

The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 60 min.

(Note 1)

Basis:

Motor control centers (ECS-EC-121/221) from non-Class 1E bussesbuses ECS-ES-1 and ECS-ES-2 power the battery chargers for the Class 1E safety-related batteries. If these bussesbuses are deenergized, the safety-related batteries cannot be charged. As used in this EAL the term capability means at least one offsite or onsite standby AC power source is either currently powering a non-Class 1E bus (ECS-ES-1 or ECS-ES-2) or is capable of energizing and powering a charger on at least one non-Class 1E bus (ECS-ES-1 or ECS-ES-2) within 60 min.

This IC/EAL and the associated threshold is intended to provide an escalation from IC SU1.

Prolonged de-energization of the bussesbuses that provide power to the Class 1E 24-hr battery chargers degrades the level of safety of the plant by rendering the plant more vulnerable to a complete loss of DC power even though no operator action is required for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

60 minutes was selected to allow power restoration procedures to be effective.

The Class 1E (safety-related) 24-hr DC system provides electrical power for Class 1E motor operated valves and vital control and monitoring instrumentation loads. The offsite AC power system normally supplies power for the unit in cold shutdown, refueling, and defueled conditions. Both the normal offsite and standby onsite AC power systems are non-Class 1E with no Technical Specification requirements. The Passive ALWRs also have standby diesel generators that are not safety-related. Storage batteries are the safety-related power source for Class 1E electric power. However, this non-Class 1E AC power is required to charge the safety-related DC batteries and maintain long-term safety-related DC bus voltage.

Escalation of the emergency classification level would be via IC SS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 111 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 112 of 132 SA2 ECL: Alert Initiating Condition: UNPLANNED full loss of monitoring and control functions for 15 minutes or longer.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

UNPLANNED full loss of indicating, monitoring, and control functions from all of the following for 15 min. (Note 1):

Protection and Monitoring System (PMS)

Plant Control System (PLS)

Diverse Actuation System (DAS)

Basis:

UNPLANNED-. A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

This EAL is the hot condition equivalent of cold condition IC CU6 EAL 1.

This IC/EAL recognizes the inability of the Main Control Room staff to monitor and control the plant from the Main Control Room due to loss of normal and safety indication and monitoring systems, and diverse indication and control systems that allow the operators to monitor and safely shutdown the plant. An Alert is considered to exist if the Main Control Room staff cannot monitor and control safety functions needed for protection of the public. The loss of ability to monitor or control key safety functions following a Main Control Room evacuation would be classified under HS6 EAL 1.

This IC/EAL recognizes the challenge to the Main Control Room staff to monitor and control the plant due to a complete loss of normal and safety indication and monitoring systems. The selection of 15 minutes was chosen to allow personnel sufficient time for restoration of required systems due to an inadvertent loss.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 112 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 113 of 132 Systems that provide monitoring and control capability include:

The Protection and Safety Monitoring System (PMS) provides the functions necessary to protect the plant during normal operations, to shutdown the plant, and to maintain the plant in a safe shutdown condition.

The Plant Control System (PLS) is a nonsafety-related system and includes the control functions that provide for the control of the nuclear process, conversion of nuclear energy into heat energy, and transport of the heat energy from the nuclear reactor to the main steam turbine.

The Diverse Actuation System (DAS) is a nonsafety-related system available to ensure monitoring and control capability as well as providing an alternative means of initiating a reactor trip and selected engineering safety features.

Escalation of the emergency classification level would be via ICs FS1 or IC RS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 113 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 114 of 132 SA5 ECL: Alert Initiating Condition: Automatic or manual trip fails to shut down the reactor and subsequent manual actions taken at the control room workstations are not successful in shutting down the reactor.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup Emergency Action Levels: (1)

Note 7: A manual action is any operator action, or set of actions, taken at the Main Control Room workstations which causes the control rods to be rapidly inserted into the core, and does not include manually driving in control rods or implementation of boron injection strategies.

(1)

An automatic or manual trip did not reduce reactor power < 5%

AND Subsequent manual actions taken at the Main Control Room workstations are not successful in reducing reactor power < 5% (Note 7)

Basis:

This EAL addresses any automatic or manual reactor trip signal that fails to shut down the reactor followed by a subsequent manual trip that fails to shut down the reactor to an extent the reactor is producing energy in excess of the heat load for which the safety systems were designed ( 5%).

Following a successful reactor trip, rapid insertion of the control rods occurs. Nuclear power promptly drops to a few percent of the original power level and then decays to a level some 8 decades less at a startup rate of about -1/3 DPM. The reactor power drop continues until reactor power reaches the point at which the influence of source neutrons on reactor power starts to be observable. A predictable post-trip response from an automatic reactor trip signal should therefore consist of a prompt drop in reactor power as sensed by the nuclear instrumentation and a negative startup rate as nuclear power drops into the source range.

This IC addresses a failure of the RTS to initiate or complete an automatic or manual reactor trip that results in a reactor shutdown, and subsequent operator manual actions taken at the Main Control Room workstations (DAS, both PDSP trip switches or de-energizing Rod Drive MGs) to shut down the reactor are also unsuccessful. This condition represents an actual or potential substantial degradation of the level of safety of the plant. An emergency declaration is required even if the reactor is subsequently shut down by an action taken away from the reactor control consoles since this event entails a significant failure of the RTS.

A manual action at the Main Control Room workstations is any operator action, or set of actions, which causes the control rods to be rapidly inserted into the core (e.g., initiating a manual reactor trip). This action includes the DAS, PDSP reactor trip switches and de-energizing Rod Drive MGs. This action does not include manually driving in control rods or implementation of boron injection strategies. If this action(s) is unsuccessful, operators would immediately pursue additional manual actions at locations away from the Main Control Room workstations (e.g.,

locally opening breakers). Actions taken at back-panels or other locations within the Control ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 114 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 115 of 132 Room (or any location outside the Main Control Room are not considered to be at the Main Control Room workstations).

The plant response to the failure of an automatic or manual reactor trip will vary based upon several factors including the reactor power level prior to the event, availability of the condenser, performance of mitigation equipment and actions, other concurrent plant conditions, etc. If the failure to shut down the reactor is prolonged enough to cause a challenge to the core cooling or RCS heat removal safety functions, the emergency classification level will escalate to a Site Area Emergency via IC SS5. Depending upon plant responses and symptoms, escalation is also possible via IC FS1. Absent the plant conditions needed to meet either IC SS5 or FS1, an Alert declaration is appropriate for this event.

It is recognized that plant responses or symptoms may also require an Alert declaration in accordance with the Recognition Category F ICs; however, this IC and EAL are included to ensure a timely emergency declaration.

A reactor shutdown is determined in accordance with applicable Emergency Operating Procedure criteria.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 115 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 116 of 132 SA8 ECL: Alert Initiating Condition: Hazardous event affecting a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1)

(1)

The occurrence of any Table S-2 hazardous event AND EITHER of the following:

Event damage has caused indications of degraded performance in at least one train of a system NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode The event has caused VISIBLE DAMAGE to a system component or structure NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN, for the current operating mode Table S-2 Hazardous Events Seismic event (earthquake)

Internal or external FLOODING event High winds or tornado strike FIRE EXPLOSION Other events with similar hazard characteristics as determined by the Shift Manager Basis:

EXPLOSION - A rapid, violent and catastrophic failure of a piece of equipment due to combustion, chemical reaction or overpressurization. A release of steam (from high energy lines or components) or an electrical component failure (caused by short circuits, grounding, arcing, etc.) should not automatically be considered an EXPLOSION. Such events require a post-event inspection to determine if the attributes of an EXPLOSION are present.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 116 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 117 of 132 FIRE - Combustion characterized by heat and light. Sources of smoke such as slipping drive belts or overheated electrical equipment do not constitute FIRES. Observation of flame is preferred but is not required if large quantities of smoke and heat are observed.

FLOODING - A condition where water is entering a room or area faster than installed equipment is capable of removal, resulting in a rise of water level within the room or area.

VISIBLE DAMAGE - Damage to a component or structure that is readily observable without measurements, testing, or analysis. The visual impact of the damage is sufficient to cause concern regarding the operability or reliability of the affected component or structure. Damage resulting from an equipment failure and limited to the failed component (i.e., the failure did not cause damage to a structure or any other equipment) is not visible damage. VISIBLE DAMAGE requires at least limited damage to a single SSC; the extent of damage or need to determine the loss of an entire train is not required. This eliminates the need to evaluate the extent of damage and determine the functionality of entire safety system, which would likely exceed 15 minutes.

The significance of seismic events are discussed under HU2 EAL.

Internal FLOODING may be caused by events such as component failures, equipment misalignment, or outage activity mishaps.

Seismic Category I structures are analyzed to withstand a sustained, design wind velocity of at least 145 mph (sustained).

UFSAR Section 1.2.3 Plant Arrangement Description to identify major plant structures containing functions and systems required for safe shutdown of the plant.

An EXPLOSION (including a steam line explosion) that degrades the performance of a safety system train or visibly damages a safety system component or structure would be classified under this EAL. The need to classify a steam line break not considered an explosion itself is considered in fission product barrier degradation monitoring (EAL Category F).

NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN - Safety-related Safe Shutdown systems are defined in UFSAR Table 7.4-1, which include PMS, PXS, PCS, IDS, Containment Isolation Valves, and control rods. Safe Cooldown additionally requires RCS, RNS and associated support SSCs (eg. the applicable portions of CCS, SWS, ECS, EDS and RNS room cooling needed to support RNS) because the RCS is not capable of being cooled to MODE 5 using only safety systems. FWS/SGS are NOT required to support Safe Cooldown because PRHR is capable of cooling the plant to RNS cut-in conditions.

This IC/EAL addresses a hazardous event that causes damage to a system, structure, or component NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN for the current operating mode. These would be evidenced by control indications of degraded system response or performance or represents a challenge to the FSAR design basis or prevents operators from taking required actions to place the reactor in a safe condition. This condition significantly reduces the margin to a loss or potential loss of a fission product barrier, and therefore represents an actual or potential substantial degradation of the level of safety of the plant.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 117 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 118 of 132 The first condition addresses damage to a system, or a structure containing system components NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN using indications that are readily available. The indications of degraded performance should be significant enough to cause concern regarding the operability or reliability of the system division.

The second condition addresses damage to a system, or a structure containing system components, NEEDED FOR SAFE COOLDOWN OR SAFE SHUTDOWN that is not readily apparent through indications alone. Operators will make this determination based on the totality of available event and damage report information. This is intended to be a brief assessment not requiring lengthy analysis or quantification of the damage.

Escalation of the emergency classification level would be via IC FS1 or RS1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 118 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 119 of 132 SU1 ECL: Notification of Unusual Event Initiating Condition Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 30 minutes or longer.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1) Loss of all capability to charge at least one Class 1E 24-hr. DC battery for 30 min. (Note

1)

Basis:

Motor control centers (ECS-EC-121/221) from non-Class 1E bussesbuses ECS-ES-1 and ECS-ES-2 power the battery chargers for the Class 1E safety-related batteries. If these bussesbuses are deenergized, the safety-related batteries cannot be charged. As used in this EAL the term capability means at least one offsite or onsite standby AC power source is either currently powering a non-Class 1E bus (ECS-ES-1 or ECS-ES-2) or is capable of energizing and powering a charger on at least one non-Class 1E bus (ECS-ES-1 or ECS-ES-2) within 30 min.

This hot condition EAL is equivalent to the cold condition loss of Class 1E DC or UPS power IC CU4 EAL 1.

The Class 1E 24-hr. (safety-related) DC system provides electrical power for safety-related and vital control and monitoring instrumentation loads. The offsite AC power system normally supplies power for the unit in cold shutdown, refueling, and defueled conditions. Both the normal offsite and standby onsite AC power systems are non-Class 1E with no Technical Specification requirements. All safety-related functions associated with the unit in cold shutdown and refueling are provided by the safety-related onsite Class 1E DC power systems including the 120V Vital AC power system supplied from the batteries powering the safety-related DC buses through inverters. The Passive ALWRs also have standby diesel generators that are not safety-related. Storage batteries are the safety-related power source for Class 1E electric power. However, this non-Class 1E AC power is required to charge the safety-related DC batteries and maintain long-term safety-related DC bus voltage.

Loss of Class 1E 24-hr. DC power potentially compromises all safety-related plant systems requiring electric power. The event can be classified as a Notice of Unusual Event, because the passive design affords additional and redundant means to remove heat passively or restore power to active components.

30 minutes was chosen to allow sufficient time for plant personnel to attempt to establish a viable offsite or diesel generator AC power supply to the plant-specific AC power buses required to charge one or more Class 1E 24-hr. DC batteries.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 119 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 120 of 132 Escalation of the emergency classification level would be via IC SA1 if at least one Class 1E battery cannot be charged within 60 min.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 120 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 121 of 132 SU2 ECL: Notification of Unusual Event Initiating Condition: UNPLANNED partial loss of monitoring and control functions for 30 minutes or longer.

Operating Mode Applicability:

1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

UNPLANNED partial loss of indicating, monitoring, and control functions from any of the following for 30 min. (Note 1):

Protection and Monitoring System (PMS)

Plant Control System (PLS)

Diverse Actuation System (DAS)

Basis:

UNPLANNED-A parameter change or an event that is not 1) the result of an intended evolution or 2) an expected plant response to a transient. The cause of the parameter change or event may be known or unknown.

This IC recognizes the difficulty associated with monitoring and controlling changing plant conditions without the use of a major portion of the control and indication systems under hot conditions.

The selection of 30 minutes was chosen to allow personnel sufficient time for restoration of required systems in the Main Control Room due to an inadvertent loss.

Systems that provide monitoring and control capability include:

The Protection and Safety Monitoring System (PMS) provides the functions necessary to protect the plant during normal operations, to shut down the plant, and to maintain the plant in a safe shutdown condition.

The Plant Control System (PLS) is a non-safety-related system and includes the control functions that provide for the control of the nuclear process, conversion of nuclear energy into heat energy, and transport of the heat energy from the nuclear reactor to the main steam turbine.

The Diverse Actuation System (DAS) is a non-safety-related system available to ensure monitoring and control capability as well as providing an alternative means of initiating a reactor trip and selected engineering safety features.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 121 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 122 of 132 SU3 ECL: Notification of Unusual Event Initiating Condition: Reactor coolant activity greater than Technical Specification allowable limits.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby ( 500 ºF)

Emergency Action Levels: (1 or 2)

(1)

Primary Sampling Liquid Radiation Monitor (PSS-RY050) high alarm (2)

Sample analysis indicates that a reactor coolant activity value > an allowable limit specified in Technical Specifications (TS 3.4.10)

Basis:

This IC/EAL addresses a reactor coolant activity value that exceeds an allowable limit specified in Technical Specifications. This condition is a precursor to a more significant event and represents a potential degradation of the level of safety of the plant.

Mode applicability has been limited to Modes 1, 2 and 3 ( 500 ºF) consistent with applicability of the coolant activity Technical Specification limits.

EAL (1)

The primary sampling system (PSS) liquid sample radiation monitor (PSS-RY050) measures and indicates the concentration of radioactive materials in the samples from the reactor coolant system. The liquid sample radiation monitor's primary function is to indicate elevated sample radiation levels following a design basis or severe accident. The monitor may be used to provide early indication of a significant increase in the radioactivity of the reactor coolant indicating a possible fuel cladding breach. When a predetermined setpoint is exceeded, the primary sampling system liquid sample radiation monitor isolates the sample flow by closing the outside containment isolation valve and initiates an alarm in the Main Control Room and locally to alert the Operator.

EAL (2)

The RCS specific activity LCO limits the allowable concentration of iodines and noble gases in the reactor coolant. The LCO limits are established to be consistent with a fuel defect level of 0.25 percent and to ensure that plant operation remains within the conditions assumed for shielding and Design Basis Accident (DBA) release analyses.

The LCO contains specific activity limits for both dose equivalent I-131 and dose equivalent XE-133. The allowable levels are intended to limit the doses due to postulated accidents to within the values calculated in the radiological consequences analyses.

Escalation of the emergency classification level would be via ICs FA1 or the Recognition Category R ICs.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 122 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 123 of 132 SU4 ECL: Notification of Unusual Event Initiating Condition: RCS leakage for 15 minutes or longer.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1 or 2 or 3)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

RCS unidentified or pressure boundary leakage > 10 gpm for 15 min.

(2)

RCS identified leakage > 25 gpm for 15 min.

(3)

Leakage from the RCS to a location outside containment > 25 gpm for 15 min.

(Note 1)

Basis:

The safety significance of RCS leakage varies widely depending on its source, rate, and duration. Therefore, detecting and monitoring RCS leakage into and external to the containment area is necessary. Quickly separating the identified leakage from the unidentified leakage is necessary to provide quantitative information to the Operators, allowing them to take corrective action should a leak occur that is detrimental to the safety of the facility and the public.

This IC/EALs addresses RCS leakage which may be a precursor to a more significant event. In this case, RCS leakage has been detected and operators, following applicable procedures, have been unable to promptly isolate the leak. This condition is considered to be a potential degradation of the level of safety of the plant.

The first and second EAL conditions are focused on a loss of mass from the RCS due to unidentified leakage, pressure boundary leakage, or identified leakage (as these leakage types are defined in the plant Technical Specifications).

The third EAL condition addresses a RCS mass loss not considered either unidentified or identified leakage caused by an UNISOLABLE leak through an interfacing system external to the containment. These EALs thus apply to leakage into the containment, (a secondary-side system (e.g., steam generator tube leakage) or a location outside of containment.

The leak rate values for each EAL were selected because they are usually observable with normal Main Control Room indications. Lesser values typically require time-consuming calculations to determine (e.g., a mass balance calculation). The first condition uses a lower value that reflects the greater significance of unidentified or pressure boundary leakage.

The release of mass from the RCS due to the as-designed/expected operation of a relief valve does not warrant an emergency classification. An emergency classification would be required if a mass loss is caused by a relief valve that is not functioning as designed/expected (e.g., a relief valve sticks open and the line flow cannot be isolated).

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 123 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 124 of 132 The 15-minute threshold duration allows sufficient time for prompt operator actions to isolate the leakage, if possible.

Escalation of the emergency classification level would be via ICs of Recognition Category R or F.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 124 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 125 of 132 SU5 ECL: Notification of Unusual Event Initiating Condition: Automatic or manual trip fails to shut down the reactor.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup Emergency Action Levels: (1 or 2)

Note 7: A manual action is any operator action, or set of actions, taken at the Main Control Room workstations which causes the control rods to be rapidly inserted into the core, and does not include manually driving in control rods or implementation of boron injection strategies.

(1)

An automatic trip did not reduce reactor power to < 5%

AND A subsequent automatic trip or manual action taken at the Main Control Room workstations is successful in reducing reactor power < 5% (Note 7)

(2)

A manual trip did not reduce reactor power to < 5%

AND A subsequent automatic trip or manual trip action taken at the Main Control Room workstations is successful in reducing reactor power < 5% (Note 7).

Basis:

Following a successful reactor trip, rapid insertion of the control rods occurs. Nuclear power promptly drops to a few percent of the original power level and then decays to a level some 8 decades less at a startup rate of about -1/3 DPM. The reactor power drop continues until reactor power reaches the point at which the influence of source neutrons on reactor power starts to be observable. A predictable post-trip response from an automatic reactor trip signal should therefore consist of a prompt drop in reactor power as sensed by the nuclear instrumentation and a negative startup rate as nuclear power drops into the source range.

A manual action at the Main Control Room workstations is any operator action, or set of actions, which causes the control rods to be rapidly inserted into the core (e.g., initiating a manual reactor trip). This action includes DAS, one or both PDSP reactor trip switches and de-energizing Rod Drive MGs. This action does not include manually driving in control rods or implementation of boron injection strategies. Actions taken at back-panels or other locations within the Main Control Room or any location outside the Main Control Room are not considered to be at the Main Control Room workstations.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 125 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 126 of 132 The plant response to the failure of an automatic or manual reactor trip will vary based upon several factors including the reactor power level prior to the event, availability of the condenser, performance of mitigation equipment and actions, other concurrent plant conditions, etc. If subsequent operator manual actions taken at the reactor control consoles are also unsuccessful in shutting down the reactor, then the emergency classification level will escalate to an Alert via IC SA5. Depending upon the plant response, escalation is also possible via IC FA1. Absent the plant conditions needed to meet either IC SA5 or FA1, an Notification of Unusual Event declaration is appropriate for this event.

A reactor shutdown is determined in accordance with applicable Emergency Operating Procedure criteria.

Should a reactor trip signal be generated as a result of plant work (e.g., RPS setpoint testing),

the following classification guidance should be applied.

If the signal causes a plant transient that should have included an automatic reactor trip and the RTS fails to automatically shut down the reactor, this IC and the EALs are applicable, and must be evaluated.

If the signal does not cause a plant transient and the failure is determined through other means (e.g., assessment of test results), this IC and the EALs are not applicable and no classification is warranted.

EAL (1)

A reactor trip is automatically initiated by the Reactor Trip System (RTS) when certain continuously monitored parameters exceed predetermined setpoints:

Following an automatic trip signal the Operator verifies that the Reactor Trip Breakers are open and that neutron flux is less than 5%. If either response is not obtained the Operator manually actuates DAS Reactor and Turbine Trip.

In the event that the Operator identifies a reactor trip is imminent and successfully initiates a manual reactor trip before the automatic trip setpoint is reached, no declaration is required. The successful manual trip of the reactor before it reaches its automatic trip setpoint or reactor trip signals caused by instrumentation channel failures do not lead to a potential loss of the fuel clad barrier. If manual reactor trip actions in the Main Control Room fail to reduce reactor power below the power associated with the safety system design (< 5%), the event escalates to an Alert under IC SA5 EAL 1.

This EAL addresses a failure of the RTS to initiate or complete an automatic or manual reactor trip that results in a reactor shutdown, and either a subsequent operator manual action taken at the Main Control Room workstations or an automatic trip is successful in shutting down the reactor. This event is a precursor to a more significant condition and thus represents a potential degradation of the level of safety of the plant.

Following the failure on an automatic reactor trip, operators will promptly initiate manual actions at the Main Control Room workstations (DAS, either PDSP trip switch, or de-energizing Rod Drive MGs) to shut down the reactor (e.g., initiate a manual reactor trip). If any these manual actions are successful in shutting down the reactor, core heat generation will quickly fall to a level within the capabilities of the plants decay heat removal systems.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 126 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 127 of 132 If an initial manual reactor trip is unsuccessful, operators will promptly take manual action at another location(s) on the Main Control Room workstations to shut down the reactor (e.g.,

initiate a manual reactor (trip) using a different method). Depending upon several factors, the initial or subsequent effort to manually trip the reactor, or a concurrent plant condition, may lead to the generation of an automatic reactor trip signal. If a subsequent manual or automatic trip is successful in shutting down the reactor, core heat generation will quickly fall to a level within the capabilities of the decay heat removal systems.

EAL (2)

This EAL addresses a failure of a manually initiated trip in the absence of having exceeded an automatic RTS trip setpoint and a subsequent automatic or manual trip is successful in shutting down the reactor (reactor power < 5%).

Following a manually initiated reactor trip signal the operator verifies that the Reactor Trip Breakers are open and that neutron flux is less than 5%. If either response is not obtained the operator manually actuates DAS Reactor and Turbine Trip.

This EAL addresses a failure of the RTS to initiate or complete a manual reactor trip that results in a reactor shutdown, and either a subsequent operator manual action taken at the Main Control Room workstations or an automatic trip is successful in shutting down the reactor. This event is a precursor to a more significant condition and thus represents a potential degradation of the level of safety of the plant.

If an initial manual reactor trip is unsuccessful, operators will promptly take manual action at another location(s) on the Main Control Room workstations (DAS, either PDSP trip switch or de-energizing Rod Drive MGs) to shut down the reactor (e.g., initiate a manual reactor(trip) using a different method). Depending upon several factors, the initial or subsequent effort to manually trip the reactor, or a concurrent plant condition, may lead to the generation of an automatic reactor trip signal. If a subsequent manual or automatic trip is successful in shutting down the reactor, core heat generation will quickly fall to a level within the capabilities of the decay heat removal systems.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 127 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 128 of 132 SU6 ECL: Notification of Unusual Event Initiating Condition: Loss of all onsite or offsite communications capabilities.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1 or 2 or 3)

(1)

Loss of all Table S-1 onsite communication methods (2)

Loss of all Table S-1 ORO communication methods (3)

Loss of all Table S-1 NRC communication methods Table S-1 Communication Methods System Onsite ORO NRC Public Address System X

In Plant Telephones X

Plant Radio Systems X

Commercial Phones X

X ENN (Emergency Notification Network)

X ENS on Federal Telecommunications System (FTS)

X Basis:

The Table S-1 list for onsite communications loss encompasses the loss of all means of routine communications (e.g., in plant telephones, page system, and radios).

The Table S-1 list for offsite (ORO) communications loss encompasses the loss of all means of communications with offsite authorities (e.g., ENN and commercial telephone lines).

The Table S-1 list for NRC communications loss includes the FTS (ENS) and commercial telephone lines.

This IC is the hot condition equivalent of the cold condition IC CU5 EAL 1.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 128 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 129 of 132 This IC addresses a significant loss of onsite or offsite communications capabilities. While not a direct challenge to plant or personnel safety, this event warrants prompt notifications to OROs and the NRC.

This IC should be assessed only when extraordinary means are being utilized to make communications possible (e.g., use of non-plant, privately owned equipment, relaying of onsite information via individuals or multiple radio transmission points, individuals being sent to offsite locations, etc.).

EAL (1)

The first EAL condition addresses a total loss of the communications methods used in support of routine plant operations.

EAL (2 and 3)

The second and third EAL conditions address a total loss of the communications methods used to notify all offsite organizations of an emergency declaration. The OROs referred to here are the States of Georgia and South Carolina; Burke, Aiken, Allendale and Barnwell Counties; Savannah River Site (SRS); and the NRC.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 129 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 130 of 132 SU7 ECL: Notification of Unusual Event Initiating Condition: Failure to isolate containment or loss of containment pressure control.

Operating Mode Applicability: 1 - Power Operation, 2 - Startup, 3 - Hot Standby, 4 - Safe Shutdown Emergency Action Levels: (1 or 2)

Note 1: The Emergency Director should declare the event promptly upon determining that time limit has been exceeded, or will likely be exceeded.

(1)

Failure of containment to isolate when required by an actuation signal AND At least one isolation valve in each penetration is not closed within 15 min. of the actuation (Note 1)

(2)

Containment pressure 5.0 psig (High 2)

AND PCS flow cannot be established within 15 min. (Note 1)

Basis:

EAL (1)

This IC/EAL addresses a failure of one or more containment penetrations to automatically isolate (close) when required by an actuation signal. Absent challenges to another fission product barrier, this condition represents potential degradation of the level of safety of the plant.

For this EAL the containment isolation signal must be generated as the result of an off-normal/accident condition (e.g., automatic or manual Safeguards or PCS signals); a failure resulting from testing or maintenance does not warrant classification. The determination of containment and penetration status - isolated or not isolated - should be made in accordance with the appropriate criteria contained in the plant AOPs and EOPs. The 15-minute criterion is included to allow operators time to manually isolate the required penetrations, if possible.

This event would escalate to a Site Area Emergency in accordance with IC FS1 if there were a concurrent loss or potential loss of either the Fuel Clad or RCS fission product barriers and a direct release pathway to the environment as a result of the failed isolation.

EAL (2)

The containment pressure High 2 setpoint (5.0 psig) is the pressure (PCS-PT005/006/007/008) at which PCS should actuate and begin performing its function.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 130 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 131 of 132 During a DBA, one passive containment cooling water flow path is required to maintain the containment peak pressure and temperature below the design limits.

This IC/EAL addresses an event that results in high containment pressure with a concurrent failure of containment pressure control systems. Absent challenges to another fission product barrier this condition represents potential degradation of the level of safety of the plant.

This EAL addresses a condition where containment pressure is greater than or equal to the setpoint at which the Passive Containment Cooling System (PCS) is designed to automatically actuate per design. The 15-minute criterion is included to allow operators time to manually align PCS components that may not have automatically actuated, if possible. The inability to actuate the required equipment and perform its safety function indicates that containment heat removal/depressurization systems are either lost or performing in a degraded manner.

This event would escalate to a Site Area Emergency in accordance with IC FS1 if there were a concurrent loss or potential loss of either the Fuel Clad or RCS fission product barriers.

ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 131 of 132

Vogtle 3 & 4 Emergency Action Levels and Basis (NEI 07-01 Revision 0)

NMP-EP-141-004 SNC Unit S Version 2.0 Page 132 of 132

5.0 REFERENCES

1. NUREG-0654/FEMA-REP-1, Criteria for Preparation and Evaluation of Radiological Emergency Response Plans and Preparedness in Support of Nuclear Power Plants, October 1980.
2. NUREG-1022, Event Reporting Guidelines 10 CFR § 50.72 and § 50.73
3. NUREG-1228, Source Estimations During Incident Response to Severe Nuclear Power Plant Accidents
4. NUREG-1140, A Regulatory Analysis on Emergency Preparedness for Fuel Cycle and Other Radioactive Material Licensees
5. NUREG-1449, Shutdown and Low-Power Operation at Commercial Nuclear Power Plants in the United States
6. Regulatory Guide 1.101, Emergency Response Planning and Preparedness for Nuclear Power Reactors
7. NSIR/DPR-ISG-01, Interim Staff Guidance, Emergency Planning for Nuclear Power Plants
8. Regulatory Issue Summary (RIS) 2007-02, Clarification of NRC Guidance for Emergency Notifications During Quickly Changing Events
9. Generic Letter 88-17, Loss of Decay Heat Removal
10. SECY 91-283, Evaluation of Shutdown and Low Power Risk Issues
11. NUMARC 91-06, Guidelines for Industry Actions to Assess Shutdown Management
12. NEI 03-12, Template for the Security Plan, Training and Qualification Plan, Safeguards Contingency Plan [and Independent Spent Fuel Storage Installation Security Program]
13. Vogtle Unit 3 & 4 Technical Specifications (TS)
14. VEGP Units 3 and 4 Offsite Dose Calculation Manual (ODCM) 14.15............................................................................................................................................. S afety Evaluation Report (SER, ADAMS ML17079A292) 6.0 COMMITMENTS None End of procedure text ND-19-1095

Enclosure:

Emergency Action Levels and Basis (NEI 07-01 Revision 0)

Enclosure Page 132 of 132