MONTHYEARML18113A9961979-03-13013 March 1979 Order to Show Cause Re Potentially Deficient Piping Design. Orders Facility to Be Placed in Cold Shutdown within 48-h Project stage: Other ML19282C6771979-03-15015 March 1979 Summary of 790308 Meeting W/S&W to Discuss Pipe Stress Calculations Using Pipestress Code Project stage: Meeting ML18113A9671979-03-15015 March 1979 Notification of 790316 & 17 Meeting W/S&W in Bethesda,Md to Discuss Reinstating Operation at Facilities Which Received Shutdown Orders on 790313 Project stage: Meeting ML18113A9661979-03-20020 March 1979 Summarizes 790320 Telcon W/S&W Re Future Actions to Resolve Outstanding Seismic Concern of Five Shutdown Plants.Requests Reanalysis Results of safety-related Piping Sys & Supports Project stage: Other ML19263D8341979-03-26026 March 1979 Discusses 790301 Telcon W/Util & S&W.Nrc Requested Copy of Pipestress Computer Code to Compare W/Nupipe.S&W Stated Policy of Not Releasing Codes or Calculations.Meeting on 790308 for S&W to Bring Pipestress to NRC for Review Project stage: Meeting ML18114A5381979-03-29029 March 1979 Assigns Responsibility for Prompt Meeting Notification Re 790313 Show Cause Orders Project stage: Meeting ML20244A5561979-03-31031 March 1979 Answer to NRC 790313 Order to Show Cause.Will Reanalyze Seismic Loads on Piping Sys & Will Modify Sys Where Necessary.Expects to Submit Documented Results by 790424. Believes NRC Should Examine S&W Analyses Project stage: Other ML20244A5501979-03-31031 March 1979 Forwards Formal Util Response to NRC 790313 Order to Show Cause Re Potentially Unsafe Piping Sys Project stage: Other ML19261C9841979-04-0202 April 1979 Forwards Description of Info to Be Documented for NRC Review for Facility.Requests Schedule for Submittal of This Info Prior to Plant Startup Project stage: Other ML19344D7361979-04-10010 April 1979 Record of Telcon W/D Ford (Ucs) on 790320 Re Chronology of NRC Activities Re Pipestress Issue Project stage: Other ML19289E9721979-04-10010 April 1979 Summary of 790329-30 Meeting W/Util & S&W in Boston,Ma Re Progress to Date & Early Analysis of Pipe Stresses in safety-related Sys Project stage: Meeting ML19270G5371979-04-11011 April 1979 Delineates Criterion to Develop plant-specific Info Packages on Site Visits Project stage: Request ML20244A6471979-04-17017 April 1979 Licensees Response to 790402 Request of PA Public Util Commission for Hearing & Petition to Intervene Re 790313 Show Cause Order.Urges NRC to Hold Ruling in Abeyance. Certificate of Svc Encl Project stage: Other ML19289F0811979-04-20020 April 1979 Summary of 790411-12 Meeting W/Util & S&W in Boston,Ma Re Status of Reanalysis Efforts & Review of Packages Completed to Date Project stage: Meeting ML18114A6121979-05-18018 May 1979 Summarizes Procedures & Calculational Techniques Used in Reanalysis of Piping Sys Designed W/Shock II Computer Program.Reanalysis Will Satisfy 790313 Order to Show Cause Project stage: Other ML19224C7941979-05-18018 May 1979 Requests Addl Info in Order for NRC to Review Proposed Amplified Response Spectra Using Soil Structure Interaction Project stage: Other ML19269D6151979-05-23023 May 1979 Responds to NRC .Forwards Amplified Response Spectra Based on Soil Structure Interaction.Details Result of Analysis of Small Strain Valves of Plus or Minus 50% Project stage: Other ML18114A7201979-05-25025 May 1979 Discusses Position Re Use of Soil Structure Interaction for Seismic Pipestress Analyses Being Performed.Approves Methodology,Provided That Seismic Stresses Calculated Are Increased by Factor of 1.5 Project stage: Other ML19246A7211979-05-25025 May 1979 Submits Identified Areas to Be Addressed During Seismic Pipestress Reanalysis Project stage: Other ML19241B2111979-05-25025 May 1979 Discusses Areas to Be Covered in Interim or Final Rept on Seismic Pipestress Reanalysis,Including Stresses Due to Seismic Anchor Movements,Support Stiffness Accountability & Criteria for Pipe Support & Design Project stage: Other ML19289F6761979-06-11011 June 1979 Discusses Present Status of Piping Sys Reanalysis.Reanalysis Complete & Two Hydraulic Snubbers Installed.No Pipe Is Overstressed in Event of Safe Shutdown Earthquake.Rept Supporting 790706 Request to Be Submitted by 790618 Project stage: Other ML19241B8541979-06-14014 June 1979 Summary of 790524 Meeting W/S&W & Util in Bethesda,Md Re Amplified Response Spectra Developed W/Consideration of Soil Structure Interactions Project stage: Meeting ML19225C0641979-07-23023 July 1979 Requests Termination of 790313 Order to Show Cause Re safety-related Piping Sys Project stage: Other ML19249A7131979-08-0303 August 1979 Draft Safety Evaluation Supporting Resumption of Operation Per Required Mods to Seven Supports,Addition of Three Others & Approval of Two Supports Not Yet Found to Be Acceptable Project stage: Draft Approval ML19249A7091979-08-0303 August 1979 Draft Order Not Requiring Continued Shutdown of Facility or Termination Proceeding Initiated by 790313 Order.Analysis & Mod to Fuel Pool Cooling & Purification Sys Required Before Further Use Project stage: Draft Other ML19249A7041979-08-0303 August 1979 Forwards for Consideration Draft Order & Draft Safety Evaluation Re Facility Shutdown Per Lack of Assurance That Analysis of Piping Sys for Seismic Loads Provided Proof of Safe Shutdown During Seismic Event Project stage: Draft Approval ML19207B0861979-08-0808 August 1979 Safety Evaluation Supporting Order Terminating Proceeding Initiated by 790313 Show Cause Order Re Cold Shutdown Condition.Facility May Resume Power Operation Project stage: Approval ML19207B0791979-08-0808 August 1979 Order Terminating Proceeding Initiated by 790313 Show Cause Order Re Cold Shutdown Condition Project stage: Other 1979-04-02
[Table View] |
Text
Egu l
/
h, UN11LL. TATEs NUCLEAR REGULATORY COMMISSION y
g
.K WASHING TON, D. C. 20555
?
o
'+4
,o May 25, 1979
Docket No. 50-334 Mr. C. N. Dunn, Vice President Operations Division Duquesne Light Company 435 Sixth Avenue Pittsburgh, Pennsylvania 15219 I
Dear Mr. Dunn:
In the systems review of the Beaver Yalley, Unit No.1 pipestress reanalysis, we have identified the following areas which are to be addressed during your seismic pipestress reanalysis.
1.
All pipe runs analyzed with SHOCK 2 must be identified.
2.
Request the following full size drawings:
RM-21B i
RM-27A, B RM-29A, B, C, D RM-37A RM-39A, 8 3.
Reanalysis of the Primary Component Cooling Water Heat Exchanger discharge piping.
Lines:
18"-WR-14-151 Q3 f
18"-WR-15-151 Q3 18"-WR-16-151 Q3 30"-WR-17-151 Q3 Failure of any of these lines would result in flooding of redundant safety related equipment.
4.
Reanalysis of the following lines located in the Intake Structure.
30"-WR-171-151-Q3 30"-WR-172-151-Q 3 30"-WR-175-151-Q 3 18"-WR-154-151-Q3 12"-WR-177-151-Q3 i
10"-SWW-14-151-Q 3
'>n.
,_l 790706027o-
Mr. C. N. Dunn Duquesne Light Company May 25,1979 Failure of any of these lines could result in possible flooding of safety related pumps. The asterisked line, unlike the other lines was not considered safety-related during the plant design and was nev( r seismically analyzed. This line runs above and adjacent to diver Water Pump 18 and can only be isolated from the seismically designed piping by a manually operated butterfly valve which is normally open during plant operation.
5.
The cooling water discharge lines from the Emergency Diesel Generator Cooling System Heat Exchangers downstream of the normal open isolation valves are not seismically qualified.
These lines are located in the diesel generator compartments and their failure could impact on the operation of the emergency diesels. A seismic analysis should be perfonned on these lines.
6.
The discharge lines of the Quench Spray Pumps have not been proposed for reanalysis.
10"-QS-3-153-Q3 10"-QS-4-153-Q3 1
8"-QS-22-153-Q3 8"-QS-23-153-Q3 Justify that reanalysis of the above lines is not necessary.
7.
The Recirculation Spray Piping both inside and outside containment with the exception of the lines listed below is not being reanalyzed.
Justify that reanalysis of the Recirculation Spray System is not l
necessary.
I 12"-RS-5-153-Q 3 12"-RS-7-153-Q3 12"-RS-8-153-Q3 8.
Verify that the discharge lines from the Control Room Air Condition Condensers, the Charging Pump Coolers, and Line 6"-WR-53-151-Q have been seismicially analyzed by an acceptable method. Thes$
lines are part of the River Water System.
209 hj
Mr. C. N. Dunn 3-May 25,1979 Duquense Light Company In the above requirements for reanalysis, Duquesne Light Company may elect to justify why a reanalysis is not required. This justification should be provided to the NRC within one week following receipt of this letter.
If you have any questions, please let us know.
Sincerely, s
l l
l Darrell G.' Eisenhut, Deputy Director Division of Operating Reactors cc:
See next page t
i o
i b Ii
Mr. C. N. Dunn Duquesne Light Company May 25,1979 cc:
Gerald Charnof f, Esquire Mr. James A. Werling day E. Silberg, Esquire Plant Superintendent Shaw, Pittman, Potts and Trowbridge Beaver Valley Power Station 1800 M Street, N.W.
P. O. Box 4 Washington, D. C.
20036 Shippingport, Pennsylvania 15077 Karin Carter, Esquire Special Assistant Attorney General Bureau of Administrative Enforcement 5th Flc--
Executive House Harrisourg, Pennsylvania 17120 Mr. J. M. Cumiskey Stone and Webster Engineering Corporation P. O. Box 2325 Boston, Massachusetts 02107 Mr. J. D. Woodward R & D Center Westinghouse Electric Corporation Building 7-303 Pittsburgh, Pennsylvania 15230 B. F. Jones Memorial Library 663 Franklin Avenue Aliquippa, Pennsylvania 15001 Mr. Jack Carey Technical Assistant Duquesne Light Company P. O. Box 4 Shippingport, Pennsylvania 15077 Mr. R. E. Martin Duquesne Light Company 435 Sixth Avenue Pittsburgh, Pennsylvania 15219 Marvin Fein i
Utility Counsel City of Pittsburgh 313 City-County Building Pi ttsburgh, Dennsylvania 15219 a
oqn Og*
/ /
I e