LR-N18-0086, Supplemental Information to License Amendment Request (LAR) to Amend the Hope Creek Technical Specifications (TS) to Revise Action for Inoperable Emergency Diesel Generator (EDG) a or 8

From kanterella
(Redirected from ML18269A244)
Jump to navigation Jump to search

Supplemental Information to License Amendment Request (LAR) to Amend the Hope Creek Technical Specifications (TS) to Revise Action for Inoperable Emergency Diesel Generator (EDG) a or 8
ML18269A244
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 09/26/2018
From: Carr E
Public Service Enterprise Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LAR H18-01, LR-N18-0086
Download: ML18269A244 (4)


Text

PSEG Nuclear LLC P.O . Box 236, Hancocks Bridge, New Jersey 08038-0236 0 PSEG NuclW,r LLC 10 CFR 50.90 LR-N 18-0086 LAR H18-01 SEP 2e**201B U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Hope Creek Generating Station Renewed Facility Operating License No. NPF-57 NRC Docket No. 50-354

Subject:

Supplemental Information to License Amendment Request (LAR) to Amend the Hope Creek Technical Specifications (TS) to Revise Action for Inoperable Emergency Diesel Generator (EDG) A or 8

Reference:

1. PSEG letter to NRC, "License Amendment Request to Amend the Hope Creek Technical Specifications to Revise Action for Inoperable Emergency Diesel Generator A or B, dated March 28, 2018 (ADAMS Accession No. ML18087A095)

In the Reference 1 letter PSEG Nuclear LLC (PSEG) submitted a license amendment request (LAR) to Renewed Facility Operating License No. NPF-57 for Hope Creek Generating Station (HCGS) to revise TS 3/4.8.1.1, "AC Sources - Operating"; specifically Action b.2.b concerning one inoperable Emergency Diesel Generator (EOG).

Based upon further development of the design and procurement activities for the supplemental power source that is credited in the subject LAR, PSEG has determined that a supplement to the Reference 1 LAR is warranted. The supplemental information is provided in the Attachment to this letter.

PSEG has determined that the information provided in this submittal does not alter the conclusions reached in the 10 CFR 50.92 no significant hazards determination previously submitted. In addition, the information provided in this submittal does not affect the bases for concluding that neither an environmental impact statement nor an environmental assessment needs to be prepared in connection with the proposed amendment.

There are no regulatory commitments contained in this letter. If you have any questions or require additional information, please contact Mr. Michael Wiwel at 856-339-7907.

LR-N 18-0086 10 CFR 50.90 Page2 I declare under penalty of perjury that the foregoing is true and correct.

Executed on c;,Pc<;f~

(Date)

Respectfully, cV Eric S. Carr Site Vice President Hope Creek Generating Station

Attachment:

Supplemental Information for LAR H18-01 cc: Administrator, Region I, NRC Project Manager, NRC NRC Senior Resident Inspector, Hope Creek Mr. P. Mulligan, Chief, NJBNE PSEG Corporate Commitment Tracking Coordinator Hope Creek Commitment Tracking Coordinator

LR-N18-0086 LAR H18-01 Enclosure Supplemental Information Regarding the Supplemental Power Source Described in LAR H18-01 By letter dated March 28, 2018, PSEG Nuclear LLC (PSEG) submitted a license amendment request (LAR) to revise Technical Specification (TS) 3/4.8.1.1, "AC Sources - Operating";

specifically Action b.2.b, to remove reference to the Salem Unit-3 gas turbine generator and replace it with a supplemental power source. The supplemental power source would meet the intent of Branch Technical Position 8-8, "Onsite (Emergency Diesel Generators) and Offsite Power Sources Allowed Outage Time Extensions" to accommodate outages of up to 14-days for either the A or B emergency diesel generators at Hope Creek Generating Station (HCGS).

The description of the supplemental power source within the subject LAR was based on requirements contained in the bid specification provided to multiple diesel generator suppliers.

Based on the review of proposals received from these suppliers, certain descriptions of the supplemental diesel generators (SDGs) need to be updated.

The LAR described the supplemental power supply as consisting of portable, trailered diesel generators and associated connection cables that could be transported and connected to the plant's 4.16-kV electrical system and aligned to either the A or B 4.16-kV Class 1E bus when necessary. The description identified that each diesel would include a fuel supply tank capable of providing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of operation at rated load with access to additional fuel supplies from the onsite diesel fuel oil storage tank and/or the availability of offsite fuel delivery via tanker truck.

Based on the proposals received from diesel generator suppliers, none were able to provide a tank size capable of providing 24-hours of rated operation due to the size and weight constraints associated with a tank of this capacity. This supplement updates the fuel supply tank description in the subject LAR to a tank size capable of supplying a minimum of 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> of operation at rated load. This time frame is based on the 1600 gallon tank size available from the diesel generator suppliers and the fuel consumption rate of the diesel at rated load.

For conservatism, the timeline described in the reference LAR to transport and connect the supplemental power source to the 4.16kV bus reflects a total of three synchronized diesel generators. Based on the selected diesel supplier, there will only be two synchronized diesel generators, therefore the transport and connection timelines described in the LAR are conservative.

Finally, the LAR states that the supplemental diesel generators will be load tested via a 100%

rated load bank to approximately 30% of load to verify voltage and frequency. The 30% load value was identified as a common industry recommendation to minimize carbon build up in the machine. Based on the submitted proposal and subsequent discussions with the supplier, the load bank will not be rated for the full load of each SDG (2.25 MW) but will be rated for 1.0 MW which is nominally 44% of the rated load for each SDG. Also, the SDGs will be loaded based on manufacturer's recommendation to verify voltage and frequency which may be a load value different than 30%.

PSEG has determined the update described in this supplement does not change the Regulatory Evaluation or No Significant Hazards Determination described in the subject LAR. The update relative to diesel fuel oil tank size, number of SDGs or load testing does not alter the electrical capacity of the supplemental source.

A 10-hour ( 1600 gallon) inventory of fuel oil is reasonable based on the fact that the SDGs will likely not be operated continuously at rated load and operators can readily refill the SDG fuel tanks using multiple sources of diesel fuel available on site. There are eight transportable, 1

LR-N18-0086 LAR H18-01 Enclosure double walled fuel pods each capable of containing 250 gallons of diesel fuel oil and two 500 gallon fuel pods. These fuel pods are filled as necessary from a 4,000 gallon primary tank located on site and transported to wherever they are needed. These fuel pods can be filled, transported and staged as required in proximity to the SDGs to augment their 10 hour1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> capacity tanks. The 2,000 gallon fuel truck whose internal pump is used to fill the fuel pods from the primary tank can itself be used as a stationed source of additional fuel to the SDGs. Fuel transfer to and from these pods is routinely performed by station personnel via controlled procedures for various routine diesel fuel uses on site. The same transfer process will be implemented and controlled by approved operating procedures for the SDGs when they are placed into service. The 44,800 gallon diesel fuel supply dedicated to the out-of-service EOG can also be accessed to augment these mobile fuel sources. If necessary, the large (-million gallon) diesel fuel oil storage tank can also be accessed for additional inventory. In addition, offsite delivery of diesel fuel via 7,600 gallon tanker truck is available from a local, qualified supplier per arrangement developed to support Phase-3 of the Flexible Coping Strategies (FLEX) program to cope with beyond design basis external events. Based on these diverse sources and quantities of diesel fuel available, the 10-hour fuel tank capacity coupled with established operating procedures for the SDGs provides a reasonably conservative time frame to allow operators to augment the SDG with additional fuel for continuous duty.

All SDG electrical ratings and associated loading capability identified in the reference LAR will remain as described. The load testing of the SDGs will conform to the manufacturer's recommended test that will adequately verify that each SDG is capable of providing power within its specified range of voltage and frequency. The load value used for this test will conform to the size of the available load bank from the supplier and will comply with established industry standards and hence will ensure proper functioning and performance of the machine when called upon. Therefore, the supplemental power source will be capable of providing power to all required A or B 4.16-kV Class 1E loads for any anticipated period of time.

In the referenced March 28, 2018 letter, PSEG requested the amendment to be issued with implementation required within 60 days of the date of issuance. Based on the current schedules for vendor delivery of the SDGs and receipt of a required environmental permit, PSEG requests that the amendment be issued with implementation required no later than September 2, 2019.

2