REVISIONS LTR ECO DESCRIPTION DATE TITLE ATP PS294-Q2 GI NEERING NUMBER

....._-----~i,+,i
;,....-....... --------+----"-.......

QUAL CONTROL ATP 451 SHEET I

8626 WILBUR AVENUE

  • NORTHRIDGE. CA 91324 * (213) 886-8488
  • Telex No. 65-1303 VEC 304-11/80 APPROVED*

OF 5

REV A

.---------------------------------~~-~-----

1.0 SCOPE AlidyNE ENOINEl!IIINO CORPORATION ACCEPTANCE TEST PROCEDURE NO. 451 PS294-Q2 This document defines the Acceptance Test Procedure (ATP) for the PS294-Q2 power supply board assembly. Either the end item ATP or a special test procedure appropriate to a p~rticular contract will define any additional requirements.

2.0 EQUIPMENT REQUIRED Table One lists the test equipment required to perform the ATP.

TABLE ONE - EQUIPMENT REQUIRED FOR ATP DescriEtion Manuf acture*r Part or Model #

Alternate PS294 Tester Validyne T-1095 None Variac The Superior 116 Commercial Equiv...

Electric Co.

2 Digital Mult-imeters Data Precision DP248 Commercial Equiv.

Oscilloscope B & K 1470 Commercial Equiv.

3.0 PRELIMINARY PROCEDURE Record test results as indicated in Appendix A.

3.1 Refer to Assembly Drawing No. Q9854 and inspect assembly for completeness and accuracy.

Inspect the heat sinks to ensure that they are flush mounted on the transistors Ql, Q3, and Q4.

4.0 INITIAL TEST SET-UP 4.1 Connect PS294-Q2, digital voltmeters (DVM) and oscilloscope to the tester as shown in Figure 1. Set the output of the variac to the lowest dial setting and connect to the tester.

Make sure Sl and S2 are in "OFF" position, S3 in"OPERATE" position and S4, SS and S6 are in "OUT" posi-tion.

4.2 Plug in the variac to 115V AC.

Set S7 switch to "AC" position *. Slowly increase the variac output to llSV AC.

The "POWER AVAILABLE" light emit-ting-diode (LED) on tester should be "ON", if not then tester fuse is open.

NUMBER ATP 451 SHHT

'2 REV A

DVM 0

SCOPE

-PS294--

OVM 115 VAC FIGURE 1 ATP 451

  • _ TEST ADJ.

L AlidyNE ENOINEEIIINO COIIPOIIATION ACCEPTANCE TEST PROCEDURE NO. 451 PS924-Q2 4.3 Check the green LED on the PS924-Q2 for ON or OFF, it should be "ON".

5.0 FUNCTIONAL TESTS 5.1 LOAD REGULATION Set switch Sl to Position 1.

The DVM should read 5.00 +/-0.25 VDC (no load regulated voltage). Adjust the +5 load to 8,5 ohm.

Set switch S4 to"IN" position. Note the DVM reading (full load regulated voltage).

The differ~

ence between the full load and no load voltage should be less than or equal to 50mV.

Turn switch S4 to"OUT" position.

5.2 Set switch Sl to Position 2.

DVM should read 15.00 +/-0.75 VDC (no load regulated voltage).

Adjust +15 load to 85 ohm.

Set switch S5 to"IN" position. Note the DVM reading again (full load regulated voltage).

The difference between full load and no load voltage should be less than or equal to 150mV.

Set switch, S5 to"OUT".position.

5.3 Set switch Sl to position 3.

DVM should read -15.00 +/-.75 VDC (no load regulated voltage). Adjust -15 load to 85 ohm.

Set switch, S6 to"IN" position. Note the DVM reading (full load regulated voltage).

The difference between no load and full load voltage should be less than or equal to 150mV.

Set switch, S6 to 110UT11 position.

6.0 OUTPUT FAULT 6.1 Set switches*S4, S5 and S6 to"IN" position.

Set switch, S2 to position 2.

Green LED will flash periodically.

Set switch, S2 to"OFF" position.

Green LED will remain on.

6.2 Leave S4, S5 and S6 on"IN" position. Set switch, S2 to position 31 Green LED will be flashing. Set switch, S2 to"OFF" position Green LED will remain on.

7.0 OUTPUT SHORT 7.1 Set switch S2 to. "OFF" position, S4, S5 and S6 to"OUT" position. Sl to "OFF", S3 to Short. Set scope for D.C. coupling.

Sl to position 1. Out-put voltage pulse should_ be 80 +/-20 mSec,.o.so +/-.2 VP-P. (Volts peak to peak).

7.2 Set Sl to position 2.

Output voltage pulse should be 60 +/-20mSec &.25.:t...05 VP-R 7.3 Set Sl to position 3. Output voltage pulse should be 80 +/-20 mSec and

-.25.:!:.*05 VP-P.

Set S3 to operate.

NUMBER ATP 451 SHEET 4

OF 5

REV A

A(idyNE ENGIINEEIIINGI COlll"OIIATION ACCEPTANCE TEST PROCEDURE NO. 451 PS924-Q2 8.0 LINE REGULATION 8.1 Set Sl to position 1. S4, S5 and S6 to"IN" position.

Set +5V load to 8.5 ohm, +15V load to 85 ohm and -15V load to 85 ohm *.

8.2 Decrease AC voltage down to 103.5V and increase up to 126.5V.

+SV output change should be less than or equal to 25mV DC.

8.3 Set Sl to position 2.

Decrease AC voltage down to 103.5 VAC.

+15V output*

change should be less than or equal to 75mV DC.

8.4 Set Sl to position 3.

Increase AC voltage to 126.5.

-15V output change should be less than or equal to 75mV DC.

Return to AC voltage to 115 VAC.

9.0 OUTPUT RIPPLE 9.1 Set DVM to ACV.

Set Sl to position 1. Output should be less than or equal to lOmV RMS.

9.2 Set Sl to position 2.

Output should be less than or equal to lOmV RMS.

9.3 Set Sl to position 3.

Output should be less than or equal to lOmV RMS.

Set DVM to DCV.

Set S7 to"OFF".

10.0 OVERVOLTAGE (O~V.) PROTECTION CIRCUIT TEST 10.1 Set switch SI to position 1.

Set switch S2 in"OFF" position.

Set switch S3 to"OPERATE".

Set switches S4, S5 and S6 in"OUT" position.

Set O.V. test adjust potentiometer (located on right hand side of tester) to zero.

10.2 Refer to PS294-Q2 Assembly Drawing No. Q9854 and connect a jumper between TPI and junction of Rl and F2~ and add a jumper across F2.

10.3 Set switch S7 to 110.v. Test" position. Adjust O~V. test potentiometer slowly to increase the test voltage (as indicated by DVM) until the voltage goes to less than or equal to 1.00 VDC. Observe green LED on PS294-Q2 goes off. This should occur at 6.5 +/-0.5 voe.

10.4 Set switch S7 to"OFF".

Remove jumper from TPI and junction of Rl and F2.

NUMBER ATP 451 SHEET 5

OF 5

REV A

AlidyNE ENGINEERING COlll"OIIATION APPENDIX A TEST REPORT NUMBER APPENDIX A ATP 4Sl 1

of 3

REV A

ASSY PS2 94-Q2 POWER SUPPLY S/0 CUSTOMER W/0 SERIAL NO.

TESTED BY DATE Paragraph/Step 3al Visual Inspection 4.3 Green LED on/off 5.1* Regulated +SVDC (S4 out) A Regulated +SVDC (S4 in) B Regulated +5VDC (A-B) 2 Regulated +15 VDC (S5 out) C Regulated +15 voe (S5 in) D

  • Regulated +15 voe (C-D) 5.3 Regulated -15VDC (S6 out) E Regulated -15VDC (S6 in) F Regulated -15VDC (E-F) 6al S2 at Position 2~0FF 602 S2 at position 3~0FF 7.0 VOLTAGE PULSE 7.1 Voltage Pulse and On Time (+SV) 7.2 Voltage Pulse and On Time (+lSV) 7.3 Voltage Pulse and On Time (-iSV) 8.0 LINE REGULATION 8.2

+5V DC Output Change

. +15V DC Output Change

-15V DC Output Change QC Accepted Specification Assembly Complete ON

+S.00 +/-.25 VDC

+5.00 +/-.25 VDC less than/equal to

+/-0.05 VDC

+15.00 +/-.75 VDC

+15.00 +/-.75 VDC

  • less than/equal to

+/-.150 VDC

-15.00 +/-.75 VDC

-15.00 +/-.75 VDC less than/equal to

+/-.150 VDC Green LED recovers Green LED recovers

.80 +/-.20V & 80+/-20msec

.25 +/-.0-SV & 60+/-20msec

.25 +/-.05V & 80+/-20msec

  • 025Vmax.
  • 075Vmax *
  • 075V max.

NUMBER APP~IDIX A

  • ATP 451 SHEET 2

OF 3

REV A

An7n WILBUR A.VENUE e NnATl-lAtnr.i: rt,. Q1...'!.'2.4.

a......1'211\\ RRF..R4RR

  • T... 1.... M,.. IU::.1'ln'l

TEST REPORT ASSY PS 294-Q2 POWER SUPPLY S/0 CUSTOMER W /0 ScRIAL NO.

TESTED BY DATE Paragraph/Step Accepted Specification 9.0 RIPPLE 9.1

+SV Ripple 9.2

+lSV Ripple 9.3 -lSV Ripple 10.3 Peak Over* Voltage QC NUMBER Less than/equal to lOmV RMS Less than/equal to lOm.V RMS Less than/equal to lOmV RMS 6.5 +O.SVDC APPENDIX A ATP.451 SHEET 3

OF 3

REV A