8 to Fire Hazards Analysis Report (Fhar)Vol. 2. Attachment 3-5O to 3-5R
ML18120A019
Person / Time
Site: Crane 
Issue date: 04/06/2018
From:
Exelon Generation Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18117A343 List: ... further results
References
TMI-18-047
Download: ML18120A019 (23)


Text

ATTACHMENT 3-5O APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air Rev. 27 DECAY HEAT RIVER WATER A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

DR-P-1A X

X X

P X

S X

X X

X Train A DR-P-1B X

X X

X P

X X

R S

D R

S D

R S

D Train B DR-S-1A S

S S

S S

S S

S S

Train A DR-S-1B S

S S

S S

S Train B DR-V-1A X

X X

S S

X X

X Train A DR-V-1B X

X X

X P

X S

R S

D R

S D

R S

D Train B

ATTACHMENT 3-5O APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air Rev. 27 7DECAY HEAT RIVER WATER D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T G

G H

H H

H H

H B

B B

B B

B B

B S

S S

S B

B B

B B

B B

B P

P P

P F

F F

F F

F F

F F

F F

F F

F F

F H

H H

H F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 DR-P-1A S

X X

X R

Train A DR-P-1B S

P X

X R

X Train B DR-S-1A S

S S

X Train A DR-S-1B S

S S

X Train B DR-V-1A S

X X

X M

Train A DR-V-1B S

P X

X M

X Train B

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

NI-11 X

X P

S X

X X

X Train A NI-12 S

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD RC4A-TE-1 S

X S

X X

X X

Train X RC4A-TE-4 S

S S

X X

X Train X RC4B-TE-1 S

X S

S X

X X

Train X RC4B-TE-4 S

S S

X X

Train X RC-TE-958 S

X X

X X

X X

R S

D R

S D

Train A - Control Room & RSD RC-TE-960 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD RC5A-TE-2 S

X S

S X

X X

Train X RC5A-TE-4 S

S S

X X

Train X RC5B-TE-2 S

X S

S X

X X

X Train X RC5B-TE-4 S

S X

X X

Train X RC-TE-959 S

X X

X X

X X

R S

D R

S D

Train A - Control Room & RSD RC-TE-961 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD RC3A-PT3 S

X P

X X

X P

X X

X Train A RC-PT-963 S

X X

X X

X X

X R

S D

R S

D Train A - RSD Only RC-PT-949 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 2a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

RC1-LT-1 S

D S

S X

X X

Train X RC1-LT-3 S

D S

S S

X X

X X

Train X RC-LT-777 X

X X

R S

D R

S D

R S

D Train B - Control Room & RSD RC2-TE-1 S

S S

X X

Train X RC2-TE-2 X

X X

R S

D R

S D

R S

D Train B FW-LT-775 S

X P

P X

X X

R S

D R

S D

Train A - Control Room & RSD FW-LT-789 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD FW-LT-788 S

X X

X X

X X

R S

D R

S D

Train A - Control Room & RSD FW-LT-776 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD SP6A-PT-1 S

S S

X X

X Train X - Also for MS-V-3D, E, F SP6A-PT-2 S

S S

S X

X X

Train X - Also for MS-V-3D, E, F MS-PT-950 S

X P

P X

X X

R S

D R

S D

Train A - Control Room & RSD MS-PT-1180 S

X X

X Train B SP6B-PT-1 S

S S

S X

X X

Train X - Also for MS-V-3A, B, C SP6B-PT-2 S

S S

X X

X Train X - Also for MS-V-3A, B, C MS-PT-951 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 3a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

MS-PT-1184 S

S S

X X

X X

Train A DH-DPT-802 X

X X

S X

X X

X X

X R

S D

R S

D Train A - Control Room & RSD DH-DPT-803 X

X X

S X

X X

R S

D R

S D

Train B - Control Room & RSD DH-FI-299A Train A - Local Indication DH-FI-299B Train B - Local Indication DH2-TE-1 X

X X

S X

X X

X X

X R

S D

R S

D Train A - Control Room & RSD DH2-TE-2 X

X X

S X

S X

S X

R S

D R

S D

R S

D Train B - Control Room & RSD DH6-TE-1 X

X X

S X

X X

X X

X R

S D

R S

D Train A - Control Room & RSD DH6-TE-2 X

X X

S X

S X

S X

R S

D R

S D

R S

D Train B - Control Room & RSD CO-LI-1004 Local Indication CO-LI-1005 Local Indication MU14-LT X

S X

S S

X X

X Train X MU-LT-778 X

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD DH-LT-808 P

X S

X X

X X

X X

X X

Train A - Control Room & RSD DH-LT-809 X

P X

X X

R S

D R

S D

Train B - Control Room & RSD

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 4a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

EF-FT-788 S

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD EF-FT-779 S

S X

X X

X R

S D

R S

D Train C - Control Room & RSD EF-FT-782 S

X X

X R

S D

R S

D R

S D

Train B - Control Room & RSD EF-FT-791 S

S X

X X

X R

S D

R S

D Train C - Control Room & RSD FW-LT-1044 (1)

X X

X X

HSPS-Not required.

FW-LT-1040 (2)

X X

X HSPS-Not required.

FW-LT-1045 (3)

X HSPS-Not required.

FW-LT-1041 (4)

X HSPS-Not required.

FW-LT-1046 (1)

X X

X X

HSPS-Not required.

FW-LT-1042 (2)

X X

X HSPS-Not required.

FW-LT-1047 (3)

X HSPS-Not required.

FW-LT-1043 (4)

X HSPS-Not required.

FW-LT-1052 (1)

X X

X X

HSPS. Required in CB-FA-3b.

FW-LT-1048 (2)

X X

X HSPS-Not required.

FW-LT-1053 (3)

X HSPS-Not required.

FW-LT-1049 (4)

X HSPS-Not required.

FW-LT-1054 (1)

X X

X X

HSPS-Not required.

FW-LT-1050 (2)

X X

X HSPS-Not required.

FW-LT-1055 (3)

X HSPS-Not required.

FW-LT-1051 (4)

X HSPS-Not required.

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 5a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

CO-LT-1060 (1)

S S

X X

X X

HSPS-Not required.

CO-LT-1061 (2)

X X

S X

X X

HSPS-Not required.

CO-LT-1062 (1)

S S

X X

X X

HSPS-Not required.

CO-LT-1063 (2)

X X

S X

X X

HSPS-Not required.

MS-PT-950 (1)

S X

P P

X X

X R

S D

R S

D MS-PT-1180 (2)

X X

X HSPS-Not required.

MS-PT-1182 (3)

X HSPS-Not required.

MS-PT-1181 (4)

X HSPS-Not required.

MS-PT-1184 (1)

X X

X X

HSPS-Not required.

MS-PT-951 (2)

X X

X X

R S

D R

S D

R S

D MS-PT-1185 (3)

X HSPS-Not required.

MS-PT-1183 (4)

X HSPS-Not required.

FW-TE-1046 (1)

X X

HSPS-Not required.

FW-TE-1044 (2)

X HSPS-Not required.

FW-TE-1047 (3)

X HSPS-Not required.

FW-TE-1045 (4)

X HSPS-Not required.

FW-TE-1050 (1)

X X

HSPS-Required in CB-FA-3b.

FW-TE-1048 (2)

X HSPS-Not required.

FW-TE-1051 (3)

X HSPS-Not required.

FW-TE-1049 (4)

X HSPS-Not required.

IC5-DPT X

S X

S X

X X

IC9-TE S

S X

X X

Interlock to Close MU-V-1A/1B MU5-TE X

X X

X X

Interlock to Close MU-V-3

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 6a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

MU42-DPT X

X X

S X

S X

X Auto Control for MU-V-32 RC3A-PT-1 X

X X

SP10A-PT-1 X

X SP10A-PT-2 X

X SP10B-PT-1 X

X SP10B-PT-2 X

X DF-LS-244A DF-LS-244B RM-L-1 S

X X

S X

X Interlock to Close MU-V-2A/2B RC3A-PT-3 S

X P

X X

X P

X X

X Train A RC3A-PT-4 S

S X

S X

X Train B RC3B-PT-3 S

S S

X S

Train C BS-PT-282 X

X X

X X

X X

X X

X X

X X

X Train A BS-PT-285 X

X X

X X

X X

S X

S Train B BS-PT 288 X

X S

S X

X X

X Train C BS-PS-932 X

X X

S S

S S

S X

Train A BS-PS-933 X

X X

S S

X S

Train B BS-PS-934 X

X X

S S

S S

S S

X Train C BS-PS-935 X

S S

S S

X Train A BS-PS-936 X

S S

S X

Train B BS-PS-937 X

S S

S X

Train D IC-LT-802 S

X X

X X

X X

Train A. ICCW Tank Level Only IC-LT-803 X

X X

X X

X Train B. ICCW Tank Level Only BS-PS-283 X

X X

X X

X X

X X

Auto Start for BS-P-1A BS-PS-286 X

X X

X X

X X

X X

Auto Start for BS-P-1A BS-PS-289 X

X X

X X

X X

X X

Auto Start for BS-P-1A

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 7a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

BS-PS-284 X

X X

X Auto Start for BS-P-1B BS-PS-287 X

X X

X Auto Start for BS-P-1B BS-PS-290 X

X X

X Auto Start for BS-P-1B IM-SPND-5, 31, 34, 52 (BIRO)

X X

Train A IM-SPND-3, 4, 9, 24 (BIRO)

X X

Train B IM-SPND-12, 13, 21, 38 (BIRO)

X X

Train C IM-SPND-17, 42, 48, 49 (BIRO)

X X

Train D MJ-FT-1126 S

X X

X X

X X

X X

Train A MU-FT-1127 S

X X

X X

X X

X X

Train A MU-FT-1128 X

S X

X X

X Train B MU-FT-1129 X

S X

X X

X Train B

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 NI-11 X

P X

p Train A NI-12 P

X X

X P

P Train B -Control Room & RSD RC4A-TE-1 P

X X

X X

Train X RC4A-TE-4 X

X X

X Train X RC4B-TE-1 X

X X

X Train X RC4B-TE-4 X

X X

X Train X RC-TE-958 X

X X

X X

X Train A - Control Room & RSD RC-TE-960 X

P P

Train B - Control Room & RSD RC5A-TE-2 P

X X

X Train X RC5A-TE-4 P

X X

X Train X RC5B-TE-2 X

X X

Train X RC5B-TE-4 X

X X

X Train X RC-TE-959 X

X X

X X

X X

Train A - Control Room & RSD RC-TE-961 X

P P

Train B - Control Room & RSD RC3A-PT3 P

X X

X X

X X

Train A RC-PT-963 X

X X

X X

X Train A - RSD Only RC-PT-949 X

P P

P Train B - Control Room & RSD RC1-LT-1 X

X X

Train X RC1-LT-3 P

P P

Train X RC-LT-777 X

S X

X X

Train B - Control Room & RSD RC2-TE-1 X

X P

X X

Train X RC2-TE-2 P

X P

X P

Train B FW-LT-775 P

P P

P P

P Train A - Control Room & RSD FW-LT-789 X

X X

Train B - Control Room & RSD FW-LT-788 X

X X

Train A - Control Room & RSD

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 2b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 FW-LT-776 P

P Train B - Control Room & RSD SP6A-PT-1 P

X X

X Train X - Also for MS-V-3D, E, F SP6A-PT-2 P

X X

X Train X - Also for MS-V-3D, E, F MS-PT-950 P

D P

P P

Train A - Control Room & RSD MS-PT-1180 X

X X

X X

Train B SP6B-PT-1 P

X X

Train X - Also for MS-V-3A, B, C SP6B-PT-2 P

X X

Train X - Also for MS-V-3A, B, C MS-PT-951 P

D P

P Train B - Control Room & RSD MS-PT-1184 X

X X

X X

Train A DH-DPT-802 X

X Train A - Control Room & RSD DH-DPT-803 X

Train B - Control Room & RSD DH-FI-299A Train A - Local Indication DH-FI-299B Train B - Local Indication DH2-TE-1 X

X X

Train A - Control Room & RSD DH2-TE-2 X

X X

Train B - Control Room & RSD DH6-TE-1 X

X X

Train A - Control Room & RSD DH6-TE-2 X

X X

Train B - Control Room & RSD CO-LI-1004 Local Indication CO-LI-1005 Local Indication MU14-LT X

X X

Train X MU-LT-778 X

Train B - Control Room & RSD DH-LT-808 X

X X

Train A - Control Room & RSD DH-LT-809 P

X Train B - Control Room & RSD EF-FT-788 X

X X

Train B - Control Room & RSD EF-FT-779 X

X X

X Train C - Control Room & RSD

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 3b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 EF-FT-782 X

X X

Train B - Control Room & RSD EF-FT-791 X

X X

X Train C - Control Room & RSD FW-LT-1044 (1)

X X

X X

X HSPS-Not required.

FW-LT-1040 (2)

X X

X X

HSPS-Not required.

FW-LT-1045 (3)

X X

X X

HSPS-Not required.

FW-LT-1041 (4)

X X

X X

HSPS-Not required.

FW-LT-1046 (1)

X X

X X

X HSPS-Not required.

FW-LT-1042 (2)

X X

X X

HSPS-Not required.

FW-LT-1047 (3)

X X

X X

HSPS-Not required.

FW-LT-1043 (4)

X X

X X

HSPS-Not required.

FW-LT-1052 (1)

X X

X X

HSPS-Required in CB-FA-3b.

FW-LT-1048 (2)

X X

X HSPS-Not required.

FW-LT-1053 (3)

X X

X X

HSPS-Not required.

FW-LT-1049 (4)

X X

X HSPS-Not required.

FW-LT-1054 (1)

X X

X X

HSPS-Not required.

FW-LT-1050 (2)

X X

X HSPS-Not required.

FW-LT-1055 (3)

X X

X X

HSPS-Not required.

FW-LT-1051 (4)

X X

X HSPS-Not required.

CO-LT-1060 (1)

X X

X X

X X

HSPS-Not required.

CO-LT-1061 (2)

X X

X X

HSPS-Not required.

CO-LT-1062 (1)

X X

X X

X X

HSPS-Not required.

CO-LT-1063 (2)

X X

X X

HSPS-Not required.

MS-PT-950 (1)

P D

P P

MS-PT-1180 (2)

X X

X X

X HSPS-Not required.

MS-PT-1182 (3)

X X

X X

X HSPS-Not required.

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 4b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 MS-PT-1181 (4)

X X

X X

X HSPS-Not required.

MS-PT-1184 (1)

X X

X X

X HSPS-Not required.

MS-PT-951 (2)

P D

P P

MS-PT-1185 (3)

X X

X X

X HSPS-Not required.

MS-PT-1183 (4)

X X

X X

X HSPS-Not required.

FW-TE-1046 (1)

X X

X X

X X

X X

HSPS-Not required.

FW-TE-1044 (2)

X X

X X

X X

HSPS-Not required.

FW-TE-1047 (3)

X X

X X

X X

HSPS-Not required.

FW-TE-1045 (4)

X X

X X

X X

HSPS-Not required.

FW-TE-1050 (1)

X X

X X

X X

X X

HSPS-Required in CB-FA-3b.

FW-TE-1048 (2)

X X

X X

X X

X HSPS-Not required.

FW-TE-1051 (3)

X X

X X

X X

X HSPS-Not required.

FW-TE-1049 (4)

X X

X X

X X

X HSPS-Not required.

IC5-DPT X

X X

IC9-TE X

X X

X X

Interlock to Close MU-V-1A/1B MU5-TE X

X X

Interlock to Close MU-V-3 MU42-DPT X

X X

Auto Control for MU-V-32 RC3A-PT-1 P

X X

X X

X X

SP10A-PT-1 X

SP10A-PT-2 X

SP10B-PT-1 X

SP10B-PT-2 X

DF-LS-244A X

DF-LS-244B X

RM-L-1 X

X X

Interlock to Close MU-V-2A/2B

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 5b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 RC3A-PT-3 P

X X

X X

X X

Train A RC3A-PT-4 X

X X

X X

X Train B RC3B-PT-3 X

X X

X Train C BS-PT-282 X

X X

X X

X X

Train A BS-PT-285 X

X X

Train B BS-PT-288 X

X X

Train C BS-PS-932 X

X X

Train A BS-PS-933 X

X X

Train B BS-PS-934 X

X X

Train C BS-PS-935 X

X Train A BS-PS-936 X

X Train B BS-PS-937 X

X Train D IC-LT-802 X

X X

Train A; ICCW Tank Level Only IC-LT-803 X

X Train B; ICCW Tank Level Only BS-PS-283 X

X Auto Start for BS-P-1A BS-PS-286 X

X Auto Start for BS-P-1A BS-PS-289 X

X Auto Start for BS-P-1A BS-PS-284 X

X X

Auto Start for BS-P-1B BS-PS-287 X

X X

Auto Start for BS-P-1B BS-PS-290 X

X X

Auto Start for BS-P-1B IM-SPND-5, 31, 34, 52 (BIRO)

X X

X F

F F

F F

F F

Train A IM-SPND-3, 4, 9, 24 (BIRO)

X X

X F

F F

F F

F F

Train B IM-SPND-12, 13, 21, 38 (BIRO)

X X

X F

F F

F F

F F

Train C

ATTACHMENT 3-5P APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 6b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air F - One or Other is Available Rev. 27 INSTRUMENTATION AND CONTROLS D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T Y

G G

H H

H H

H H

B B

B B

B B

B B

S S

S S

B B

B B

B B

B B

A P

P P

P R

F F

F F

F F

F F

F F

F F

F F

F F

H H

H H

F F

F F

F F

F F

D A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 IM-SPND-17, 42, 48, 49 (BIRO)

X X

X F

F F

F F

F F

Train D MU-FT-1126 X

X Train A MU-FT-1127 X

X Train A MU-FT-1128 X

X Train B MU-FT-1129 X

X Train B

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1a LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker Note 2:

Signal conditioning cabinet B3 is not available in CB-FA-2b.

M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room T1

- Crosstie 1P and 1S 480V Switchgear T2

- Crosstie 1A and 1B DC Panels Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

EE-SWG-4160V-1D X

X X

S X

S X

X Train A EE-SWG-4160V-1E P

X X

S X

R S

D R

S D

R S

D Train B EG-Y-1A X

X P

X S

X P

X X

X Train A EG-Y-1B P

X S

S P

X R

S D

R S

D R

S D

Train B EE-SWG-480V-1P X

X P

X S

X P

X X

X Train A EE-SWG-480V-1S P

X X

P X

X R

S D

R S

D R

S D

Train B EE-SWG-480V-1R X

X X

X S

X P

X X

X Train A EE-SWG-480V-1T X

P X

X X

P X

X R

S D

R S

D R

S D

Train B EE-MCC-ES-1A X

X X

S S

S X

X Train A EE-MCC-ES-1B X

X P

X S

R S

D R

S D

R S

D Train B EE-MCC-ESV-1A X

X X

X S

S S

S S

S Train A EE-MCC-ESV-1B X

X P

X S

S S

R S

D R

S D

R S

D Train B EE-MCC-ESV-1C-EX1 (1C ESV MCC Transfer Switch)

X P

X R

S D

R S

D R

S D

R S

D Train C EE-MCC-ESV-1C P

X S

R S

D R

S D

R S

D Train C EE-MCC-SH-1A X

X X

S S

X S

X X

Train A

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 2a LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker Note 2:

Signal conditioning cabinet B3 is not available in CB-FA-2b.

M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room T1

- Crosstie 1P and 1S 480V Switchgear T2

- Crosstie 1A and 1B DC Panels Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

EE-MCC-SH-1B X

X X

X P

X S

R S

D R

S D

R S

D Train B EE-PNL-ATA X

X S

Train X EE-PNL-ATB X

X S

Train X EE-PNL-VBA X

T2 X

S T2 T2 T2 T2 Train A EE-PNL-VBB P

T2 S

X S

T2 Train B EE-PNL-VBC X

T2 X

S T2 T2 T2 T2 Train C EE-PNL-VBD P

T2 S

X S

T2 Train D EE-INV-1A X

T2 X

S T2 T2 T2 T2 Train A EE-INV-1B P

T2 X

X S

T2 Train B EE-INV-1C X

T2 X

S T2 T2 T2 T2 Train C EE-INV-1D P

T2 X

X S

T2 Train D EE-INV-1E (Note 1)

X T2 X

S S

S S

S Train C EE-INV-1F S

X S

Train B or D EED-BC-1A X

X X

S S

S S

S Train A EED-BC-1B P

X X

S S

Train B EED-BC-1C X

X X

S S

S S

S Train C EED-BC-1D P

X X

S S

Train D EED-PNL-1A X

T2 X

X T2 T2 T2 T2 Train A EED-PNL-1B P

T2 X

X T2 Train B EED-PNL-1M X

X X

X X

Train C EED-PNL-1E X

X S

Train A EED-PNL-1F P

X S

Train B EED-PNL-1P X

X S

Train A EED-PNL-1Q P

X S

Train B

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 3a LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker Note 2:

Signal conditioning cabinet B3 is not available in CB-FA-2b.

M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room T1

- Crosstie 1P and 1S 480V Switchgear T2

- Crosstie 1A and 1B DC Panels Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

EE-PNL-TRA X

X X

X S

S S

S S

Train X EE-PNL-TRB X

X X

X S

S Train X SCC-A1, A2, A3 S

X P

X S

X Train A SCC-B1, B2, B3 X

X S

Train B (Note 2)

RSP-A S

X S

S X

Train A; RSD RSP-B S

X S

S Train B; RSD RSTSP-A X

X X

X X

R S

D R

S D

Train A, X; RSD RSTSP-B X

X R

S D

R S

D R

S D

Train B, C, X; RSD RSTSP-C X

X X

R S

D R

S D

R S

D Train C; RSD ESAS Bistable Cabinets S

X S

X X

ESAS Relay Cabinets A

S X

X S

X X

ESAS Defeat A S

S S

S X

X X

X X

ESAS Relay Cabinets B

B X

B X

B S

X X

ESAS Defeat B S

S S

X X

X X

Emergency Control Room Lighting (AC)

X X

S S

S S

S X

X Train A: EED-PNL-CT-2 (Upper)

Normal Control Room Lighting (AC)

X X

S S

S X

S X

X Train B: EED-PNL-CT-2 (Lower)

Emergency Control Room Lighting (DC)

S S

X S

X X

Train C: EED-PNL-1M FS-PNL-CB-1 (CARDOX)

O Train X. O = Open CT-5 Switch 32 at 1A ES MCC Unit 8A

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1b LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T G

G H

H H

H H

H B

B B

B B

B B

B S

S S

S B

B B

B B

B B

B P

P P

P F

F F

F F

F F

F F

F F

F F

F F

F H

H H

H F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 EE-SWG-4160V-1D X

Train A EE-SWG-4160V-1E X

Train B EG-Y-1A X

Train A EG-Y-1B X

Train B EE-SWG-480V-1P S

Train A EE-SWG-480V-1S S

Train B EE-SWG-480V-1R S

X X

X P

Train A EE-SWG-480V-1T S

P X

X P

X Train B EE-MCC-ES-1A S

Train A EE-MCC-ES-1B S

Train B EE-MCC-ESV-1A S

X X

Train A EE-MCC-ESV-1B S

X Train B EE-MCC-ESV-1C-EX1 (1C ESV MCC Transfer Switch)

Train C EE-MCC-ESV-1C X

P Train C EE-MCC-SH-1A S

X X

X P

Train A EE-MCC-SH-1B S

P X

X P

X Train B EE-PNL-ATA Train X EE-PNL-ATB Train X EE-PNL-VBA T1 Train A EE-PNL-VBB T1 Train B EE-PNL-VBC T1 Train C EE-PNL-VBD T1 Train D EE-INV-1A T1 Train A EE-INV-1B T1 Train B

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 2b LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T G

G H

H H

H H

H B

B B

B B

B B

B S

S S

S B

B B

B B

B B

B P

P P

P F

F F

F F

F F

F F

F F

F F

F F

F H

H H

H F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 EE-INV-1C T1 Train C EE-INV-1D T1 Train D EE-INV-1E (Note 1)

T1 Train C EE-INV-1F Train B EED-BC-1A T1 Train A EED-BC-1B T1 Train B EED-BC-1C T1 Train C EED-BC-1D T1 Train D EED-PNL-1A T1 Train A EED-PNL-1B T1 Train B EED-PNL-1M Train C EED-PNL-1E Train A EED-PNL-1F Train B EED-PNL-1P X

Train A EED-PNL-1Q X

Train B EE-PNL-TRA S

X X

Train X EE-PNL-TRB S

X X

Train X SCC-A1, A2, A3 Train A SCC-B1, B2, B3 Train B RSP-A Train A; RSD RSP-B Train B; RSD RSTSP-A Train A, X; RSD RSTSP-B Train B, C, X; RSD RSTSP-C Train C; RSD ESAS Bistable Cabinets

ATTACHMENT 3-5Q APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 3b LEGEND X - Component Not Available D

- Design Modification Note 1:

For fire areas where the DC cross tie (T2) is used to energize Train A, manual action is taken to lockout inverter 1E.

S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air B - Use ES Bypass in Control Room Rev. 27 AUXILIARY ELECTRICAL POWER SYSTEM D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T G

G H

H H

H H

H B

B B

B B

B B

B S

S S

S B

B B

B B

B B

B P

P P

P F

F F

F F

F F

F F

F F

F F

F F

F H

H H

H F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 ESAS Relay Cabinets A

ESAS Defeat A ESAS Relay Cabinets B

ESAS Defeat B Emergency Control Room Lighting (AC)

S X

X Train A: EE-PNL-CT-2(Upper)

Normal Control Room Lighting (AC)

S Train B: EE-PNL-CT-2(Lower)

Emergency Control Room Lighting (DC)

X Train C: EED-PNL-1M FS-PNL-CB-1 (CARDOX)

X Train X. O = Open CT-5 Switch 32 at 1A ES MCC Unit 8A.

ATTACHMENT 3-5R APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1a LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air Rev. 27 INSTRUMENT AIR A

A A

A A

A A

A A

A A

A A

A A

A A

A C

C C

C C

C C

C C

C C

C C

C C

C B

B B

B B

B B

B B

B B

B B

B B

B I

I B

B B

B B

B B

B B

B B

B B

B B

B T

T F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z F

F A

A A

A A

A A

A A

A A

A A

A Z

Z Z

Z 1

2 1

2 2

2 3

4 5

6 6

7 8

9 1

1 1

2 2

2 2

2 2

2 3

3 3

3 4

4 5

5 COMPONENTS a

b c

a 0

1 1

1 a

b c

d e

f g

a b

c d

a b

a b

REMARKS a

IA-P-1A X

X X

S S

S X

X IA-P-1B X

X X

S X

S S

R S

D R

S D

Normal Instrument Air Line (Copper)

X X

X X

X X

X X

X X

2-Hour Backup Instrument Air System Steel Tubing; Except at Valve Location (Copper)

ATTACHMENT 3-5R APPENDIX R EVALUATION REPORT - THREE MILE ISLAND UNIT 1 COMPONENT AVAILABILITY FOR A FIRE IN FIRE AREA/ZONE SHEET 1b LEGEND X - Component Not Available D

- Design Modification S - Support Not Available RSD - Remote Shut Down P - Available-Cable Protected O

- Open Switch or Breaker M - Available-Manual Operation R

- Repair A - Manual Op. Due to Loss of Inst. Air Rev. 27 INSTRUMENT AIR D

D F

F F

F F

F I

I I

I I

I I

I I

I I

I R

R R

R R

R R

T G

G H

H H

H H

H B

B B

B B

B B

B S

S S

S B

B B

B B

B B

B P

P P

P F

F F

F F

F F

F F

F F

F F

F F

F H

H H

H F

F F

F F

F F

F A

A Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

Z Z

A F

F F

F 1

2 1

2 3

4 5

6 1

2 3

4 5

6 7

8 A

Z Z

Z 1

1 1

1 1

2 3

1 COMPONENTS a

b c

d e

REMARKS 2

1 2

3 IA-P-1A S

X X

X X

IA-P-1B S

X X

S X

X Normal Instrument Air Line (Copper)

X X

X X

X X

X X

X X

X X

X X

X X

2-Hour Backup Instrument Air System X

X X

Steel Tubing; Except at Valve Location (Copper)