ML18106B162
| ML18106B162 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 04/09/1999 |
| From: | Blough A NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | Keiser H Public Service Enterprise Group |
| References | |
| NUDOCS 9904160191 | |
| Download: ML18106B162 (26) | |
Text
Mr. Harold W. Keiser President and Chief Nuclear Officer Nuclear Business Unit April 9, 1999 Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038
SUBJECT:
PLANT PERFORMANCE REVIEW - SALEM On February 10, 1999, the NRC staff completed a Plant Performance Review (PPR) of the Salem Generating Station. The staff conducts these reviews for all operating nuclear power plants to develop an integrated understanding of safety performance. The results are used by NRC management to facilitate planning and allocation of inspection resources. PPRs examine information since the last assessment of licensee performance to evaluate long term trends, but emphasize the last six months to ensure that the assessments reflect current performance.
PPRs also provide NRC management with a current summary of licensee performance and serve as inputs to the NRC's senior management meeting (SMM) reviews. The PPR for Salem involved the participation of all technical divisions in a detailed evaluation of inspection results and safety performance information for the period of April 1998 through January 1999. The NRC's most recent summary of licensee performance was provided in a letter of September 15, 1998, and was discussed in a public meeting with you on September 30, 1998.
As discussed in the NRC's Administrative Letter 98-07 of October 2, 1998, the PPR provides an assessment of licensee performance during an interim period that the NRC has suspended its Systematic Assessment of Licensee Performance (SALP) program. The NRC suspended its SALP program to complete a review of its processes for assessing performance at nuclear power plants. At the end of the review period, the NRC will decide whether to resume the SALP program or terminate it in favor of another process. The NRC plans to maintain direct communication with you on assessed plant performance on a minimum frequency of two years.
- This will include a meeting open to public observation to be scheduled by my staff. Additionally, your facility was-selected to be a pilot plant for the new reactor oversight process. We will notify you of any associated changes to planned inspections by separate correspondence iri the near future. Discussed below please find an operational history summary from this assessment period followed by our assessment of plant performance derived from the PPR process.
During this assessment period, Salem Unit 1 restarted in April 1998 from an extended shutdown and operated continuously until February 28, 1999, when the inadvertent draining of turbine lube oil led to a reactor trip. Salem Unit 2 had three forced outages, totaling four weeks, to address emergent equipment problems related to service water, pressurizer safety valves, and a reactor coolant pump seal. Salem Unit 2 had no reactor.trips.
(' (
9904160191 990409 PDR ADOCK 05000272 G
- r. r, <\\ '>~ _:_
-\\ \\* \\ \\I \\_ -./
\\
Mr. Harold W. Keiser Salem Generating Station 2
Overall performance at the Salem station was acceptable. Given the significant challenges PSE&G faced in recovering both units from extended shutdowns, operational results were sound, and management demonstrated that high standards were in place. However, a number of operational events resulted from personnel errors, including two declared Unusual Events involving a reactor coolant system leak and a loss of control room annunciators. Some work execution problems occurred that adversely impacted equipment operability, further highlighting human performance inconsistencies. Material condition of the plant was generally good.
Although the number of items in the corrective maintenance work backlog declined somewhat, it remained large and continued to be an area of active management involvement. Engineering supported day-to-day operations effectively. Management oversight was strong and included critical review of ongoing plant activities. Plant problems were promptly identified and corrected, and the corrective action program continued to be effective. Self-assessment activities were thorough and self-critical.
Overall, the plants were operated well, with one reactor trip between the two plants. Operating personnel exhibited high operational standards and a sound safety ethic, including conservative decision making, generally effective command of control room activities, and good teamwork.
Control room deficiencies and operator workarounds were appropriately tracked to resolution with the overall number at a reasonably low level. Following the exten,ded outages, operators performed well returning the units to normal operation and during subsequent routine and transient operations. However, in December 1998 a reactor coolant system leak developed during a startup from a Unit 2 forced outage as a result of weak control room supervision, an inadequate procedure and an operator error. Also, a Unit 1 reactor trip resulted from improper draining of turbine lube oil due to unfamiliarity with operation of an isolation valve. Because Salem is one of the voluntary pilot plants for the NRC's new assessment program, the associated baseline inspection program. (being developed) will affect inspections beginning in June 1999. Until then, we plan to perform the normal NRC core inspection with emphasis on your corrective actions to prevent personnel errors.
Maintenance activities continued to be performed acceptably. The material condition of the plant was good, as evidenced by generally uneventful plant operation. Maintenance Rule implementation was appropriate and risk assessments for on-line work were sound. However, the backlog of corrective maintenance activities remained large. On occasion, equipment operability was impacted by work execution problems. While this is a continuing issue, the errors did.not typically result in plant transients (e.g., the loss of control room overhead annunciators). The organization, however, remained challenged by problems in the maintenance work control process, by the large backlog of corrective maintenance activities, and by frequent unplanned equipment outages resulting in technical specification action statement entries. We plan to perform the normal NRC core inspection with additional emphasis on work control. The new baseline inspection program will affect inspections beginning in June 1999.
Strong oversight of station engineering activities was evident with notable improvements in the implementation of engineering programs. Engineering support of plant operations was good, and the performance of maintenance and system engineering functions also improved. Design engineering activities were performed acceptably, although some problems. were found involving
Mr. Harold W. Keiser Salem Generating Station 3
design evaluations. Resolutions associated with identified problems were generally appropriate, though a longstanding fire wrap issue was still being addressed. Backlog reduction efforts continued. We plan to perform the normal NRC core inspection with emphasis on backlog reduction. In addition, an initiative inspection is planned to review progress on the fire wrap issue. The baseline inspection program also will affect inspections beginning in June 1999.
Performance in the plant support areas continued to be good. Radiological protection programs were strong, including control of high radiation areas, training and radwaste transportation.
PSE&G maintained and implemented the radiological environmental monitoring program well, though minor procedural deficiencies existed in sample collection processes. Plant security programs continued to be appropriately implemented and maintained. Station performance in emergency preparedness was generally good, though the emergency classification of the December 1998 Unusual Event was not timely. We plan to perform the normal NRC core inspection. The baseline inspection program will affect inspections beginning in June 1999. contains a historical listing of plant issues, referred to as the Plant Issues Matrix (PIM), that were considered during this PPR process to arrive at an integrated view of performance trends. You will find that the PIM is in two different formats due to a program change that was effective on October 1, 1998. The PIM includes only items from inspection reports or other docketed correspondence between the NRC and Public Service Electric and Gas Company. The NRC does not attempt to document all aspects of licensee programs and performance that may be functioning appropriately. Rather, the NRC only documents issues that the NRC believes warrant management attention or represent noteworthy aspects of performance. In addition, the PPR may also have considered some predecisional and draft material that does not appear in the attached PIM, including observations from events and inspections that have occurred since the last NRC inspection report was issued, but had not yet received full NRC review and consideration. This material will be placed in the PDR as part of the normal issuance of NRC inspection reports and our other correspondence.
This letter advises you of our planned inspection effort resulting from the PPR. It is provided to minimize the resource impact on your staff and to allow for scheduling conflicts and personnel availability fo be resolved in advance of inspector arrival onsite. Enclosure 2 details our inspection plan for the next few months, beyond which the pilot program will address. The rationale or basis for each inspection outside the core inspection program is provided so that you are aware of the reason for emphasis in these program areas. Resident inspections are not listed due to their ongoing and continuous nature.
Mr. Harold W. Keiser Salem Generating Station 4
We will inform you of any changes to the inspection plan. If you have any questions, please contact Mr. Glenn Meyer at (610) 337-5211.
Docket No. 50-354 License No. NPF-57
Enclosures:
Plant Issues Matrix Inspection Plan cc w/encl:
Sincerely, Original Signed By:
A. Randolph Blough, Director Reactor Projects Branch 3 Division of Reactor Projects L. Storz, Senior Vice President - Nuclear Operations E. Simpson, Senior Vice President - Nuclear Engineering E. Salowitz, Director - Nuclear Business Support A. F. Kirby, Ill, External Operations - Nuclear, Delmarva Power & Light Co.
D.Garchow, Acting General Manager - Salem Operations J. McMahon, Director - QA/Nuclear Training/Emergency Preparedness D. Powell, Director, Licensing, Regulation and Fuels R. Kankus, Joint Owner Affairs A. Tapert, Program Administrator J. J. Keenan, Esquire M. J. Wetterhahn, Esquire J. A. Isabella, Manager, Joint Generation Atlantic Electric Consumer Advocate, Office of Consumer Advocate William Conklin, Public Safety Consultant, Lower Alloways Creek Township Public Service Commission of Maryland State of New Jersey State of Delaware Institute for Nuclear Power Operations (INPO)
Mr. Harold W. Keiser Salem Generating Station Distribution w/encl:
Region I Docket Room (with concurrences)
Nuclear Safety Information Center (NSIC)
NRC Resident Inspector PUBLIC H. Miller, RA/J. Wiggins, DRA A. Blough, Director, DRP R. Crlenjak, Deputy Director, DRP W. Lanning, Director, DRS W. Ruland, Deputy Director, DRS G. Meyer, DRP L. Harrison, PRP C. O'Daniell, DRP L. Prividy, DRS Distribution w/encl: (Via E-Mail)
W. Travers, EDO S. Collins, NRR J. Zwolinski, NRR B. Boger, NRR T. Boyce, NRR M. Tschiltz, OEDO E. Adensam, NRR P. Milano, PDl-2, NRR T. Madden, OCA Inspection Program Branch, NRR (IPAS)
R. Correia, NRR DOCDESK 5
DOCUMENT NAME: G:\\BRANCH3\\2-SAL\\PPR\\L TR-399.WPD To receive a copy of this document, indicate in the box: "C" = Copy without attachment/enclosure "E" = Copy with attachment/enclosure "N" = No copy OFFICE Rl/DRP Rl/DRP Rl/DRP NAME LHarrison DATE 04/08/99 04/ /99 04/ /99
Page: 1of6 United States Nuclear Regulatory Commission Date: 04/06/1999 Time: 08:24:47 Region PLANT ISSUE MATRIX SALEM By Primary Functional Area Functional Template Date*
Source Area ID Type Codes Item Description 12/21/1998 1998011 Pri: OPS NRC POS Pri: 1A Observed operator performance was generally good. Operators responded promptly and appropriately to the Sec:
Sec:3A unplanned trip of a Unit 2 steam generator feed pump. Additionally, Unit 2 shutdown activities to make repairs to the No. 21 reactor coolant pump seal were well controlled.
Ter:
12/21/1998 1998011 Pri: OPS NRC POS Pri: 5B Operational Experience department personnel reviewed the selected NRC and industry communications in a timerc Sec:
Sec:
manner, and thoroughly communicated the information to the appropriate station departments. PSE&G's actions or selected risk-significant NRC communications were effective.
Ter:
e 11/19/1998 1998009 Pri: OPS NRC NEG Pri: 2B Inadequate procedure guidance resulted in the inadvertent actuation of engineered safety features equipment during Sec:
Sec:
surveillance testing. PSE&G's corrective actions to address this event were adequate. (Reference LER 50-311/98-11)
Ter:
11/19/1998 1998009 Pri: OPS NRC NEG Prl: 2B The main coolant system leak air particulate monitor was not functional for about five days, which was not known by Sec:
Sec: 5A PSE&G personnel. Although the monitor is not safety-related, this event demonstrated weak control of important to safety equipment status.
Ter:
11/19/1998 1998009 Pri: OPS NRC NEG Pri: 38 Operator misinterpretation of procedural ~uidance resulted in an inoperable control room emergency air conditioning Sec:
Sec:2B system train. PSE&G's immediate and panned corrective actions for this event were adequate. (Reference LER 50-272/98-13)
Ter:
11/19/1998 1998009 Pri: OPS NRC POS Pri: 1A Observed operator performance was generally good. The decision to isolate the Unit 1 and 2 positive displacement Sec:3A pumps during an evaluation of emergency core cooling system leakage outside containment was conservative. The Sec:
detection of the No. 23 steam generator tube leak showed good attention to detail, and PSE&G's actions in response -
Ter: 3B the leak were reasonable.
11/19/1998 1998009 Pri: OPS NRC POS Pri: 5B The Station Operations Review Committee continued to provide effective oversight of Salem operations and the Corrective Action Review Board appropriately challenged the quality of corrective actions for previously identified Sec:
Sec:5C issues. There was a need to provide expectations to board presenters to ensure all necessary information was Ter:
available for discussion.
10/05/1998 1998008 Pri: OPS NRC NEG Pri: 3A Control room operators were slow to identify improperly established control rod insertion limit monitor setpoints.
Sec:
Sec:
PSE&G's corrective actions to address this self-identified issue were adequate.
Ter:
10/05/1998 1998008 Pri: OPS NRC POS Pri: 1A Operator performance during routine control room observations and plant tours was generally good. Plant equipment responded as designed during two unplanned events, specifically a loss of the 2A 4160 VAC vital bus and the trip of the Sec:
Sec:2A no. 12 steam generator feed pump.
Ter: 3A Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
Page:
2 of 6 United States Nuclear Regulatory Commission Date: 04/06/1999 Time: 08:24:47 Region PLANT ISSUE MATRIX SALEM By Primary Functional Area Functional Template Date Source Area ID Type Codes Item Description 10/05/1998 1998008 Pri: OPS NRC POS Pri: 28 Operators properly implemented.PSE&G's technical specification required "Primary Coolant Sources Outside Sec:
Sec: 1C Containment" program and promptly initiated corrective actions when conditions were identified which challenged the acceptable leakage limits established therein. The program itself was adequate with only one minor issue involving Ter: 48 program implementation identified. An operability determination developed to account for plant leakage determined to be in excess of program requirements had a sound basis. (Ref: LER 50-311 /98-1 O) 10/05/1998 1998008 Pri: OPS NRC POS Pri: 38 Operators demonstrated good performance during the conduct of a periodic requalification exam scenario ir: the control Sec:
Sec:
room simulator. Examiners were objective and completed a critical assessment of individual and crew performance.
Ter:
e 12/21/1998 1998011-01 Pri: MAINT NRC VIOIV Pri: 3A PSE&G personnel failed to evaluate the potential impact of connecting non-safety-related test equipment on all four Sec:
Sec:39 operable channels of the reactor protection system, thereby potentially compromising the system's design bases.
Corrective actions for previous issues identified by the NRG involving the similar connections of temporary equipment to Ter:
operable safety-related s$stems were ineffective in preventing the occurrence of the event described in the subject licensee event report. P E&G's root cause evaluation thoroughly examined the issues. As a result, PSE&G personnel developed extensive corrective actions. A violation of 10 CFR 50, Appendix B, Grit. XVI, Corrective Action resulted.
(Ref. LER 50-272/98-15) 11/19/1998 1998009 Pri: MAINT NRC NEG Pri: 1C The multiple leak repairs performed on feedwater containment isolation valve 12BF22 demonstrated poor planning and Sec:
Sec:3A communications between departments, and weak management oversight. Additionally, overall communication with the NRC was weak considering the relative importance of the valve.
Ter: 3C 11/19/1998 1998009 Pri: MAINT NRC NEG Prl: 28 The 1A 1 125 volt DC battery charger was found to be inoperable due to an incorrect setting of the high voltage Sec:
shutdown relay, resulting in an unplanned entry into a seven-day technical specification action statement. The other Sec:
two Unit 1 chargers and one Unit 2 charger were also set incorrectly. This event was self-revealing, but had no safety Ter:
consequence, and corrective actions were adequate.
11/19/1998 1998009 Pri: MAINT NRG NEG Prl: 3A Inspectors noted several weaknesses in preventive maintenance activities performed on the 13 auxiliary feedwater Sec:
(AFW) pump. PSE&G documented these issues in action requests and immediate corrective actions were adequate. e Sec:
The 13 AFW pump surveillance test was adequate to test pump discharge pressure, and showed satisfactory results.
Ter:
11/19/1998 1998009 Pri: MAINT NRC NEG Pri: 3C The inspectors found that the backlog of outstanding corrective maintenance activities remained high and no significant Sec:s8 improvement had been made in reducing it. The inspectors concluded that the program has been slowly evolving and Sec:
required additional management oversight to ensure improvement. Performance indicators were useful and the Salem Ter: 5C Planning and Scheduling department had established an effective self-assessment program.
11/19/1998 1998009-03 Pri: MAINT NRC VIOIV Pri: 3A PSE&G implemented reasonable corrective actions for a self-revealing event involving a failure by maintenance Sec:
Sec:
technicians to restore the 22 auxiliary feed water pump discharge pressure transmitter to service following a calibration.
However, largely because of the repetitive nature of this issue, this failure resulted in a violation of technical Ter:
specification 6.8.1 for failure to implement procedures. (Reference LER 50-311/98-12)
Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
Page:
3 of 6 United States Nuclear Regulatory Commission Date: 04/06/1999 Time: 08:24:47 Region PLANT ISSUE MATRIX SALEM By Primary Functional Area Functional
_ Template Date Source Area ID Type Codes Item Description 12/21/1998 1998011-02 Pri: ENG NRG NCV Pri: 28 Following self-identification, PSE&G appropriately documented and corrected a deficiency involving the use of a Sec:
Sec:
non-safety-related spring charging motor in a safety-related circuit breaker, which resulted in a non-cited violation.
Ter:
11/19/1998 1998009 Pri: ENG NRG NEG Pri: 5C The licensee's response to a question associated with the potential for age-related seal failures of C02 valves was Sec:
Sec:
weak. The licensee was slow in addressing this issue, which was first identified at Hope Creek in September 1997.
When the licensee confirmed the applicability of this failure to Salem, the licensee did not assure that the C02 valves Ter:
would perform as designed. Subsequent to NRC questioning, the licensee developed an analysis that provided the e bases _for assuring that the valv~s w_ould perfo.1"!11 as designed.. The licensee indicated t~at steps had been !nitiated to expedite replacement and examination of add1t1onal valves during the next work week window. Although this action appeared reasonable, this issue was left unresolved pending NRG review of the results of the licensee's examination of these valves.
11/19/1998 1998009 Pri: ENG NRG POS Pri: 2A PSE&G personnel were adequately monitoring EOG reliability under the requirements of 1 O CFR 50.65.
Sec:
Sec:
Ter:
11/19/1998 1998009 Pri: ENG NRG POS Pri: 3A Current system engineering procedures contained sufficient guidance for the proper implementation of the system Sec:
Sec:29 engineering monitoring program. System engineers continued to operate partly in a reactive mode, despite the establishment of a maintenance engineering group. However, clear areas of responsibility had been established and Ter:
the system engineers were assuming system responsibility. Also, a system engineering master plan was underway to further strengthen the role of the system engineer and to better manage work activities. Communications with maintenance engineering and operations were good_
11/19/1998 1998009 Pri: ENG NRC POS Pri: 38 The Salem system engineering staff included a nucleus of knowledgeable system engineers with several years of Sec:
Sec:49 nuclear experience. System experience was limited at times, but engineers indicated strong willingness to seek guidance from more experienced personnel. Individual system training was acceptable. The system performance Ter:
review meetings were good management tools to evaluate individual knowledge of the systems and to impart integrated insights on the systems.
11/19/1998 1998009 Pri: ENG NRC POS Pri: 3C Improved management oversight of the corrective action program was evident. Engineering self-assessments and Sec:
quality assurance reviews provided valuable insights.
Sec:
Ter:
11/19/1998 1998009 Pri: ENG NRG POS Pri: 5C PSE&G was actively engaged in the resolution of concerns raised by the NRG regarding spent fuel pool cooling design Sec:
Sec:
and decay heat load management, and has implemented a reasonable approach to completing these activities prior to the next core off-load.
Ter:
11/19/1998 1998009 Pri: ENG NRG POS Pri: 5C The licensee continued to experience reliability and availability problems with radiation monitors at both Salem Units.
Sec:
Sec:59 However, appropriate steps were being taken to address the instrument failures. The root cause analysis multi-disciplinary team showed good understanding of the issues involved. Good management support of the effort was Ter:
also evident.
Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
Page:
4 of 6 United States Nuclear Regulatory Commission Date: 04/06/1999 Time: 08:24:47 Region PLANT ISSUE MATRIX SALEM By Primary Functional Area Functional Template Date Source Area ID Type Codes Item Description 10/05/1998 1998008 Pri: ENG NRC MISC Pri:4c PSE&G had a reasonable Year 2000 program in place with a dedicated manager and appropriate senior management involvement.
Sec:
Sec:
Ter:
10/05/1998 1998008 Pri: ENG NRC POS Pri: 28 Periodic system manager development of maintenance rule category a(1) system health reports was a good initiative to Sec:4c provide an overall assessment of system performance and to evaluate the effectiveness of performance improvement Sec:
initiatives for station management. However, the quality of the individual reports varied widely.
Ter:
e 10/05/1998 1998008 Pri: ENG NRC POS Pri:4A PSE&G adequately justified the installation of a design change which removed packing gland leak-off lines from several Sec: 3A pressurizer spray and relief system valves. Installation work in the field was good and post-installation testing was Sec:
acceptable. This modification effectively reduced reactor coolant system identified leakage into the pressurizer relief Ter:
tank.
12/21/1998 1998011 Pri: PLTSUP NRC POS Pri: 1C An effective radiation protection program has been established for controlling high, locked high and very high radiation areas, and planning and maintaining occupational exposures ALARA. Appropriate controls were implemented in Sec:
Sec:
radiation protection to support forced outage work in the Unit 2 containment.
Ter:
11/19/1998 1998009 Pri: PLTSUP NRC POS Pri: 1C PSE&G's emergency operations facility and Salem's technical support center were properly maintained. All necessary emergency equipment and pro~dures were adequately controlled.
Sec:
Sec:
Ter:
10/05/1998 1998008 Pri: PLTSUP NRC POS Prl: 1C PSE&G maintained effective radioactive liquid and gaseous effluent control programs in that: (1) the technical specification (TS) and offsite dose calculation manual (ODCM) requirements for reporting effluent releases and Sec:
Sec:
projected doses to the public were effectively implemented; and, (2) the ODCM contained sufficient specification, e Ter:
information, and instruction to acceptably implement and maintain the radioactive liquid and gaseous effluent control programs.
10/05/1998 1998008 Pri: PLTSUP NRC POS Pri: 1C PSE&G had generally established, implemented, and maintained an* adequate radiation monitoring system program with respect to electronic calibrations, radiological calibrations, system reliability, and tracking and trending.
Sec:
Sec:5A Ter:
10/05/1998 1998008 Pri: PLTSUP NRC POS Pri: 58 PSE&G implemented an effective quality control program to validate measurement results for radioactive effluent samples. PSE&G established and implemented an effective quality assurance audit of the radioactive effluent control Sec:
Sec:5A program.
Ter:
10/05/1998 1998008 Pri: PLTSUP NRC POS Pri: 5C Fire protection impairments were pro~erly identified and effectively managed to ensure timely resolution of the various degraded conditions. The backlog o impairment items was large, but was being aggressively reduced.
Sec:
Sec:
Ter:
Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
Page:
5 of 6 Region SALEM Date 10/05/1998 Source 1998008-11 Functional Area Pri: PLTSUP Sec:
ID NRC United States Nuclear Regulatory Commission PLANT ISSUE MATRIX Date: 04/06/1999 Time: 08:24:47 Type VIOIV Template Codes Pri: 28 Sec:
Ter:
By Primary Functional Area Item Description A violation was identified pertaining to a failure to calibrate Unit 1 R-18 liquid effluent monitor in accordance with established procedures. PSE&G's response to this problem was timely and appropriate.
Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
Page:
6 of 6 Type Codes:
8-u
- sii11etin CDR Construction DEV Deviation EEi Escalated Enforcement Item IFI Inspector follow-up item LER Licensee Event Report LIC Licensing Issue MISC Miscellaneous MV Minor Violation NCV NonCited Violation NEG Negative NOED Notice of Enforcement Discretion NON Notice of Non-Conformance P21 Part 21 POS Positive SGI Safeguard Event Report STR Strength
[URI Unresolved item lVIO Violation WK Weakness United States Nuclear Regulatory Commission PLANT ISSUE MATRIX By Primary Functional Area Legend Template Codes:
1A Normal Operations 1 B Operations During Transients 1 C Programs and Processes 2A Equipment Condition 28 Programs and Processes 3A Work Performance 38 KSA 3C Work Environment 4A Design 48 Engineering Support 4C Programs and Processes 5A Identification 58 Analysis 5C Resolution
~------------------------------
10 Codes:
l'fRC NRC Self Self-Revealed Licensee Licensee Functional Areas:
- ops*---- **-operations MAINT Maintenance ENG Engineering PL TSUP Plant Support OTHER Other Date: 04/06/1999 Time: 08:24:47 EEis are apparent violations of NRC Requirements that are being considered for escalated enforcement action in accordance with the "General Statement of Policy and Procedure for NRC Enforcement Action" (Enforcement Policy), NUREG-1600. However, the NRC has not reached its final enforcement decision on the issues identified by the EEis and the PIM entries may be modified when the final decisions are made.
URls are unresolved items about which more information is required to determine whether the issue in question is an acceptable item, a deviation, a nonconformance, or a violation. A URI may also be a potential violation that is not likely to be considered for escalated enforcement action. However, the NRC has not reached its final conclusions on the issues, and the PIM entries may be modified when the final conclusions are made.
Item Type (Compliance,Followup,Other), From 10/01/1998 To 01/15/1999
SALEM 1 & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 8/21/98
.Positive IR 98-06 N
OPS 58 PSE&G's independent review groups, including the quality assurance department and the 3C station operations review committee, continued to provide effective oversight of Salem operations. The corrective action review board sufficiently challenged the quality of completed corrective actions for previous issues and events.
8/21/98 Negative IR 98-06 N
OPS 28 The timeliness of a 125 volt DC system operability determination that was not consistent with 3A the system's safety significance. Required audits of active operability determinations, were inconsistently performed, indicating a weakness in the implementation of program guidance.
8/21/98 Positive IR 98-06 N
OPS 28 Equipment operability determinations were of good quality, and generally performed in accordance with procedural guidance.
8/21/98 Positive IR 98-06 N
OPS 1A Operators performed well during a Unit 2 controlled shutdown and cooldown for a mid-cycle outage. An appropriate focus was maintained on shutdown cooling system status once Mode 5 conditions were achieved.
8/21/98 Positive IR 98-06 N
OPS SA PSE&G demonstrated good initiative in recent efforts to identify and minimize primary plant operational leakage sources.
8/21/98 Negative IR 98-06 N
OPS 3A Two instances of operator errors contributed to a reverse-power trip of a diesel generator output breaker and the overflow of a liquid waste collection tank.
8/21/98 Positive IR 98~06 N
OPS 3A Operations department performance was generally focused on safety-conscious plant operation.
7/10/98 Positive IR 98-0S N
OPS 1A PSE&G personnel completed advanced digital feedwater control system testing during Salem 3A Unit 1 startup in a well controlled and deliberate manner. Control room operators and test engineers maintained formal communications and demonstrated good coordination.
7/10/98 Positive IR 98-0S N
OPS 2A PSE&G operators and maintenance technicians promptly identified an unexpected increase in SA pressurizer relief tank in leakage and implemented effective actions to identify, quantify, and minimize the source of the reactor coolant system leak.
7/10/98 Positive IR 98-05 N
OPS 2A The decision to declare both solid state protection system trains inoperable following the SC discovery of a failed steam generator feed pump trip coil was reasonable and conservative.
Corrective actions taken in response to this event were prompt and effective.
FROM: 10/1/97 TO: 10/1/98 Page 1of14
. 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date
. Type Source ID SFA Code Item Description 7/10/98 Negative IR 98-05 N
OPS 28 Premature degradation of safety related chiller control valves, resulting from the use of valves of 3A a weak design for their application, led to multiple chiller corrective maintenance outages to 4A effect repairs. Inattention to detail resulted in an inadvertent start of a safety-related chiller during troubleshooting efforts. Maintenance personnel performed repairs in a safe manner, however, operations personnel declared a chiller operable without performing an appropriate post-maintenance retest. Overall coordination between the operations, maintenance, and engineering departments was good.
e 7/10/98 Negative IR 98-05 N
OPS 1A On two occasions, PSE&G operators inadvertently failed to restore the 11 component cooling 5C water loop to an operable status following manual operation of the associated heat exchanger flow controller, indicating weaknesses in safety-related equipment configuration control and corrective action effectiveness.
7/10/98 NCV IR 98-05 L
OPS 5C Inadequate control of a steam generator level instrument vent valve resulted in the conduct of LER LER 272/ 98-Unit 1 core alterations and subsequent operational mode four operation without containment 007 integrity being established. PSE&G's response and corrective actions to this self-identified NCV 98-05-01 event were good, resulting in a Non-Cited Violation.
5/3/98 Positive LER 98-002 L
OPS 5C This LER described an adverse condition where an auxiliary building ventilation excess flow IR 98-03 damper was found wired open with spring removed. Corrective actions were reasonable and complete. The safety significance evaluation performed for this event, documented in LER Supplement 1, was also acceptable.
5/3/98 Positive IR 98-03 N
OPS 5C PSE&G's actions to address and correct the cause of missing service water (SW) strainer filter 18 disks and cracked filter disk retaining rings were appropriate and promptly implemented. Unit 2 control operators responded promptly to the clogging of two SW pump discharge strainers in the e SW same loop. PSE&G managemenf s decision to take Salem unit 2 off-line for strainer repairs was appropriate, and corrective actions were adequate.
5/3/98 Positive IR 98-03 N
OPS 2A The 125 volt DC electrical distribution system was properly aligned for existing plant conditions at Unit 1 and 2. Material condition and housekeeping were acceptable. Adequate surveillance test procedures were implemented to verify system operability.
5/3/98 Positive*
IR 98-03 N
OPS 18 Operators responded promptly and effectively to an unexpected loss of the 21 steam generator feed pump while a 100% power. All plant equipment functioned as designed during the transient.
FROM: 10/1/97 TO: 10/1/98 Page 2of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 5/3/98 Positive IR 98-03 N
OPS 1A Overall, Salem plant management and staff controlled the Unit 1 reactor startup and power 3A ascension test activities well. The operating crews were attentive, used excellent communication skills, and responded appropriately to planned and emergent events and issues.
Reactor engineering and chemistry department support, as well as pre-evolution briefings, were usually of good quality although some deficiencies were observed during low power physics testing. Strong management and quality assurance oversight was indicated by continuous on-site management presence during restart activities and the willingness to halt further plant evolutions following the identification of emergent issues. Good self-assessment capability was e evident during hold point release discussions with the NRC Salem Assessment Panel.
3/15/98 Negative IR 98-01 N
OPS 3A The licensee's corrective actions to address the reasons for an apparently fatigued licensed SC control room supervisor were acceptable. However, there were some weaknesses identified in licensee management oversight of individual employee work hours which the licensee has initiated actions to address.
1/30/98.
Positive IR 98-02 N
OPS 38 The candidates demonstrated very good communications during the simulator exercises, both during routine and emergency portions of the exercise. Briefings were conducted by the control room supervisor candidates on a routine basis. The briefings were well controlled and ensured that all personnel knew the plant (simulator) status.
1/30/98 Positive IR 98-02 N
OPS 38 The examiners overall observed very good self and peer checking prior to reactivity manipulations during the simulator scenarios and generally good self checking during the other operational portions of the exam. Peer checks prior to reactivity changes was considered a strength by the examiners.
1/30/98 Positive IR 98-02 N
OPS 38 Overall, candidate performance during the operating tests was determined to be good. There e were no significant generic weaknesses identified.
3/15/98 Negative IR 98-01 N
OPS 1A Licensed operators' inadequate monitoring of plant parameters and maintenance of steam 3A generator levels, combined with inadequate communications and crew teamwork resulted in an inadvertent automatic start of the auxiliary feedwater pumps when the 14 steam generator level decreased to 9%. The reactor operator did not follow procedure requirements to maintain the steam generator levels within the required band.
3/15/98 Positive IR 98-01 N
OPS 1A In general, the conduct of operations was professional and safety-conscious. Activities 18 associated with the shutdown of Unit 2 on February 11 and the heatup of Unit 1 on February 18, were performed in a deliberate manner with clear communications.
FROM: 10/1/97 TO: 10/1/98 Page 3of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type*
Source ID SFA Code Item Description 8/21/98 Negative
. IR 98-06 N
MAINT 5A PSE&G personnel appropriately monitored containment fan cooler units (CFCUs) in accordance with maintenance rule requirements. Weaknesses in system.functional failure identification and classification were noted for the CFCUs.
8/21/98 Negative IR 98-06 N
MAINT 2A PSE&G maintenance technicians failed to restore an auxiliary feed water (AFW) pump 3A discharge pressure transmitter to an operable condition following an instrument calibration, resulting in the undetected inoperability of the 22 AFW pump for eighteen days.
e 8/21/98 Positive IR 98-06 N
MAINT 28 All technical specification action statement requirements were satisfied and the affected diesels were returned to service in a timely manner. Maintenance rule accounting for system unavailability time was proper.
8/21/98 Negative IR 98-06 N
MAINT 5C Corrective actions from earlier emergency diesel generator fuel oil leaks were narrowly focused.
8/21/98 Positive
- IR 98-06 N
MAINT 28 PSE&G's immediate corrective actions for two unrelated emergency diesel generator fuel oil leaks were appropriate.
8/21/98 NCV IR 98-06 N
MAINT 28 Continued deficiencies associated with safety tagging program implementation were also NCV 98-06-02 evident. [i.e. improper release of tagging boundary while maintenance activities were still being conducted, failure to apply a blocking tag to the proper component, failure to sign-on to a taggout prior to conducting work, and failure of a maintenance supervisor to verify that appropriate tagging boundaries were established prior to authorizing technicians to begin work]
8/21/98 Positive IR 98-06 N
MAINT 58 Plant risk was appropriately managed during the performance of scheduled and emergent work 5A activities. PSE&G self-identified weak performance with respect to recognition and implementation of compensatory measures associated with maintenance on service water supply and return valves for two containment fan cooler units.
8/21/98 Positive IR 98-06 N
MAINT 3A The Salem plant staff completed observed maintenance and surveillance test activities 3C effectively and in accordance with governing procedures. Maintenance support of operations was prompt and appropriate. The Unit 2 safety valve replacement effort was well planned and executed.
7/10/98 Positive IR 98-05 N
MAINT 28 Observed maintenance and surveillance activities were properly scheduled and completed in accordance with PSE&G program guidelines and technical specification requirements.
7110/98 Pos'itive IR 98-05 N
MAINT 28 Following an inservice test failure, PSE&G personnel properly repaired and tested the 13 auxiliary feed water pump turbine steam supply check valve in accordance with maintenance procedures and American Society of Mechanical Engineers code requirements.
FROM: 10/1/97 TO: 10/1/98 Page 4of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID
.SFA Code Item Description 7/10/98 NCV IR 98-0S L
MAINT
- 18. Inadequate implementation of a maintenance procedure involving work on in-core detector guide NCV 98-0S-02 3A tubes in August 1996 led to a later unplanned personnel radiation exposure incident.
Specifically, the detector guide tubing separated during in-core system operation allowing an irradiated in-core detector to remain unshielded in close proximity to nearby maintenance work site. Corrective actions were prompt and effective, resulting in a Non-Cited Violation.
7/10/98 Negative*
IR 98-0S N
MAINT 2A Failure to perform adequate 10 CFR SO.S9 applicability reviews for revisions to an inservice.
VIO 98-0S-03 3A single cell battery charging procedure resulted in the operation of the 1A 12S volt DC (VDC) e LER 98-011 48 battery system in a nonconforming condition. Additionally, poor control of this charging activity was evident. Specifically, control room operators were unaware of the in-progress 12S VDC single cell battery charge, which was completed using an uncalibrated and improperly restrained non-safety related charger. Further, inadequate monitoring and trending of 12S VDC battery system performance allowed a degraded individual cell voltage to trend below a maintenance rule goal without being promptly identified. The subsequent cell replacement evolution was adequately controlled, but a discrepancy in the retest procedures acceptance criteria was identified.
7/10/98 NCV IR 98-0S L
MAINT 28 PSE&G appropriately reported and corrected a self-identified issue involving a failure to LER NCV 98-0S-04 establish adequate surveillance procedures for vital bus load shed testing, resulting in a Non-LER 96-03S Cited Violation.
7/10/98 NCV IR 98-0S L
MAINT 28 An inadequate review of system design during associated system test procedure development LER NCV 98-0S-OS 38 resulted in the failure to perform testing of the automatic isolation of steam generator blowdown LER 272/ 97-4C and sampling valves upon an actuation of the auxiliary feedwater system. Corrective actions to 011 address this self-identified issue were timely and effective, resulting in a Non-Cited Violation.
7/f0/98 NCV IR 98-0S L
MAINT
. 28 PSE&G appropriately reported and corrected two self-identified issues involving failures to e
LER NCV 98-0S-06 SA complete technical specification required channel check surveillances.
LER 97-012 7/10/98 LER IR 98-0S L
MAINT 28 PSE&G appropriately reported and corrected a self-identified issue involving a failure to cycle LER 97-09 SA containment spray pump discharge valves after pump operation to alleviate the potential for valve pressure-locking.
7/10/98 NCV IR 98-05 L
MAINT 28 Improper scheduling of solid state protection and auxiliary feedwater system testing resulted in LER NCV 98-05-07 5A the failure to perform technical specification surveillance testing within specified time periods.
LER 311/97-PSE&G's root cause analysis and corrective actions were adequate, leading to a Non-Cited 011 Violation.
FROM: 10/1/97 TO: 10/1/98 Page 5of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description NCV IR 98-05 L
MAINT 28 PSE&G appropriately corrected a self-identified issue involving a failure to test the main steam LER NCV 98-05-08 5A isolation valve hydraulic actuator override feature. This led to a Non-Cited Violation.
LER311/97-018 7/10/98 NCV IR 98-05 L
MAINT 38 Following self-identification of the issue, PSE&G appropriately reported the Channel 23 OTdT
- LER NCV 98-05-09 4A setpoint inoperability. Initial actions to address this condition were both timely and appropriate.
LER 311/98-5A PSE&G's documented assessment of the consequences of this issue was weak because it did e 02 not adequately describe acceptable levels of protection for a slow Rod Withdrawal Accident at Power. The remaining aspects of the licensee event report were acceptable. This issue resulted in a Non-Cited Violation.
. 7/10/98 LER IR 98-05 L
MAINT 5A PSE&G appropriately reported and evaluated a self-identified turbine first stage pressure LER 311/98-instrument scaling error. Corrective actions to address this error were both timely and 006 appropriate.
5/3/98 Positive
-LER 97-013 L
MAINT 5C On July 2, 1997, following surveillance testing, the 2A emergency diesel generator (EOG) was IR 98-03 inappropriately declared operable with electrical test equipment still installed in the EOG control cabinet. After this issue was identified, a follow-up surveillance test was performed satisfactorily, and the test equipment was removed. PSE&G attributed the cause of this event to human error. Corrective actions taken to address the deficiencies identified following the improper restoration of a Unit 2 emergency diesel generator were adequate. Associated design calculations and safety evaluations were thorough.
5/3/98 Positive IR 98-03 N
MAINT 5C PSE&G implemented appropriate corrective actions to repair degraded auxiliary feedwater 4A piping revealed by a through-wall leak on.a pump minimum-flow orifice line. Technical e
specification and ASME code class 3 requirements were satisfied. However, this event revea.led a weakness in scope of the flow-accelerated corrosion program in that only the steam-driven pumps were included for monitoring.
5/3/98 Negative IR 98-03 N
MAINT 1C PSE&G determined that the lack of clear ownership for and coordination of recent emergency 3C diesel generator (EOG) on-line maintenance outages resulted in unnecessary delays in work completion, extending the overall equipment unavailability time. Inadequate tagging controls during the 28 EOG outage resulted in an electrical breaker blocking tag being released while personnel were actively working on equipment supplied by that breaker.
FROM: 10/1/97 TO: 10/1/98 Page 6of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 3/15/98 VIO IR 98-01 N
MAINT 3C Poor planning and inadequate maintenance practices resulted in an incorrect control switch 38 being installed on the 12 Diesel Fuel Oil Transfer Pump (DFOTP), which rendered the pump inoperable. The licensee ascended to Mode 4 on Unit 1 with less than the required DFOTPs operable, which was a Technical Specification violation. The licensee's immediate corrective actions for this event were weak, including an untimely operability determination for the wrong part being installed on the 21 DFOTP, and untimely verification of correct part numbers for similar control switches on the four DFOTP electrical panels.
e 3/15/98 VIO IR 98-01 N
MAINT 3A Procedural adherence for the 2A Emergency Diesel Generator (EOG) post-maintenance testing*
VIO 98-01-04 28 was poor. Numerous procedural violations by maintenance and operations personnel resulted 1C in the improper operation of the diesel. There was little safety significance to these violations as the diesel was out of service tor maintenance. However, they showed a lack of questioning attitude and attention to detail by numerous personnel. Additionally, the engineering action plan utilized for the maintenance effort was not sufficiently detailed to promote smooth transition between the maintenance and operations procedures used.
3/15/98 Positive.
IR 98-01 N
MAINT 2C The licensee adequately implemented their Technical Specification Surveillance Improvement 4C Program to support Unit 1 restart.
3/15/98 Negative IR 98-01 N
MAINT 38 The licensee met all Technical Specification requirements for the 2C EOG outage and the 3C crankcase alarm on the 28 EOG. The operator correctly followed the alarm response procedure for the 28 alarm. The operability determination for the 28 EOG after the cause of the alarm was determined was adequate, but the decision to run the 28 EOG during the 16-hour 2C EOG outage was not appropriate.
3/15/98 Positive IR 98-01 N
MAINT 28 On February 11, 1998, the 2A EOG turbocharger failed during a post maintenance test. The e
. 58 licensee formed a team to get the relevant facts, find the cause of the failure, evaluate its significance to the operability of the other EDGs, and establish corrective actions. The NRC.
concluded that the preliminary root cause evaluation of the failed turbocharger blade was thorough, detailed, and accurate. The inspector also concluded that the licensee had properly responded to the EOG turbocharger failure by initiating a thorough evaluation.
FROM: 10/1/97 TO: 10/.1/98 Page 7of14 8 February 1999
SALEM 1 & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 8/4/98 Positive IR 98-07 N
ENG SC The actions taken to address the Votes testing deficiencies and the missed testing of a containment electrical penetration breaker were acceptable.
8/4/98 Negative IR 98-07 N
ENG 4A The proposed change to the surveillance procedure did not adequately address the TS requirement regarding periodic verification of the ability of CREACS to remove the assumed heat load. However, the procedure had not yet been revised, no violation of NRC requirements occurred.
8/4/98.
Positive IR 98-07 N
ENG 48 The calculations and associated engineering evaluations for the component cooling flow e
S8 acceptance criteria, for the verification of computer generated results and for establishing operator required time to complete the switchover of the ECCS pump suction from the RWST to the containment sump were comprehensive and technically sound.
8/4/98 Positive IR 98-07 N
ENG 48 Acceptable actions were taken to address the MOV design-basis setpoint configuration control, SC and to validate the RHR pump curves for the required flow and NPSH in the recirculation mode of operation.
8/21/98 Positive IR 98-06 N
ENG 28 PSE&G implemented and maintained a satisfactory inservice inspection program at Salem. The 38 bases for selected ASME code relief requests were valid and accurate. Non-destructive examination personnel were properly trained in accordance with industry standards.
8/21/98 Positive IR 98-06 N
ENG 48 Timely and appropriate engineering support of operations and maintenance was indicated by 4A active participation in daily station interface meetings,* as well as effective development of minor design changes and completion of several safety evaluations.
8/4/98 Positive IR 98-:-07 N
ENG 4C The inspectors found that licensee actions taken to address eighteen of the nineteen previously SC identified issues were acceptable. Those issues and two additional fire protection-related items e reviewed by the NRC were closed. Another item pertaining to periodic verification that each control room emergency air conditioning system train has the capability to remove the assumed heat loads, as required by the Salem Technical Specification, could not be closed because the corrective actions were incomplete.
8/4/98 Positive IR 98-07 N
ENG 4A The calculations and associated engineering evaluations for the component cooling flow SC acceptance criteria, for the verification of computer generated results and for establishing operator required time to complete the switchover of the ECCS pump suction from the RWST to the containment sump were comprehensive and technically sound.
7/10/98 Positive IR 98-0S N
ENG SC Following several unplanned technical specification action statement entries, PSE&G implemented appropriate corrective actions to resolve control room air intake radiation monitor channel check surveillance test failures.
FROM: 10/1/97 TO: 10/1/98 Page 8of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source
- ID SFA Code Item Description 7/10/98 LER IR 98-05 L
ENG SC Initial corrective actions for a failed diesel service water inlet valve were not fully effective in LER 272196-preventing a subsequent similar failure, Indicating a weakness in PSE&G's ability to develop and 032 implement lasting corrective measures for this safety-related valve.
7/10/98 Positive IR 98-0S N
ENG 4C PSE&G maintained adequate controls for temporary modifications. Minor weaknesses involving the timeliness of modification package closure and the accuracy of control tags were identified.
7/10/98 NCV IR 98-0S L
ENG SA PSE&G appropriately reported and corrected self-identified design deficiencies associated with -
LER NCV 98-05-10 SC the switchgear penetration area ventilation system, resulting in a Non-Cited Violation.
LER 272/96-038 7/10/98 NCV IR 98-0S L
ENG 4A Inadequate review of design information resulted in the failure to include ail necessary LER NCV 98-0S-11 48 engineered safeguard features actuation system relays in technical specifications surveillance LER 272/96-test procedures. PSE&G's corrective actions for this self-identified issue were adequate, 040 resulting in a Non-:Cited Violation.
5/3/98 Positive IR 98-03 N
ENG 28 PSE&G restored the 22 steam generator steam flow channels II and Ill to an operable status in.
a slow and deliberate manner, meeting all technical specification requirements during the process.
4/1/98 Positive IR 98-04 N
ENG 48 The licensee's resolution of the NRC observations regarding the requirements traceability matrix 2A was acceptable.
4/1/98 Positive IR 98-04 N
ENG 48 The licensee appropriately addressed the NRC concerns regarding signing off of test procedure 2A prerequisites.
e 4/1/98 Positive IR98-04 N
ENG 48 The actions to address the control room ventilation test procedure inadequacies were 2A acceptable.
4/1/98 Positive IR 98-04 N
ENG 48 The licensee's review and resolution of test discrepancies regarding component cooling water 2A flow balance were acceptable and the engineering documents resulting from this review were also acceptable.
4/1/98 Positive IR 98-04 N
ENG 48 PSE&G maintained acceptable controls over the conduct of the Unit 1 power ascension tests 2A and the integrated test program remained acceptable. Tests were being conducted in an acceptable manner by a knowledgeable technical staff.
FROM: 10/1/97 TO: 10/1/98 Page 9of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 4/1/98 Negative IR 98-04 N
ENG 48 Although the control loop tuning acceptance criteria were incorrec~ no violation of NRC 2A requirements occurred. However, a better understanding by engineering of the process dynamics, might have resulted in a better definition of the acceptance criteria and avoided test delays.
4/1/98 Positive IR 98-04 N
ENG 48 The licensee properly addressed the inadequate surveillance test procedure pertaining to the 2A turbine trip logic testing.
3/15/98 VIO IR 98-01 N
ENG 2A Elevated grass levels in the Delaware River combined with degraded service water strainers and e VIO 98-01-10 28 lack of service water reliability program oversight resulted in accelerated rates of service water LER 96-34 biofouling. Weak management attention allowed biofouling to occur at unpredictable rates.
Several instances of biofouling occurred in plant components before strainer degradation was identified and effective corrective actions were taken. In one instance, the biofouling contributed to the. inoperability of a Unit 2 safety related chiller. Salem staff failed to take prompt corrective actions to determine and correct the cause of service water biofouling problems. System Engineering and Operations interfaces were weak during the analysis of those problems. The licensee did not adequately evaluate the extent of condition at both Salem Units.
3/15/98 Negative IR 98-01 N
ENG 5C The licensee continued to adequately pursue resolution of issues related to the control area ve~tilation system (CAVS). However, long term corrective actions are still necessary to eliminate the need for maintenance mode, a time-consuming, resource-intensive work around which ensures adequate differential pressure margin between the control room and the adjacent spaces. When this mode is employed, then any circumstance which necessitates accident pressurized mode, such as an inoperable CAVS radiation monitor, would require a unit shutdown to Mode 5 so that the control room emergency air conditioning system intake could be e lined up to a non-operating unit.
3/15/98.
Positive IR 98-01 N
ENG 4A The licensee had adequately demonstrated design basis capability for Salem Unit 1 MOVs to 4C support restart. Justifications for key program assumptions and the applied valve factors were adequate.
FROM: 10/1/97 TO: 10/1/98 Page 10of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Date Type Source ID SFA Code Item Description 8/21/98 Positive IR 98-06 N
PS 3C Salem radioactive waste processing and radioactive material shipping procedures were of good quality and effectively implemented regulatory requirements.
8/21/98 Positive IR 98-06 N
PS 3A
- PSE&G effectively limited the amount of stored contaminated equipment and radioactive wastes.
8/21/98 Positive IR 98-06 N
PS 3C Salem solid radioactive wastes were effectively sampled, packaged, and dewatered in accordance with requirements.
7/10/98 Positive IR 98-05 N
PS 1C PSE&G management demonstrated good self-assessment capability during the development of e a detailed action plan to correct long-standing out-of-specification water chemistry parameters.
This plan also addressed the basic causes for these deficiencies which remained uncorrected for an extended period of time.
7/10/98 Negative IR 98-05 N
PS 1C PSE&G effectively maintained and implemented the Radiological Environmental Monitoring VIO 98-05-12 Program. However, the failure to establish written procedures to collect drinking water, fish, and invertebrate samples required by technical specifications resulted in a violation.
7/10/98 Positive
. IR 98-05 N
PS 1C A Quality Assurance department audit of the implementation of the Radioactive Effluent Monitoring Program was of sufficient scope and depth to effectively assess program performance.
7/10/98 Positive IR 98-05 N
PS 1C The contractor laboratory implemented effective Quality Assurance and Quality Control programs for the Radiological Environmental Monitoring Program, and provided effective validation of analytical results. These programs were capable of ensuring independent checks on the precision and accuracy of the measurements of radioactive material in environmental media.
e 7/10/98 NCV IR 98-05 L
PS 1C Following self-identification, PSE&G appropriately reported and corrected procedure deficiencies LER NCV 98-05-14 involving the use of inadequate sample line purge times prior to collection and analysis of LER 272/96-technical specification required chemistry samples. The circumstances of this issue resulted in 033 a Non-Cited Violation.
7/10/98 Positive IR 98-05 N
PS
-1c The annual Quality Assurance review of the station security program was effective in that PSE&G auditors identified several quality issues, and promptly raised them to station management to initiate cause determinations and corrective actions. P$E&G auditors identified several quality issues, and promptly raised them to station management to initiate cause determinations and corrective actions.
FROM: 10/1/97 TO: 10/1/98 Page 11of14 8 February 1999
SALEM I & 2 PLANT ISSUES MATRIX Oat~
Type Source ID SFA Code Item Description 7/10/98 LER IR 98-05 L
PS 1C PSE&G's corrective actions for an event involving inadequate control of fire protection system LER 311/97-water supply valves were acceptable.
016 & 97-18 5/3/98 Positive IR 98-03 N
PS 1C Quality Assurance audits of the emergency preparedness (EP) program were thorough and the reports were useful to PSE&G management in assessing the effectiveness of the EP program and providing enhancement recommendations. This area was assessed as excellent.
5/3/98 Positive IR 98-03 N
PS 1C The department reorganization and hiring of a manager with extensive EP experience enhanced -
the EP program. The inspectors concluded that the positive findings during this inspection were an indication that the program had significantly improved since the last inspection.
5/3/98 Positive IR 98-03 N
PS 1C PSE&G conducted emergency response training and drills as required. Based upon overall good performance during the drills and the March 1998 biennial full-participation emergency exercise, the inspectors concluded that training for the ERO was effective.
5/3/98 Positive IR 98-03 N
PS 1C PSE&G emergency plan changes were adequately reviewed in accordance with 10 CFR 50.54(q). PSE&G planned to review, evaluate/rewrite the emergency plan implementing procedures for conformance to other station procedures and to improve the review process.
The inspectors also concluded that letters of agreement with offsite agencies were *in place.
5/3/98 Positive IR 98-03 N
PS 1C The emergency response facilities and equipment were in a good state of operational readiness.
Surveillance tests and inventories were performed as required and discrepancies were resolved in a timely manner. Expenditure of resources to improve equipment and facilities demonstrated PSE&G's commitment to support and maintain the emergency preparedness program. Overall, the inspectors considered this area to be very good.
e 5/3/98 Positive l.R 98-03 N
PS 1C Based upon a review of selected items and procedures, the inspectors concluded that PSE&G's method for tracking Emergency Preparedness corrective* actions was very good and that the self-assessment program provided good feedback to the staff. The timeliness of resolving some identified issues was weak.
FROM: 10/1/97 TO: 10/1/98 Page 12of14 8 February 1999
ABBREVIATIONS USED IN PIM TABLE CAVS control area ventilation system DFOTP diesel fuel oil transfer pump ECCS emergency core cooling system EDG emergency diesel generator IST inservice test program LCO limiting condition for operation LEFM leading edge flow meter MR maintenance rule PM preventive maintenance POPS pressurizer overpressure protection system PORV power-operated relief valve PSE&G Public Service Electric & Gas Company RP radiation protection SSC structure, system, or component TS technical specification TSSIP technical specification surveillance improvement project UFSAR updated final safety analysis report VOTES valve operation test and evaluation system FROM: 10/1/97 TO: 10/1/98 Page 13of14
. 8 February 1999
GENERAL DESCRIPTION OF PIM TABLE COLUMNS Date The actual date of an event or significant issue for those items that have a clear date of occurrence (mainly LERs), the date the source of the information was issued (such as for EALs), or the last date of the inspection period (for IRs).
Type The categorization of the item or finding - see the Type I Findings Type Code table, below.
Source The document that describes the findings: LER for Licensee Event Reports, EAL for Enforcement Action Letters, or IR for NRC Inspection Reports.
ID Identification of who discovered issue: N for NRC; L for Licensee; or S for Self Identifying (events).
SFA SALP Functional Area Codes: OPS for Operations; MAINT for Maintenance; ENG for Engineering; and PS for Plant Support.
Code Template Code - see table below.
Item Description Details of NRC findings on LERs that have safety significance (as stated in IRs), findings described in JR Executive Summaries, and amplifying information contained in EALs.
TYPE I FINDINGS CODES ED Enforcement Discretion - No Civil Penalty Strength Overall Strong Licensee Performance Weakness Overall Weak Licensee Performance EEi
- Escalated Enforcement Item - Waiting Final NRC Action VIO Violation Level I, II, Ill, or IV NCV Non-Cited Violation DEV Deviation from Licensee Commitment to NRC Positive Individual Good Inspection Finding Negative Individual Poor Inspection Finding LER Licensee Event Report to the NRC URI..
Unresolved Item from Inspection Report Licensing Licensing Issue from NRR MISC Miscellaneous - Emergency Preparedness Finding (EP),
Declared Emergency, Nonconformance Issue, etc. The type of all MISC findings are to be put in the item Description column.
FROM: 10/1/97 TO: 10/1/98 TEMPLATE CODES 1
Operational Performance: A-Normal Operations; B - Operations During Transients; and C - Programs and Processes 2
Material Condition: A - Equipment Condition or B - Programs and Processes 3
- Human Performance: A - Work Performance; B - Knowledge, Skills, and Abilities i Training; C - Work Environment 4
Engineering/Design: A - Design; B - Engineering Support; C - Programs and Processes 5
Problem Identification and Resolution: A - Identification; B - Analysis; and C -
Resolution NOTES:
EEis are apparent violations of NRC requirements that are being considered for escalated enforcement action in accordance with the "General Statement of Policy and Procedure for NRC Enforcement Action" (Enforcement Policy), NUREG-1600.
However, the NRC has not reached its final enforcement decision on the issues identified by the EEis and the PIM entries may be modified when the final decisions are made. Before the NRC makes its enforcement decision, the licensee will be provided with an opportunity to either (1) respond to the apparent violation or (2) request a predecisional enforcement conference.
URls are unresolved items about which more information is required to determine whether the issue In question is an acceptable item, a deviation, a nonconformance, or a violation. However, the NRC has not reached its final conclusions on the issues, and the PIM entries may be modified when the final conclusions are made.
Page 14of 14 8 February 1999
Mr. Harold W. Keiser Salem Generating Station 6
ENCLOSURE 2 SALEM INSPECTION PLAN" INSPECTION TITLE/ PROGRAM AREA PLANNED PROCEDURE DATES 64704 Appendix R Fire Wrap Review 04/12/99 83750 Occupational Radiation Exposure -
04/19/99 Unit 2 Outage 73753 lnservice Inspection 04/19/99 81700 Physical Security Program 04/19/99 INSPECTION TYPE Initiative (DRS)
Core (DRS)
Core (DRS)
Core (DRS)
"NOTE: Salem is one of the pilot plants for the new performance assessment process.
Accordingly, implementation of the baseline inspection program will affect the inspection scope and schedule significantly. Scheduling of the core and regional initiative inspe,ctions proposed at the PPR will not be finalized until May 1999.