ENCLOSURE 5 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION (RAI) 1 .d (MOV Performance Indicator Report for Cycle 20) to ULNRC-06410 Page 1 of 45 NET 20150022 July 16. 2015 To: Matt Hall Victor Thomas From: Mike Brenner Re: MOV Testing Program The attached 18 Month MOV Performance Indicator Report for Cycle 20 was prepared in accordance with the provisions of EDP-ZZ-0l 114, Motor Operated Valve Program Guide.
Key Accomplishments:
All of Callaways safety-related Motor Operated Valves (MOV) are properly set up and are in good working condition. There are no signs of adverse trends. Nominal operating parameters for Cycle 20 are documented in Attachment 1.
a) All rising stem MOVs with active safety related functions using a torque switch in their closing stroke are setup to exceed the 25% target margin with the exception of EGHVOI3O which has a closing stroke margin of 19%. Job 14511998 has been written to restore the margin to 25%. Having 25% margin allows a 4-cycle/6 year static testing (rather than DP testing) interval for periodic verification of operability.
- 5) All rising stem MOVs with active safety function using a limit switch to open and or close have positive margin.
c) All butterfly MOVs have had their torque switches jumpered or removed. These MOVs must have positive margin for opening and closing stroke with an active safety-related function. All butterfly MOVs meet the parameters required to: 1) eliminate the need for periodic differential pressure testing, and 2) utilize the 4 cycle/6 year interval for periodic verification of operability.
- The results of testing performed on rising stem valves during cycle 20 confirms that there is no lubrication degradation of the stem-to-stem nut interface over the 18-month interval between maintenance.
Page 1 of2 to ULNRC-06410 Page 2 of 45 Planned Enhancements
- Improve Test Criteria worksheets for MOV testing. Potentially combine the Test Criteria Worksheet and the Signature Analysis Report into one datasheet.
- Easy Thrust Torque (ETT) Sensors will be utilized on quarter-turn, butterfly MOVs to improve test results.
- Enter Test Criteria Worksheets, UDS Test Records and Predictive Performance Reports into Document Room for revision control and Planner access without engineering support.
elE.Br&
MOV Engineer Attachment 1: 18 Month Motor Operated Valve Program Performance Indicator Report for Cycle 20 Attachment 2: Database for Cycle 20 with Margins and Limits Attachment 3: Predictive Performance Reports for CycLe 20 cc: file: A 160.0446 Matt Hall Greg Kremer Victor Thomas Mike Brenner Darrel Heckel Curtis Wood Page 2 of 2 to ULNRC-06410 Page 3 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 July 20, 2015 ATTACHMENT 1 This report provides an overview of the performance and condition of all safety-related and recaps Motor-Operated Valve Program activities over Cycle 20; end of Refuel 19 to end of Refuel 20 in accordance with provisions of EDP-ZZ-011 14, Motor-Operated Valve ProQram Guide.
The 18-Month MDV Performance Indicator Report is broken down into eight main sections:
- 1. Summary of Diagnostic Testing Performed to Date and a Recap of Testing Performed during Cycle 20.
- 2. Description of the Current Setup of all Safety-Related MOVs, in the Genetic Letter 89-10 Program.
- 3. Description of Major Work Completed on Safety-Related MOVs
- 5. Summary of Trends Identified from Predictive Performance Reports
- 6. Actions to Improve Margin and Reduced Voltage Performance
- 7. Operating Experience Reviewed During Cycle 20
- 8. Planned Actions to Enhance the Callaway MDV Program 1
to ULNRC-06410 Page 4 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20
- 1. Summary of Diagnostic Testing Performed to Date and a Recap of Testing Performed during Cycle 20
- There are currently 144 valves in the MOV program. All 144 have been static baseline tested and 99 have been differential pressure tested.
- During Cycle 20, a total of 31 Periodic Verification Tests were performed. This included 1 Baseline Test on EGHVOO1 1 following an actuator grease change-out, 1 Baseline Test on ALHV0005 following an actuator grease change-out and 1 baseline test on ALHV0009 following a valve inspection. All MOV diagnostic tests are now being documented as Periodic Verification Tests with the exception of partial tests to verify packing loads.
These are called Packing Force Tests.
- During Cycle 20, a total of 18 Service and Inspect PMs were performed on GL 89-10 Program MOVs. 203 Actuator Gearbox and Motor Pinion Gearbox grease inspections were performed on safety-related; Program, MOVs and non-safety-related; Production MOVs.
- 2. Description of the Current Setup of all Safety-Related MOVs, in the Generic Letter 89-10 Program.
At the end of Refuel 20:
- All rising stem torque-controlled MOVs with a safety function to close as setup to meet the 25% margin requirement except EGHVO13O which has 19% closing stroke margin. Job 14511998 is scheduled for Refuel 21 to restore the margin to greater that 25%.
- All rising stem limit-closed MOVs are setup with the required positive margin.
- All quarter-turn/butterfly valves are setup with positive margin to close.
- All MOVs use limit switch control for their opening stroke. All MOVs are setup with positive opening stroke margin.
2 to ULNRC-06410 Page 5 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20
- 3. Description of Major Work Completed on Safety-Related MOVs The following table summarizes all major work performed on GL 89-10 Program MOVs:
Location Periodic Service Actuator Valve Motor Other Verification & Grease Inspection Brush Test Inspect Change- Inspection PM out ALHV0005 X X X ALHV0009 X X ALHVOO11 X BBHV8351A X X 2 BBHV8351D X X BGHV8357A X X BGLCVO1I2C X X EFPDVOO2O X EGHVOOIJ X X EGHVOOI2 X EGHVOOI4 X X EGHVOOI5 X 3 EGHVOO71 X X EGHVO126 X X EGHVOI3O X X EGHVO131 X X ENHV0006 X ENHV0007 X X EPHV88O8A X LFFVOO95 X BNLCVO112E X X EJHV88O4B X EMHV88O1A X ALHVOO31 X X ALHVOO33 X X EFHVOO23 X X 4 EFHVOO37 X 5 EFHVOO41 X X EFHVOO42 X EFHVOO49 X X EFHVOO59 X X
- 1. Replaced torque switch
- 2. Reconditioned stem nut
- 3. Adjusted close limit switch
- 4. Adjusted tripper fingers
- 5. Replaced valve
- Other Issue: 17
- Business Tracking: 2
- Significance Level 2: 1 3
to ULNRC-06410 Page 6 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 o CAR 201408399; ALHV0005 would not full close Problem Statement: ALHV0005, MDAFP B TO S/G D HV (object), would not full close (deviation), resulting in continued flow to EBBO1D, the RCS steam generator D (impact) and the need to secure PALO1B, the B MDAFP (impact) to prevent steam generator overfilling.
This CAR is In-Process.
Significance Level 3: 5 o CAR 201303697; FCHVO3I2 motor running at approximately twice normal speed.
Problem Statement: During as-found motor-operated valve FCHVO312 testing under job 11513700 (obj) the motor was found to be operating at approximately twice the normal speed (dev) resulting in a failed post maintenance test, extended out of service time, and additional outage critical path duration (imp).
This CAR is closed.
o CAR 201302358; ESW SW cross connect valve leakage identified during Job 06527624.904 Problem Statement: The In-Service Leakage Test (ISLT) per Job 06527624.904 on valve EFHVOO24; SERV WTR TO ESW TRN B UPSIRM HV (Object), identified a leakage rate in excess of 10 GPM (Deviation), If EFHVOO26 (SERV WTR TO ESW TRN B DNSTRM HV) is unable to be closed due to a loss of power or valve failure, leakage from the 25W system could be excessive, causing a reduction in the ability to cool the RCS (Reactor Cooling System) based upon UHS (Ultimate Heat Sink) capacity (Impact).
This CAR is closed.
o CAR 201400092; EMHV88OJB failed to full stroke during OSP-BG-VOO1B Problem Statement: EMHV88OJB (Boron Injection Header Isolation Valve) (object) failed to full stroke during OSP-BG-V001 B (deviation) resulting in the inability to verify operability and entering Tech Spec 3.5.2.A (impact).
This CAR is closed.
o CAR 201401204; Adverse trend in grease inspection failures to date in 2014 Problem Statement: Motor operated valve (MOV) grease (Object) was characterized as unsatisfactory (Deviation), resulting in unnecessary jobs (on demand PM) being generated to perform grease change outs. (Impact).
This CAR is closed.
o CAR 201406426; EFHVOO66 ESW UHS Cooling Tower Bypass Valve Problem Statement: Object: EFHVOO66 Spline Adapter; Deviation: slipped from its proper position. Impact: Spline adapter was found in an undesirable position but splines were still engaged with enough contact area to operate the valve in a design basis accident.
This CAR is closed.
- Significance Level 4: 33
- Significance Level 5: 21
- Significance Level 6: 4 4
to ULNRC-06410 Page 7 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20
- 5. Summary of Trends Identified from Predictive Performance Reports No trends were identified in the Predictive Performance Reports (PPR). A copy of each PPR is attached to this report.
- 6. Actions to Improve Margin and Reduced Voltage Performance
- Job 1451998 was written to improve the close margin for EGHVO13O. The close margin is 19%. The Callaway standard for this MOV is 25%.
- Job 14001995 was written to improve the stem/stem nut coefficient for BGLCVO1J2E. The COF is 0.179. Callaway action is initiated at a COF of 0.15 or greater.
- Breakers continue to be replaced under Modification 91-1 035 and MCC Buckets under modification 01-1003 resulting in improved reduced voltage performance.
- 7. Operating Experience Evaluated During Cycle 20
- CAR 201301468; Anchor Darling/Flowserve Part 21 Problem Statement: Flowserve contacted Callaway regarding a Part 21 notification for a potential defect in Anchor Darling double disc gate valves, size 2.5 or larger. The wedge pin that serves to lock the threaded stem to upper wedge joint can shear if the actuator applies a torque that exceeds the torque applied to the assembly before the pin was installed. A pin failure results in a loss of stem to upper wedge joint integrity.
Extent of Condition: CAR 201300135 identified the following Anchor Darling double disc gate valves installed at Callaway:
o EGHVOO58 o EGHVOO59 o EGHVOO6O o EGHVO127 o EGHVOI3O o EGHVOJ3J All are safety related.
This CAR is Complete. No actions or jobs are documented. CAR 201400704.was generated to readdress the Part 21. This CAR has been completed; however, further action is still required as determined by information obtained in January 2015 at the Motor Operated Valve Users Group (MUG) meeting.
- CAR 201305792; ICES 304752
- Evaluation Statement: Evaluate the applicability of operating experience ICES 304752 on motor-operated valve limit switch failure due to over-burnishing and subsequent oxidation-induced contact failure.
Action to Resolve Issue: Action laddresses the applicability to Callaway as determined by the valve team supervisor. This OE was discussed with a senior electrical technician and it was suggested that training/retraining on the use of burnishing tools might be appropriate at this time. This training would be an enhancement. TRRQ 201400565 has been initiated to evaluate the need for this training.
This CAR is Complete.
- CAR 201306796; NRC IN 2013014; Potential Design Deficiency in MOV Control Circuit Evaluation Statement: At Limerick Generation Station, Motor-operated valves (MOV) could remain partially open following the initiation of an automatic isolation signal in response to a 5
to ULNRC-06410 Page 8 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 design-basis LOCA when power is interrupted to the actuator of certain MOVs. In addition, the valve position lights could indicate the valve is closed when the actual position could be as much as 15% open. This is reported in the Nuclear Regulatory Commission Information Notice 2013-14. The purpose of this evaluation is to determine if this Information Notice is applicable at Callaway.
Action to Resolve Issue: At Callaway, interlock/permissive functions ate not provided through the limit switches within the Limitorque actuator. Open and closed indications are provided through the Limitorque switches. When a LOCA trip signal is activated, Callaway MOVs are de-energized and then load sequenced and receive their power from their emergency diesel generator buss. With power, the MOVs will continue toward their design-basis position. Power could be lost, but the MOV will continue towards design basis position when power is restored. When power is removed and the MOV has stopped motion due to inertia, it will not reposition itself because all safety-related MOVs at Callaway have a locking gear-set through the Limitorque actuator except for GSHVOO2O and GSHVOO21. These MOVs have an HBC gear box. The gear box provides the locking gear-set condition. The condition discussed in NRC IN 2013-14 is not applicable as-built at Callaway.
This CAR is Complete.
- 8. Planned Actins to Enhance the Callaway MOV Program
- CAR 201402649 Improve Motor Operated Valve PM Basis Condition Descrittion: The Motor-Operated Valve PM Basis is wrong for numerous tasks and references.
The MOV PM Basis is being reviewed for errors and to improve the clarity of the document.
Following the PM Basis update, PM frequency will be optimized based on operating experience.
- Improve Test Criteria Worksheets for MOV testing. Potentially combine the Test Criteria Worksheet and the Signature Analysis Report into one datasheet.
- Easy Thrust Torque (EU) Sensors will be utilized on quarter-turn, butterfly MOVs to improve test results.
- Enter Test Criteria Worksheets, UDS Test Records and Predictive Performance Reports into Document Room for revision control and Planner access without engineering support.
6 to ULNRC-06410 Page 9 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 7
to ULNRC-06410 Page 10 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 DEFINITIONS FOR ATTACHED DATABASE Rising Stem-Torque Switch Controlled Motor Operated Valve Definitions Close Operable Load Limit = Differential Pressure Thrust/Minimum Available Thrust at Torque Switch Trip Close Margin = ((Minimum Available Thrust @ Torque Switch Trip Differential Pressure Thrust)/Differential Pressure Thrust) X 100 Close Reduced Voltage (RV) Limit = Close Torque at Torque Switch Trip / Allowable Reduced Voltage Running Torque Close (Actuator) Thrust Limit = Total Thrust following Torque Switch Trip / Actuator Thrust Rating Close (Actuator) Torque Limit = Total Torque following Torque Switch Trip / Actuator Torque Rating COF (Stem/Stem Nut Coefficient of Friction) = Stem/Stem Nut Interface Coefficient of Friction Lubrication Limit = Measured Stem-to-Stem Nut Friction Coefficient I Callaway Target Friction Coefficient of 0.15 Unseating Reduced Voltage (RV) Limit = Unseating Torque / Allowable Reduced Voltage Pullout Torque Current Limit = Average Motor Current / 120% of Rated Motor Current, Up to 200% of Rated Motor Current is acceptable.
Rising Stem-Limit Switch Controlled Motor Orerated Valve Definitions Close Reduced Voltage (RV) Limit = Close Torque at Limit Switch Tnp/(Allowable Reduced Voltage Running Torque Piston Effect Torque)
Close (Actuator) Thrust Limit = Total Thrust following Limit Switch Trip / (Actuator Thrust Rating -
Piston Effect Thrust)
Close (Actuator) Torque Limit = Total Torque following Limit Switch Trip I (Actuator Torque Rating
- Piston Effect Torque)
COF (Stem/Stem Nut Coefficient of Friction) = Stem/Stem Nut Interface Coefficient of Friction Valve Thrust Limit = Total Thrust following Limit Switch Trip / (Valve Thrust Rating Piston Effect Thrust)
Lubrication Limit = Measured Stem-to-Stem Nut Friction Coefficient / Callaway Target Friction Coefficient of 0.15 Unseating Reduced Voltage (RV) Limit = (Unseating Torque + Bearing DP Torque + Running Load) I Allowable Reduced Voltage Pullout Torque to ULNRC-06410 Page 11 of 45 18 MONTH MOTOR OPERATED VALVE PROGRAM PERFORMANCE INDICATOR REPORT FOR CYCLE 20 Current Limit = Average Motor Current! 120% of Rated Motor Current, Up to 200% of Rated Motor Current is acceptable.
Quarter Turn-Limit Switch Controlled Motor Operated Valve Definitions Open Stroke Operable Load Limit = (DP Effect Torque + Stem Load) / Mm (Actuator Torque Rating, RV Running Torque, Stem Allowable Torque)
Open Stroke Unseating Reduced Voltage (RV) Limit = (Unseating Torque + Bearing DP Torque +
Running Load) / Allowable Reduced Voltage Pullout Torque Open Stroke Actuator Limit = (Total Torque following Limit Switch Trip + Bearing Differential Pressure Torque) / Actuator Torque Rating Open Stroke Disk/Pin Limit = Unseating Torque / Disk/pin Allowable Torque Open Stroke Valve Stem Limit = (Unseating Torque + Running Load + Bearing DP Torque) /
Stem Allowable Torque Open Stroke Current Limit = Average Motor Current / 120% of Rated Motor Current, Up to 200%
of Rated Motor Current is acceptable.
Design Margin Open (%) = ((Minimum Available Torque at Reduced Voltage Maximum Required Torque )/Maximum Required Torque) X 100 Close Stroke Reduced Voltage (RV) Limit = (Close MAT at LST + Close Bearing DP Torque +
Running Load) / Allowable Reduced Voltage Running Torque Close Stroke Actuator Limit = (Total Torque following Limit Switch Trip + Bearing Differential Pressure Torque) / Actuator Torque Rating Close Stroke Disk/Pin Limit = (Total Torque following Limit Switch Trip Running Load) / Disk/pin Allowable Torque Close Stroke Valve Stem Limit = (Total Torque following Limit Switch Trip + Bearing Differential Pressure Torque) / Stem Allowable Torque Close Stroke Current Limit = Average Motor Current I 120% of Rated Motor Current, Up to 200%
of Rated Motor Current is acceptable.
Design Margin Close (%) = ((Minimum Available Torque at Reduced Voltage Maximum required Torque )/Maximum Required Torque) X 100 Prepared by: Michael E. Brenner 721 Date: 6/20/2015 9
DESCRIPTION OF MOTOR OPERATED VALVES Safety Close Operator Valve Location Functional Description PPR Description of MOV Functions Control Type Type Enclosure 5 to ALHV0005 is a 4 inch Masoneilan flow control globe valve equipped with a Modutronic controlled SMB ULNRC-06410 00 Limitorque actuator. The motor operated valve (MOV) has active safety functions to open and close Page 12 of 45 against 1725 psid. Close control is by torque Open & Torque Rising ALHV0005 MDAFP B TO SIG D HV switch. Close Switch Stem Globe ALHV0007 is a 4 inch Masoneilan flow control globe valve equipped with a Modutronic-controlled SMB 00 Umitorque actuator. This MOV has been setup to open and close against 1725 psid as required for Open & Torque Rising ALHV0007 MDAFP B TO S/G A HV its active safety functions. Close Switch Stem Globe ALHV0009 is a 4 inch Masoneilan flow control globe valve equipped with a Modutronic controlled SMB 00 Limitorque actuator. The motor operated valve (MOV) has active safety functions to open and close against 1725 psid. Close control is by torque Open & Torque Rising ALHV0009 MDAFP TO S/G B HV switch. Close Switch Stem Globe ALHVOO1 1 is a 4 Masoneilan flow control globe valve equipped with a Modutronic controlled SMB 00 Limitorque actuator. The Motor Operated Valve fMOV) is setup to open and close against 1725 psid Open & Torque Rising ALHVOOI 1 MDAFP TO SJG C HV as required for its active safety functions. Close Switch Stem Globe ALHVOO3O is a 6 inch Fisher Butterfly valve equipped with a Limitorque SMB 00 actuator and an Limit HBC-1 Limitorque gearbox. This MOV has been Switch set up to open against 157 psid as required by its without active safety function. It is also set up to close Torque Quarter ALHVOO3O ESW TO MD AFP B HV against 157 psid for commercial function. Open Switch Turn Butterfly ALHVOO31 is a 6 inch Fisher Butterfly valve equipped with a Limitorque SMB 00 operator. This Limit MOV has been set up to open against 156 psid as Switch required for its active safety function. It is also set without up to close against 156 psid for commercial Torque Quarter ALHVOO31 ESW TO MD AFP A HV function. Open Switch Turn Butterfly AUACHMENT2 lof 34
DESCRIPTION OF MOTOR OPERATED VALVES ALHVOO32 is an 8 inch Fisher butterfly valve Enclosure 5 to equipped with a Limitorque type SMB-00 actuator Limit and H1BC gearbox. This MOV has been set up to Switch ULNRC-06410 open against 155 psid, as required for its active without safety function. Is has been set up to close against Torque Quarter Page 13 of 45 ALHVOO32 ESW TO TD AFP HV 155 psid for commercial function. Open Switch Turn Butterfly ALHVOO33 is a 8 inch Fisher Butterfly valve equipped with a Limitorque SMB 00 actuator and an Limit HBC-1 Limitorque gearbox. This MOV has been Switch set up to open against 157 psid as required by its without active safety function. It is also set up to close Torque Quarter ALHVOO33 ESW TO TD AFP HV against 157 psid for commercial function. Open Switch Turn Butterfly ALHVOO34 is an 8 inch Anchor-Darling flex wedge gate valve, equipped with a torque close, type SMB 00 actuator. This MOV is set up to open against 25 Flex psid and close against 135 psid as required by its Open & Torque Rising Wedge ALHVOO34 CST TO MD AFP B HV active safety functions. Close Switch Stem Gate ALHVOO35 is an 8 inch Anchor-Darling flex wedge gate valve, equipped with a torque close, type SMB 00 actuator. This MOV is set up to open against 25 Flex psid and close against 154 psid as required by its Open & Torque Rising Wedge ALHVOO35 CST TO MD AFP A HV active safety functions. Close Switch Stem Gate ALHVOO36 is a 10 Anchor-Darling flex wedge gate valve equipped with a type SMB-00 Limitorque actuator. This valve is set up to open against a Flex design DP of 25 psid and close against 156 psid for Open & Torque Rising Wedge ALHVOO36 CST TO TD AFP HV its active safety functions. Close Switch Stem Gate BBHVOO13 is a 3 Velan flex wedge gate valve equipped with a Limitorque SMB-00 operator. Valve closure is controlled by torque. This MOV has been Flex RCP A THRM BAR COOL set up to open against 145 psid and close against Open & Torque Rising Wedge BBHVOOI3 COIL COOL WTR OUT HV 2335 psid as requited for its active safety functions. Close Switch Stem Gate AUACHMENT2 2o134
DESCRIPTION OF MOTOR OPERATED VALVES BBHVOO14 is a 3 Velan flex wedge gate valve equipped with a Limitorque SMB-OO operator. Enclosure 5 to Valve closure is controlled by torque. This MOV has been set up to close against 2335 psid as ULNRC-06410 required for its active safety function. BBHVOO14 Flex RCP B THRM BAR COOL has also been set up to open against 156 psid for Open & Torque Rising Wedge Page 14 of 45 BBHVOO14 COIL COOL WTR OUT HV commercial purposes. Close Switch Stem Gate BBHVOO15 is a 3 Velan flex wedge gate valve equipped with a Limitorque SMB-OO operator.
Valve closure is controlled by torque. This valve has been set up to close against 2335 psid as required by its active safety function. BBHVOO1 5 Flex RCP C THRM BAR COOL has also been set up to open against 145 psid for Open & Torque Rising Wedge BBHVOO15 COIL COOL WTR OUT HV commercial purposes. Close Switch Stem Gate BBHVOO16 is a 3 Velan flex wedge gate valve equipped with a Limitorque SMB-OO operator.
Valve closure is controlled by torque. This MOV has been set up to open against 145 psid and close Flex RCP D THRM BAR COOL against 2335 psid as required by its active safety Open & Torque Rising Wedge BBHVOO16 COIL COOL WTR OUT HV functions. Close Switch Stem Gate BBHV8000A is a 3 inch Westinghouse flex wedge gate valve equipped with a Limitorque SB-OO Limit actuator. The MOV is limit-controlled. The MOV Switch has been set up to open against 2485 psid and without Flex RCS PZR OUT PWR OPER close against 2335 psid as required for its active Open & Torque Rising Wedge BBHV8000A RLF HV safety functions. Close Switch Stem Gate BBHV8000B is a 3 inch Westinghouse flex wedge gate valve equipped with a Limitorque SB-OO Limit actuator. The Motor Operated Valve (MOV) is limit- Switch controlled. The MOV has been set up to open without Flex RCS PZR OUT PWR OPER against 2485 psid and close against 2335 psid as Open & Torque Rising Wedge BBHV8000B RLF HV required for its active safety functions. Close Switch Stem Gate BBHV8O37A is a 4 Westinghouse flex wedge gate valve equipped with a type SB-OO actuator. This motor operated valve is set up to open and close Flex RCS PRI OUT TO CTMT against 104 psid. Closure is controlled by torque Open & Torque Rising Wedge BBHV8O37A NORM SMP ISO HV switch. Close Switch Stem Gate AUACHMENT2 3of34
DESCRIPTION OF MOTOR OPERATED VALVES BBHV8O37B is a 4 Westinghouse flex wedge gate Enclosure 5 to valve equipped with a type SB-00 actuator. This Flex RCS PRT OUT TO CTMT valve is set up to open and close against 104 psid. Open & Torque Rising Wedge ULNRC-06410 BBHV8O37B NORM SMP ISO HV Closure is controlled by torque switch Close Switch Stem Gate Page 15 of 45 BBHV8351A is a 2-inch Velan globe valve equipped with a Limitorque SMB-00 actuator. The close stroke is torque switch controlled. The MDV is passive, having no active safety functions. The RCP A SEAL WTR SPLY ISO MOV is, however, set up to open and close against Torque Rising BBHV8351A HV 2813 psid for commercial purposes. None Switch Stem Globe BBHV8351 B is a 2 inch Velan globe valve equipped with a Umitorque SMB-00 actuator. The close stroke is torque switch controlled. The MDV is passive, having no active safety functions. The RCP B SEAL WTR SPLY ISO MOV is, however, set up to open and close against Torque Rising BBHV8351B HV 2813 psid for commercial purposes. None Switch Stem Globe BBHV8351C is a 2 inch Velan globe valve equipped with a Limitorque SMB-OO actuator. The close stroke is torque switch controlled. The MDV is passive, having no active safety functions. The RCP C SEAL WTR SPLY ISO MOV is, however, set up to open and close against Torque Rising BBHV8351C HV 2813 psid for commercial purposes. None Switch Stem Globe BBHV8351 D is a 2-inch Velan globe valve equipped with a Limitocque SMB-00 actuator. The close stroke is torque switch controlled. The MDV is passive, having no active safety functions. The RCP D SEAL WTR SPLY ISO MDV is, however, set up to open and close against Torque Rising BBHV835JD HV 2813 psid for commercial purposes. None Switch Stem Globe ATTACHMENT 2 4 of 34
DESCRIPTION OF MOTOR OPERATED VALVES BBPV87O2A is a 12 inch Westinghouse flex wedge Enclosure 5 to gate valve equipped with an SMB-2 Limitorque actuator. This motor operated valve (MOV) has ULNRC-06410 been set up to open against 380 psid and close against 464 psid as required for its active safety Page 16 of 45 functions related to flow control and close against 60 psid as required for its active safety function related to pressure isolation. The MOV uses soft Torque Flex RCS LOOP 1 HOT LEG TO seating, torque control in the close stroke direction Open & Switch Soft Rising Wedge BBPV87O2A RHR PMPS PCV ISO and limit switch control in the open stroke direction. Close Seating Stem Gate BBPV87O2B is a 12 inch Westinghouse flex wedge gate valve equipped with an SMB-2 Limitorque actuator. This motor operated valve fMOV) has been setup to open against 380 psid and close Torque Flex RCS LOOP 4 HOT LEG TO against 464 psid as required for its active safety Open & Switch Soft Rising Wedge BBPV87O2B RHR PMPS PCV ISO functions. Close Seating Stem Gate BGHV8100 is a 2 Velan globe valve equipped with a type SMB-00 actuator. Closure is controlled by torque switch. This valve has been set up to close against 155 psid as required by its active safety SEAL WTR RTN OUTER tunction. BGHV8100 has also been set up to open Torque Rising BGHV8100 CTMT ISO against 155 psid for commercial purposes. Close Switch Stem Globe BGHV81O4 is a 2 inch Velan Globe valve with an SMB-00 Limitorque operator. The valve has been set up to meet safety related thrust requirements of 2328 lbs in the open direction and 2757 lbs in the close direction. BGHV81 04 is setup to use torque EMERG BORATE TO switch control for the close stroke and limit switch A& Torque Rising BGHV8IO4 B HDR ISO HV control for the open stroke.
Close Switch Stem Globe BGHV81O5 is a 3 inch Westinghouse flex wedge gate valve equipped with a Limitorque SB-00 actuator. The MDV is designed to close on limit against 2750 psid as required for its active safety CVCS CHARGING HDR TO function. BGHV81O5 has no safety function to Flex REGEN HX OUTER CTMT open, but has been set up to open against 2750 Limit Rising Wedge BGHV81O5 ISO VLV psid for commercial purposes Close Switch Stem Gate ATACHMENT2 5of34
DESCRIPTION OF MOTOR OPERATED VALVES BGHV81O6 is a 3 inch Westinghouse flex wedge Enclosure 5 to gate valve equipped with a Limitorque SB-00 actuator. The MOV is limit-controlled. The MOV ULNRC-06410 has been set up to close against 2750 psid as CVCS CHARGING HDR TO required for its active safety function. The MOV has Flex Page 17 of 45 REGEN HX OUTER CTMT no safety function to open, but has been set up to Limit Rising Wedge BGHV81O6 ISO VLV open against 2750 psid for commercial purposes Close Switch Stem Gate BGHV81 09 BGHV8J1O is a 2 inch Velan globe valve equipped with a SMB-00 Limitorque actuator. The motor-operated valve (MOV) is set up to close using torque switch control and open using limit switch control. The MOV has been set up to open and A CCP DISCH MINIFLOW TO close against 2750 psid as required for its active Open & Torque Rising BGHV81 10 SEAL WTR HX ISO safety functions. Close Switch Stem Globe BGHVS1 1 1 is a 2 inch Velan globe valve equipped with a torque closed SMB-00 Limitorque actuator.
This MOV is set up to close against 2750 psid and CCP B DISCH MINIFLOW ISO open against 2750 as required by its active safety Open & Torque Rising BGHV8111 VLV function. Close Switch Stem Globe BGHV81 12 is a 2 inch Velan globe valve equipped with a Limitorque SMB-00 actuator. The close stroke is torque switch controlled. The MOV has been set up to close against 155 psid as required for its active safety function. The MOV has no SEAL WTR RTN INNER CTMT safety function to open, but has been set up to open Torque Rising BGHV8112 ISO HV against 155 psid for commercial purposes Close Switch Stem Globe BGHV8357A is a 1 Anchor Darling globe valve equipped with an SMB-000 operator. Valve closure is controlled by torque. The MOV is jog controlled; i.e. the control circuit does not seal in.
CVCS CCP A DISCH TO RCP BGHV8357A is set up to open and close against Open & Torque Rising BGHV8357A SEALS THROTTLE VLV 2722 psid as required by its active safety function Close Switch Stem Globe ATTACHMENT 2 6 of 34
DESCRIPTION OF MOTOR OPERATED VALVES BGHV8357B is a 1 Anchor Darling globe valve Enclosure 5 to equipped with an SMB-000 operator. Valve closure is controlled by torque. The MOV is jog controlled; ULNRC-06410 i.e., the control circuit does not seal in.
CVCS CCP B DISCH TO RCP BGHV8357B is set up to open and close against Open & Torque Rising Page 18 of 45 BGHV8357B SEALS THROT VLV 2722 psid as required by its active safety function. Close Switch Stem Globe BGLCVQ112B is a 4 Westinghouse flex wedge gate valve equipped with a type SB-00 operator.
This valve has active safety functions to open and close against 100 psid. Closure is controlled by Open & Torque Rising BGLCVO112B CVCS VCT OUT UPSTRM ISO torque switch. Close Switch Stem Globe BGLCVO1 12C is a 4 inch Westinghouse flex wedge gate valve equipped with a SB-0O Limitorque actuator. The motor-operated valve (MOV) is set up to close using torque switch control. The MOV has been set up to close against 100 psid as required for its safety function. BGLCVO1 1 2C has no safety function to open, but has been set up to Torque Rising BGLCVO112C CVCS VCT OUT DNSTRM ISO open against 100 psid for commercial purposes Close Switch Stem Globe BNHV0003 is a 12 flex wedge gate valve equipped with a type SMB-00 actuator. Closure is controlled RWST TO CTMT SPRY PMP by torque switch. This valve has a required safety Open & Torque Rising BNHV0003 B HV function to open and close against 32 psid. Close Switch Stem Globe BNHV0004 is a 12 flex wedge gate valve equipped with a type SMB-00 actuator. Closure is controlled RWST TO CTMT SPRY PMP by torque switch. This valve has an active safety Open & Torque Rising BNHV0004 A HV function to open and close against 32 psid. Close Switch Stem Globe BNHV88O6A is a Westinghouse 8-inch B flex wedge gate valve equipped with a type SB-00 actuator which opens and closes the valve on limit.
BNHV88O6A is set-up to meet an extrapolated Flex SI PMP A SUCT FROM RWST close DP of 2350 lbs. and an extrapolated open DP Limit Rising Wedge BNHV88O6A ISO of 4219 lbs. The safety related function is to close. Close Switch Stem Gate AUACHMENT2 7of34
DESCRIPTION OF MOTOR OPERATED VALVES BNHV88O6B is a Westinghouse 8-inch B flex Enclosure 5 to wedge gate valve equipped with a type SB-00 actuator which opens and closes the valve on limit.
ULNRC-06410 BNHV8SO6A is set-up to meet an extrapolated Flex SI PUMPS SUCT FROM close DP of 2350 lbs. and an extrapolated open DP Limit Rising Wedge Page 19 of 45 BNHV88O6B RWST ISO of 4219 lbs. The safety related function is to close. Close Switch Stem Gate BNHV8812A is a Westinghouse 14 flex wedge gate valve equipped with a type SB-i actuator.
Closure is controlled by torque switch. The motor operated valve (MOV) has been setup to close against 33 psid as required for its active safety Flex RWST TO RHR PMP A SUCT function and has been setup to open against 33 Torque Rising Wedge BNHV8812A ISO VLV psid to satisfy its commercial function Close Switch Stem Gate BNHV8812B is a Westinghouse 14 flex wedge gate valve equipped with a type SB-i actuator.
Closure is controlled by torque switch. The motor operated valve (MOV) has been setup to close against 33 psid as requited for its active safety Flex RWST TO RHR PMP B SUCT function and to open against 33 psid to satisfy its Torque Rising Wedge BNHV8812B ISO VLV commercial function. Close Switch Stem Gate BNHV8813 is a 2-inch Velan globe valve equipped with a Limitorque SMB-00 actuator. The close stroke is torque switch controlled. The MOV has been setup to close against 1552 psid as required for its active safety function. The MOV has no SI PMPS MINIFLOW TO safety function to open, but has been set up to open Torque Rising BNHV8813 RWST ISO VLV (3.0.3) against 1552 psid for commercial purposes Close Switch Stem Globe BNLCVO112D is a 4 Westinghouse flex wedge gate valve equipped with an SB-00 operator. Valve closure is controlled by limit switch. There is no close torque switch in the circuit. The Motor Operated Valve (MOV) has been setup to open Flex CCP A SUCT FROM RWST against a safety related DP of 92 psid, and close Open & Limit Rising Wedge BNLCVO112D ISO VLV against a safety related DP 01242 psid. Close Switch Stem Gate AUACHMENT2 8of34
DESCRIPTION OF MOTOR OPERATED VALVES BNLCVOJ12E is a 4 Westinghouse flex wedge Enclosure 5 to gate valve with a type SB-00 Limitorque actuator.
Both the close and open strokes are controlled by ULNRC-06410 limit switch. This MOV has been set up to open Flex CCP B SUCT FROM RWST against 92 psid and close against 242 psid, as Open & Limit Rising Wedge BNLCVO1 12E ISO VLV Page 20 of 45 required by its active safety functions. Close Switch Stem Gate ECHVOO1 1 is an 12 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an H BC-i Limitorque gearbox. This Motor Operated Valve (MOV) has been setup to open and close FUEL POOL HX A SHELL against 119 psid, as required by its active safety Open & Limit Quarter ECHVOO1 i SIDE CCW OUT ISO functions. Close Switch Turn Butterfly ECHVOO12 is an 12 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-1 Limitorque gearbox. This MOV has been FUEL POOL HX B SHELL setup to open and close against 119 psid, as Open & Limit Quarter ECHVOO12 SIDE CCW OUT ISO required by its active safety functions. Close Switch Turn Butterfly EFHVO023 is a 30 inch Anchor-Darling stainless steel butterfly valve equipped with an SMB-00 Limitorque actuator and an HBC-3 Limitorque gearbox. This MOV has been setup to close against 157 psid as required by its active safety function. The valve has no safety function to open, SERV WIR TO ESW TRN A but has been set up to open against 81 psid as Limit EFHVOO23 UPSTRM HV required by commercial function. Close Switch QT Butterfly EFHVOO24 is a 30 inch Anchor-Darling butterfly valve equipped with an SMB-00 Limitorque actuator and an HBC-3 Limitorque gearbox. This MOV has been setup to close against 150 psid as required by its active safety function. The valve has no safety SERV WTR TO ESW TRN B function to open; the MOV is set up to open against Limit Quarter EFHVOO24 UPSTRM HV 81 psid as requited by commercial function Close Switch Turn Butterfly ATFACHMENT2 9of34
DESCRIPTiON OF MOTOR OPERATED VALVES EFHVOO25 is a 30 inch Anchor-Darling butterfly Enclosure 5 to valve equipped with an SMB-00 Limitorque actuator and an HBC-3 Limitorque gearbox. This MOV has ULNRC-06410 been setup to close against 157 psid as required by its active safety function. The valve has no safety SERV WTR TO ESW IRN A Page 21 of 45 function to open; the MOV is set up to open against Limit Quarter EFHVOO25 DNSTRM HV 81 psid as required by commercial function. Close Switch Turn Butterfly EFHVOO26 is a 30 inch Anchor Darling butterfly valve equipped with an SMB-00 Limitorque actuator and an HBC-3 Limitorque gearbox. This MOV has been setup to close against 150 psid as required by its active safety function. The valve has no safety SERV WTR TO ESW TRN B function to open; the MOV is set up to open against Limit Quarter EFHVOO26 DNSTRM HV 81 psid as required by commercial function Close Switch Turn Butterfly EFHVOO31 is a 14 inch Neles-Jamesbury butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This ESW TRN A TO CTMT AIR MOV has been set up to open and close against Open & Limit Quarter EFHVOO31 CLRS OUTER CTMT HV 134 psid as required by its active safety functions Close Switch Turn Butterfly EFHVOO32 is a 14 inch Neles-Jamesbury butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This ESW TRN B TO CTMT AIR MOV has been setup to open and close against 152 Open & Limit Quarter EFHVOO32 CLRS OUTER CTMT HV psid as required by its active safety functions. Close Switch Turn Butterfly EFHVOO33 is a 14 tnch Neles-Jamesbury butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This ESW TRN A TO CTMT AIR MOV has been set up to open and close against Open & Limit Quarter EFHVOO33 CLRS INNER CTMT HV 154 psid as required by its active safety functions Close Switch Turn Butterfly EFHVOO34 is a 14 inch Neles-Jamesbury butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This Motor Operated Valve (MOV) has been setup to ESW TRN B TO CTMT AIR open and close against 150 psid as required by its Open & Limit Quarter EFHVOO34 CLRS INNER CTMT HV active safety functions Close Switch Turn Butterfly AUACHMENT2 10of34
DESCRIPTION OF MOTOR OPERATED VALVES EFHVOO37 is a 30 inch Anchor-Darling butterfly valve equipped with an SMB-00 Limitorque actua Enclosure 5 to tor and an HBC-3 Limitorque gearbox. This MOV has been setup to open against 159 psid as requ ULNRC-06410 ired by its active safety function. The valve has no safet y Page 22 of 45 function to close; the commercial requirement EFHVOO37 ESW TRN A TO UHS HV is to Limit Quarter close against 159 psid Open Switch Turn Butterfly EFHVOO38 is a 30 inch Anchor-Darling butterfly valve equipped with an SMB-00 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MDV has been set up to open against 151 psid as requ ired by its active safety function and close against Serv ice Water System return pressure as a commerc EFHVOO38 ESW TRN B TO UHS HV ial Limit Quarter requirement.
Open Switch Turn Butterfly EFHVOO39 is a 30 inch Anchor-Darling butterf ly valve equipped with an SMB-00 Limitorque actuator and an HSC-3 Limitorque gearbox. This MOV has been setup to close against 82 psid as required ESW TRN A TO SERV WTR for its active safety function and open against 146 EFHVOO39 UPSTRM HV psid Limit Quarter as required for its commercial function.
Close Switch Turn Butterfly EFHVOO4O is a 30 inch Anchor Darling butterfly valve equipped with an SMB-00 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MDV has been setup to close against 96 psid as required by its active safety function. The valve has no safet ESW TRN B TO SERV WTR y function to open; the MOV is set up to open EFHVOO4O UPSTRM HV against Limit Quarter 146 psid as required by commercial function Close Switch Turn Butterfly EFHVOO4J is a 30 inch Anchor-Darling butterfly valve equipped with an SMB-00 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MDV has been setup to close against 82 psid as required ESW TRN A TO SERV WTR for its active safety function and open against 146 EFHVOO41 DNSTRM HV psid Limit Quarter as required for its commercial function.
Close Switch Turn Butterfly AUACHMENT2 110134
DESCRIPTION OF MOTOR OPERATED VALVES EFHV0O42 is a 30 inch Anchor-Darling butte rfly Enclosure 5 to valve equipped with an SMB-00 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MOV has ULNRC-06410 been setup to close against 81 psid as requ ired by its active safety function and open against Serv ESW TRN B TO SERV WTR ice Page 23 of 45 Water System return pressure at 50 psid EFHVOO42 DNSTRM HV across the Limit Quartet MOV. EFHVOO42 has no safety function to open Close Switch Turn Butterfly EFHVOO45 is a 14 inch Neles-Jamesbury butterfly valve equipped with an SMB-000 Lim itorque actuator and an HBC-2 Limitorque gearbox.
ESW TRN A FROM CTMT AIR MOV has This EFHVOO45 been set up to open and close against CLRS INNER CTMT HV Open & Limit Quarter 154 psid as required by its active safet func y tions. Close Switch EFHVOO46 is a 14 inch Neles-Jamesbury Turn Butterfly butterfly valve equipped with an SMB-000 Limitorq ue actuator mated to an HBC-2 Limitorque gearbox.
This MOV has been setup to open and ESW TRN B FROM CTMT AIR against close EFHVOO46 157 psid as required by its active safety CLRS INNER CTMT HV Open & Limit Quarter functions.
EFHVOO47 is a 10 inch Neles-Jamesbu Close Switch Turn Butterfly ty butterfly valve equipped with an SMB-000 Limitorq ue actuator and an HBC-1 Limitorque gear box. This MOV has been set up to open and close ESW TRN A FROM CTMT AIR and 64 against 0 psid respectively, as required by its activ EFHVOO47 CLRS BYP ISO HV e Open & Limit Quartet safety functions.
Close Switch Turn Butterfly EFHVOO48 is a 10 inch Neles-Jamesbury butterfly valve equipped with an SMB-000 Limitorq ue actuator and an HBC-1 Limitorque gearbox.
This Motor Operated Valve (MOV) has been ESW TRN B FROM CTMT AIR open and set up to close against 0 and 57 psid, respective EFHVOO48 CLRS BYP ISO HV ly, Open & Limit Quartet as required by its active safety functions
. Close Switch EFHVOO49 is a 14 inch Neles Jamesbur Turn Butterfly y butterfly valve equipped with an SMB-000 Limitorq ue actuator and an HBC-2 Limitorque gear box. This MOV has been setup to open and close ESW TRN A FROM CTMT AIR and against 10 64 psid, respectively, as required by its EFHVOO49 CLRS OUTER CTMT HV active Open & Limit Quarter safety functions.
Close Switch Turn Butterfly AUACHMENT2 12 of 34
DESCRIPTION OF MOTOR OPERATED VALVES EFHVOO5O is a 14 inch Neles-Jamesbury butte rfly valve equipped with an SMB-000 Limitorq ue Enclosure 5 to actuator and an HBC-2 Limitorque gearbox. This MOV has been setup to open and close again ESW TRN B FROM CTMT AIR and 57 psid, st 10 ULNRC-06410 respectively, as required by its active EFHVOO5O CLRS OUTER CTMT HV Open & Limit Quarter safety functions Close Switch Turn Butterfly Page 24 of 45 EFHVOO51 is a 24 inch Fisher Butterfly valv e
equipped with a SMB 00 Limitorque actua tor and a HBC-3 Limitorque gearbox. This valve has been set up to open against 123 psid as required by its active safety function. The valve has no ESW TRN A TO CCW HX A safety function to close; however the MDV has EFHVOO51 HV been set Limit up to close against 157 psid for commercial Quarter function Open Switch Turn EFHVOO52 is a 24 inch Fisher butterfly valv Butterfly e
equipped with an SMB 00 Limitorque actua tor and a HBC-3 Limitorque gearbox. It has been set up to open against 123 psid as required by its activ e
safety function. EFHVOO52 has no safety ESW IRN B TO CCW HX B function to close, but has been set up to close again EFHVOO52 HV st 123 Limit Quarter psid for commercial function.
Open Switch Turn Butterfly EFHVOO59 is a 24 inch Fisher Butterfly valv e
equipped with an SMB 00 Limitorque actua tor with an HBC-3 Limitorque gearbox. This valv e has been set up to close against 1 13 psid as requ ired by its active safety function. EFHVOO59 has no ESW TRN A FROM CCW HX safety function to open; but has been set up to open EFHVOO59 A HV Limit Quarter against 1 13 psid for commercial function.
Close Switch Turn Butterfly EFHVOO6O is a 24 inch Fisher butterfly valv e
equipped with an SMB-O0 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MDV has been setup to close against 77 psid as requited by its active safety function. EFHVOO6O has ESW TRN B FROM CCW HX no safety function to open, but has been set up to EFHVOO6O B HV open Limit against 77 psid for commercial purposes Quarter
. Close Switch Turn Butterfly ATTACHMENT 2 13 of 34
DESCRIPTION OF MOTOR OPERATED VALVES EFHVOO65 is a 30 inch Anchor Darling butterfly valve equipped with an SMB-00 Limitorque actua Enclosure 5 to tor and an HBC-3 Limitorque gearbox. This MOV has ESW UHS COOL-TWR TRN A been setup to open ULNRC-06410 and close against 20 psid as Open &
EFHVOO65 BYP HV requited by its active safety functions. Limit Quarter Close Switch Turn Butterfly Page 25 of 45 EFHVOO66 is a 30 inch Anchor Darling butterfly valve equipped with an SMB-00 Limitorque actua tor and an HBC-3 Limitorque gearbox. This MOV ESW UHS COOL-TWR TRN B been setup to has open and close against 20 psid as Open &
EFHVOO66 BYP HV required by its active safety functions. Limit Quarter Close Switch Turn Butterfly FHV0097 is a 3 inch Velan solid wedge gate valve equipped with an SMB-000 Limitorque actua tor.
The MOV is set up to close on torque and open on limit. This MOV has been set up to close again st 125 psid as required by its active safety functio n.
The valve has no safety function to open; the MOV ESW PMP A DISCH RECIRC is set up to open against 125 psid as required Solid EFHVOO97 HV by its Torque Rising commercial function. Wedge Close Switch Stem Gate EFHVOO98 is a 3 inch Velan solid wedge gate valve equipped with an SMB-000 Limitorque actua tor.
The Motor Operated Valve fMOV) is set up to close on torque and open on limit. This MOV has been set up to close against 150 psid as required by its active safety function. The valve has no safet y
function to open however; the MOV is set up to ESW PMP B DISCH RECIRC open against 125 psid as requited by its com Solid EFHVOO98 HV mercial Torque Rising function. Wedge Close Switch Stem Gate EFPDVOO19 is a Stainless Steel 3 Flowserve flex wedge gate valve equipped with a torque contro lled Limitotque SMB-000 actuator. This motor oper ated valve (MOV) has been setup to open and close ESW S-C STR A DRN DP against 148 psid as required by its active Flex EFPDVOO19 CTRL VLV safety Open & Torque Rising functions Wedge Close Switch Stem Gate ATACHMENT2 14o134
DESCRIPTION OF MOTOR OPERATED VALVES EFPDVOO2O is a Stainless Steel 3 Flowserve flex wedge gate valve equipped with a torque controlled Enclosure 5 to Limitorque SMB-000 actuator. This motor operated ESW S-C STR B DRN DP valve has been setup to open and close against 150 Flex ULNRC-06410 EFPDVOO2O CTRL VLV Open & Torque Rising Wedge psid as required by its active safety functions Close Switch Stem Gate Page 26 of 45 EGHVOO1 I is a 1 .5 inch Yarway rotating rising stem globe valve with a Limitorque SMB-000 operator.
This MOV has been set up to open against 137 psid as required by its active safety function and close ESW TO CCW TRN A against 137 psid as desired by its commercial EGHVOO1 1 UPSIRM HV Torque Rising function Open Switch Stem Globe EGHVOO12 is a 1.5-inch Yarway rotating rising stem globe valve with a Limitorque SMB-000 operator.
This MOV has been set up to open against 139 psid as required by its active safety function and close ESW TO CCW TRN B against 139 psid as required by its commercial EGHVOO12 UPSTRM HV Torque Rising function.
Open Switch Stem Globe EGHVQO13 is a 1.5 inch Yarway rotating rising stem globe valve with a Limitorque SMB-000 operator.
This MOV has been set up to open against 137 psid as required by its active safety function and close ESW TO CCW TRN A against 137 psid as desired by its commercial EGHVOO13 DNSTRM HV TorqLle Rising function.
Open Switch Stem Globe EGHVOO14 is a 1.5 inch Yarway rotating rising stem globe valve with a Limitorque SMB-000 operator.
This MOV has been set up to open against 139 psid as required by its active safety function and close ESW TO CCW TRN B against 139 psid as required by its commercial EGHVOO14 DNSTRM HV Torque Rising function.
Open Switch Stem Globe EGHVOO15 is an 18 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This MOV has been CCW TRN A SPLYIRTN ISO setup to open and close against 109 psid as EGHVOO15 HV Open & Limit Quarter required by its active safety functions.
Close Switch Turn Butterfly AUACHMENT2 15of34
DESCRIPTION OF MOTOR OPERATED VALVES EGHVOO16 is a 18 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This Motor Enclosure 5 to Operated Valve (MOV) has been setup to open and CCW TRN B SPLY/RTN ISO close against 109 psid as required by its active ULNRC-06410 EGHVOO16 HV Open & Limit Quarter safety functions.
Close Switch Turn Butterfly Page 27 of 45 EGHVOO53 is an 18 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This MOV has been setup to open and close against 109 psid as EGHVOO53 CCW TRN A SPLY ISO HV Open & Limit Quarter required by its active safety functions Close Switch Turn Butterfly EGHVOO54 is a 18 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-2 Limitorque gearbox. This MOV has been setup to open and close against 108 psid as EGHVOO54 CCW TRN B SPLY ISO HV Open & Limit Quarter requited by its active safety functions.
Close Switch Turn Butterfly EGHVOO58 is a 12 inch Anchor-Darling double disk gate valve equipped with an SMB-00 Limitorque actuator. A torque switch is used for control in the closing stroke direction. Open control is achieved by limit switch. The motor-operated valve (MOV) has been set up to close against 112 psid as required by its active safety function. EGHVOO5B CCW TO CTMT OUTER ISO has been set up to open against 112 psid for EGHVOO58 HV TorqLle Rising Double commercial purposes.
EGHVOO59 Close Switch Stem Disk Gate EGHVOO6O is a 12 inch Anchor/Darling double disc gate valve equipped with an SMB-00 Limitorque actuator. This MOV has been setup to close against 1 12 psid as required for its active safety function. EFHVOO6O has also been set up to open EGHVOO6O Torque Rising Double against 112 psid to meet its commercial function.
Close Switch Stem Disk Gate AUACHMENT2 16of34
DESCRIPTION OF MOTOR OPERATED VALVES EGHVOO61 is a 4 Velan parallel slide gate valve equipped with an SMB-000 operator. Valve closure Enclosure 5 to is controlled by limit with a torque switch in the circuit for over thrust/torque protection. This MOV ULNRC-06410 Limit is setup to close against 112 psid as required by its CCW FROM RCP THRM BAR safety function. EGHVOO61 Switch with Parallel Page 28 of 45 is set up to open Torque Rising EGHVOO6J OUTER CTMT ISO against 1 12 psid for commercial purposes. Sliding Close Switch Stem Gate EGHVOQ62 is a 4 Velan parallel slide gate valve Limit equipped with a type SMB-0 actuator. This Switch with containment isolation valve has an active safety Torque Parallel function to close against 2335 psid and a EGHVOO62 Switch Rising Sliding commercial function to open against 112 psid. Close Bypass Stem Gate EGHVOO71 is an Anchor Darling 12 flex wedge gate valve equipped with a Limitorque type SMB00 operator. The valve has no active safety function to open or close. The MOV is setup to open and close CCW TO CTMT OUTER ISO against a commercial DP of 112 psid. Closure is Flex EGHVOO71 VLV Torque Rising Wedge controlled by torque switch None Switch Stem Gate EGHVO1O1 is an 18 Fisher butterfly valve equipped Limit with a Limitorque SMB-000 actuator and a Switch Limitorque H2BC gearbox. This MOV has been without setup to open and close against 104 psid, as Open &
EGHVO1O1 CCW TO RHR HX A ISO Torque Quarter required by its active safety functions. Close Switch Turn Butterfly EGHVO1O2 is an 18 Fisher butterfly valve equipped Limit with a Limitorque SMB-000 actuator and a H2BC Switch gearbox. This MOV has been setup to open and without close against 109 psid, as required by its active EGHVO1O2 CCW TO RHR HX B ISO Open & Torque Quarter safety functions Close Switch Turn Butterfly EGHVO126 is a 12 inch Anchor/Darling flex wedge gate valve equipped with an SMB-00 Limitorque actuator. The close stroke is torque switch controlled. The MOV is passive, having no safety function to open or close. EGHVO126 is, however, set up to open and close against 112 psid for Flex EGHVO126 CCW TO CTMT BYP VLV Torque Rising Wedge commercial purposes. None Switch Stem Gate AUACHMENT2 17of34
DESCRIPTION OF MOTOR OPERATED VALVES EGHVO127 is a 12 inch Anchor/Darling double disk gate valve equipped with a torque controlled Enclosure 5 to Limitorque SMB-OO actuator. This MOV has been set up to close against 112 psid as required by its passive safety function. EGHVO127 has also been ULNRC-06410 set up to open against 112 psid for commercial Torque EGHVO127 CCW TO CTMT BYP ISO HV Rising Double Page 29 of 45 purposes. Close Switch Stem Disk Gate EGHVO13O is a 12 inch Anchor/Darling double disc gate valve equipped with an SMB-OO Limitorque actuator. The close stroke is torque switch controlled. Originally, this valve had no safety function to open or close. However, to meet a commitment to operate against design basis differential pressure, unless an operator is stationed at the valve when the companion MOV (EGHVOO6O) is out of service, EGHVO13O has been CCW FROM RCS CTMT set up to open and close against 172 psid as EGHVO13O Torque Rising Double EGHVOO6O BYP ISO HV required for the part-time safety functions. Close Switch Stem Disk Gate EGHVO131 is a 12 inch Anchor/Darling double disc gate valve equipped with an SMB-OO Limitorque actuator. The close stroke is torque switch controlled. EGHVO13J has been set up to open CCW FROM CTMT and close against 112 psid as required for the part- Torque Rising Double EGHVO13J EGHVOO59 BYP ISO time safety functions. Close Switch Stem Disk Gate EGHVO132 is a 4 Velan parallel slide gate valve equipped with a type SMB-OO actuator. This containment isolation valve only has an active safety function to close when it is opened during Limit normal power operation. EGHVOJ32 must close Switch with against a OP of 2335 psid. Closure control is by Torque CCW FROM RCS CTMT Parallel limit switch with the torque switch as backup Switch EGHVO132 EGHVOO62 BYP ISO HV Rising Sliding protection. Close Bypass Stem Gate AUACHMENT2 18of34
DESCRIPTION OF MOTOR OPERATED VALVES EGHVO133 is a 4 inch Velan parallel disk gate valve equipped with an SMB-000 Limitorque actuator.
Enclosure 5 to Both the open and close strokes are controlled by limit switches, with the torque switch providing over-ULNRC-06410 torque and over-thrust protection. This valve has only passive safety functions, unless it is open for Page 30 of 45 maintenance on EGHVOO61 during power operations. The valve requires a Local Leak Rate Test (LLRT) whenever the close limit switch is adjusted. This MOV has been set up to open and CCW FROM RCP THRM BAR close against 112 psid as require d by its Rising Parallel EGHVO1 33 EGHVOO61 BYP ISO commercial functions. Close LS w/ TS Stem Disk Gate EJFCVO6JO is a Westinghouse 3 flex wedge gate valve equipped with a type SMB-000 Limitorque actuator, designed to open and close on limit. The A RHR PMP MINI FLOW MOV has been set up to open and close against Flex EJFCVO61O Open & Rising Wedge RECIRC FLOW CTRL VLV 200 psid as required for its active safety functions. Close LS w/o TS Stem Gate EJFCVO61 1 is a 3 inch Westinghouse flex wedge gate valve equipped with an SMB-000 Limitorque actuator, designed to open and close on limit. The RHR PUMP B MINIMUM MOV has been set up to open and close against Flex EJFCVO61 1 Open & Rising Wedge FLOW CTRL VLV 200 psid as required for its active safety functions. Close LS w/o IS Stem Gate EJHV8701A is a 12 inch Westinghouse flex wedge gate valve equipped with an SMB-2 Limitorque actuator. This motor operated valve fMOV) has been setup to open against 380 psid and close against 464 psid as required for its active safety functions related to flow control, and close against 60 psid as requited for its active safety function Flex EJHV87O1A Open & Rising Wedge RHR PUMP A SUCT ISO related to pressure isolation. Close TS-SS Stem Gate EJHV87O1B is a 12 inch Westinghouse flex wedge gate valve equipped with an SMB-2 Limitorque actuator. This motor operated valve (MOV) has been setup to open against 380 psid and close Flex against 464 psid as required for its active safety Open &
EJHV87O1B RHR PUMP B SUCT ISO Rising Wedge functions. Close IS-SS Stem Gate ATTACHMENT 2 19 of 34
DESCRIPTION Of MOTOR OPERATED VALVES EJHV8716A is a 10 inch Westinghouse flex wedge gate valve equipped with an SB-i Limitorque Enclosure 5 to actuator, designed to open and close on limit. The RHR TRN A SI SYS HOT LEG MOV has been set up to open and Flex ULNRC-06410 close against Open & Rising Wedge EJHV87J6A RECIRC ISO (3.0.3) 228 psid as requited for its active safety functions. Close LS wlo TS Stem Gate Page 31 of 45 E]HVB716B is a 10 inch Westinghouse flex wedge gate valve equipped with an SB-i Limitorque actuator, designed to open and close on limit. The RHR TRN B SI SYS HOT LEG MOV has been set up to open and Flex close against Open & Rising Wedge EJHV87J6B RECIRC ISO (3.0.3) 228 psid as required for its active safety functions. Close LS w/o IS Stem Gate EJHV88O4A is an 8 inch Westinghouse flex wedge gate valve equipped with a Limitorque SB-00 actuator. The MOV is limit-controlled. The MOV RHR TRN A CHARGING has been set up to open against 251 psid as Flex EJHV88O4A Open & Rising Wedge PUMPS SPLY ISO required for its active safety function Close LS w/o TS Stem Gate EJHV88O4B is an 8 inch Westinghouse flex wedge gate valve equipped with a Limitorque SB-00 actuator. The MOV is limit-controlled and has been RHR TRN B SI PUMPS SPLY set up to open and close against 251 psid as Flex EJHV88O4B Open & Rising Wedge ISO required for its active safety functions. Close LS w/o TS Stem Gate EJHV88O9A is a 10 inch Westinghouse flex wedge gate valve equipped with an SBD-3 Limitorque actuator. The open stroke is controlled by a limit switch. The close stroke, which was previously controlled by the torque switch, has been changed, per RFR 18919A, to also close on limit, to stop flow, with the torque switch activated at the end of the stoke to ensure leak tightness (soft seating). This RHR TRN A ACC INJ SPLY MOV has been setup to open and close against 228 Flex EJHV88O9A ISO f 3.0.3) Rising Wedge psid as required by its active function. Close TS-SS Stem Gate AUACHMENT2 20 of 34
DESCRIPTION OF MOTOR OPERATED VALVES EJHV88O9B is a 10 inch Westinghouse flex wedge gate valve equipped with an SBD-3 Limitorque actuator. The torque switch controls the close Enclosure 5 to stroke while a limit switch controls the open stroke.
This MOV has been set up to open and close ULNRC-06410 RHR TRN B AGO INJ SPLY Flex against 228 psid as required by its active safety EJHV88O9B ISO (3.0.3) Torque Rising Wedge Page 32 of 45 function. Close Switch Stem Gate EJHV881 1A is a 14 Westinghouse flex wedge gate valve equipped with a type SB-i operator. This Motor Operated Valve (MDV) is set up to open against 468 psid (ref. RFR OAR 200505692) and CTMT RECIRC SUMP A TO Flex close against 53 psid for its active safety functions. Open &
EJHV881 IA RHR PUMP A SUCT ISO Torque Rising Wedge Closure is controlled by torque switch. Close Switch Stem Gate EJHV8811B is a 14 Westinghouse flex wedge gate valve equipped with a type SB-i operator. This Motor Operated Valve (MDV) is set up to open against 468 psid (ref. RFR CAR 200505692) and CTMT RECIRC SUMP B TO Flex close against 53 psid for its active safety functions. Open &
EJHV881 1 B RHR PUMP B SUCT ISO Torque Rising Wedge Closure is controlled by torque switch Close Switch Stem Gate EJHV884O is a 10 inch Westinghouse flex wedge gate valve equipped with an SBD-3 actuator. The close stroke is controlled by the torque switch while the open stroke is controlled by a limit switch. This RHR TRAIN A & B SI SYS MDV has been setup to open and close against 228 Flex EJHV884O Open & Torque Rising Wedge HOT LEG RECIRC ISO (3.0.3) psid as required by its active safety functio
- n. Close Switch Stem Gate EMHV88OIA is a 4 inch Westinghouse flex wedge gate valve equipped with an SBD-00 Limitorque actuator. This motor operated valve (MDV) has been setup to open against 2713 psid as required Limit for its active safety function. EMHV88O1A has also Switch been set up to close against 2169 psid for without BORON INJ HDR TRAIN A Flex commercial purposes. The valve uses limit switch EMHV88O1A OUT TO COLD LEGS ISO Torque Rising Wedge control in both the open and close direction. Open Switch Stem Gate AUACHMENT2 21o134
DESCRIPTION OF MOTOR OPERATED VALVES EMHV8801B is a 4 inch Westinghouse flex wedge gate valve equipped with an SBD-00 Limitorque actuator, designed to open and close on limit. The Enclosure 5 to MOV has been set up to open against a safety Limit ULNRC-06410 related DP of 2713 psid and close against a Switch commercial DP of 2169 psid. This MOV uses limit BORON INJ HDR TRN B OUT switch control with a Target Seatin without Flex Page 33 of 45 g Thrust of 8000 Torque Rising Wedge EMHV88O1B TO COLD LEGS ISO lbs Open Switch Stem Gate EMHV88O2A is a 3 inch Westinghouse flex wedge gate valve equipped with a Limitorque SBD-00 actuator. The motor operated valve (MOV) has an active safety function to open and close against 250 psid. The commercial function is to open and close SI PMP A DISCH TO HOT against 1570 psid. Close control is by torque Flex EMHV88O2A Open & Torque Rising Wedge LEG INJ ISO (3.0.3) switch. Close Switch Stem Gate EMHV88O2B is a 3 inch Westinghouse flex wedge gate valve equipped with an SBD-00 Limitorque actuator, set up to open on limit and close on torque. The MOV has been set up to open and SI PMP B DISCH TO HOT close against 250 psid as required for its active Flex EMHV88O2B Open & Torque Rising Wedge LEG NJ ISO (3.0.3) safety functions. Close Switch Stem Gate EMHV88O3A is a 4 Westinghouse flex wedge gate valve equipped with an SBD-00 operator. Valve closure is controlled by limit. The close torque Limit switch is not in the circuit. This MOV is set up to Switch open and close against 2724 psid and 2180 psid BORON INJ HDR SPLY FROM respectively as required by its without Flex active safety Open & Torque Rising EMHV88O3A CCP A ISO functions. Wedge Close Switch Stem Gate EMHV88O3A is a 4 Westinghouse flex wedge gate valve equipped with an SBD-00 operator. Valve closure is controlled by limit. The close torque Limit switch is not in the circuit. This MOV is set up to Switch open and close against 2724 psid and 2180 psid BORON INJ HDR SPLY FROM respectively as required by its active without Flex safety Open & Torque Rising Wedge EMHV88O3B CCP B ISO functions. Close Switch Stem Gate ATTACHMENT 2 22 of 34
DESCRIPTION OF MOTOR OPERATED VALVES EMHV88O7A is a 6 Westinghouse flex wedge gate valve equipped with a Limitorque SMB-00 actuator.
Enclosure 5 to The Motor Operated Valve fMOV) is torque switch controlled. EMHV88O7A has been set up to open ULNRC-06410 against an extrapolated DP thrust of 3110 lbs. and a RHR HX A TO SI PMPS SUCT close an extrapolated thrust of 4665 lbs. Flex Page 34 of 45 as required Open & Torque Rising Wedge EMHV88O7A DNSTRM ISO VLV A for its commercial functions. Close Switch Stem Gate EMHV88O7B is a 6 Westinghouse flex wedge gate valve equipped with a Limitorque SMB-00 actuator.
The MOV is torque switch controlled. The MOV has RHR HX A TO SI PMPS SUCT been set up to open and close with a Flex DP thrust of Open & Torque Rising Wedge EMHV88O7B DNSTRM ISO VLV B 930 lbs. as required for its safety functions. Close Switch Stem Gate EMHV8814A is a 1.5 inch Velan globe valve equipped with an SMB-00 Limitorque actuator. This Motor Operated Valve (MOV) has been setup to SI PMP A RECIRC TO RWST open and close against 1,552 psid as required by its Torque EMHV8814A ISO active function. Close Switch RS Globe EMHV8814B is a 1.5 inch Velan globe valve eqciipped with SMB-00 Limitorque actuator. This MOV has been setup to close against 1552 psid as required by its active safety function. EMHV8814B SI PMP B RECIRC TO RWST has also been setup to open against 1552 psid as Torque EMHV8814B ISO required by its commercial function Close Switch RS Globe EMHV8821A is a 4 Westinghouse flex wedge gate valve with a type SB-00 Umitorque actuator. The Limit MOV is set up to close on limit against 1734 psid as Switch requited by its safety function. EMHV8B2JA is also without SI PMP A DISCH TO COLD Flex set up to open against 1552 psid for commercial Torque EMHV882JA LEG NJ ISO Rising Wedge purposes Close Switch Stem Gate EMHV8821B is a 4 Westinghouse flex wedge gate valve with a type SB-00 Limitorque actuator. The Limit MOV is set up to close on limit against 1734 psid as Switch requited by its safety function. EMHV8821B is also SI PMP B DISCH TO COLD without Flex set up to open against 1552 psid for commercial Torque EMHV882JB LEG IN] ISO Rising Wedge purposes. Close Switch Stem Gate AUACHMENT2 23of34
DESCRIPTION OF MOTOR OPERATED VALVES EMHV8835 is a 4 inch Westinghouse flex wedge gate valve equipped with a Limitorque SBD-00 Enclosure 5 to actuator. The motor operated valve (MOV) has an active safety function to open against 0 psid and ULNRC-06410 close against 249 psid. The commercial function is SI PMPS DISCH TO COLD Flex Page 35 of 45 to open and close against 1750 psid. Close control EMHVB835 LEG IN] ISO (3.0.3) Torque Rising Wedge is by torque switch Close Switch Stem Gate EMHV8923A is a Westinghouse 6 flex wedge gate valve with a Limitorque SMB-00 operator. This MOV has been setup to close against 215 psid as required by its active safety function. EMHV8923A does not have a safety function to open, but has been set up to open against 50 psid for commercial function. This MOV utilizes torque switch control in RWST TO SI PMP A SUCT Flex the closing direction and limit switch control in the EMHV8923A ISO HV (3.0.3) Torque Rising Wedge opening direction Close Switch Stem Gate EMHV8923B is a 6 Westinghouse flex wedge gate valve equipped with a Limitorque SMB-00 actuator.
The Motor Operated Valve (MOV) is torque switch controlled. The MDV has been set up to close against a DP of 215 psid as required for its safety RWST TO SI PMP B SUCT function. EMHV8923B is also set up to open Flex EMHV8923B ISO HV Torque Rising Wedge against a DP of 50 psid for commercial purposes. Close Switch Stem Gate ENHV0001 is a 12 Anchor-Darling flex wedge gate valve equipped with a type SMB-00 actuator. The Motor Operated Valve (MDV) has been setup to open against 54 psid and close against 10 psid as required for its active safety functions. The MDV is torque switch controlled during the closing stroke and limit switch controlled during the opening stroke CTMT RECIRC SMP TO Flex with the open torque switch bypassed for 80-85% of Open &
ENHV0001 CTMT SPRY PMP A HV Torque Rising Wedge the stroke Close Switch Stem Gate AUACHMENT2 240134
DESCRIPTION OF MOTOR OPERATED VALVES ENHV0006 is a 10 Anchor-Darling flex wedge gate Enclosure 5 to valve equipped with a type SMB-00 actuator. This motor operated valve (MDV) is set up to open CTMT SPRY PMP A DISCH Flex ULNRC-06410 against 244 psid for its active safety function. Torque HV Rising Wedge ENHV0006 has no safety function to close. Open Switch Stem Gate Page 36 of 45 ENHV0007 is a 12 inch Anchor Darling flex wedge gate valve equipped with a Limitorque SMB-0O actuator. The motor operated valve (MDV) is set up to open against 54 psid and close against 10 psid for its active safety functions. Closure is controlled by torque switch. The MDV is set up using EPRI Predictive Performance Methodology (PPM) per CTMT RECIRC SMP TO Flex CALC MPR-1861 with compensation for pressure Open & Torque ENHV0007 CTMT SPRY PMP B HV Rising Wedge locking effects Close Switch Stem Gate ENHVOO12 is a 10 inch Anchor-Darling flex wedge gate valve equipped with an SMB-00 Limitorque actuator. Closure is controlled by torque switch.
This MDV has been setup to open against 244 psid CTMT SPRY PMP B DISCH Flex as required by its active safety function. The valve Torque ENHVOO12 HV Rising Wedge has no safety function to close. Open Switch Stem Gate EPHV88O8A is a 10 Westinghouse flex wedge gate valve equipped with an SBD-3 operator. Valve closure is controlled by torque. This valve has no Flex safety function to open and must close against 0 Torque EPHV88O8A SI ACC TK A OUT ISO Rising Wedge DP. Close Switch Stem Gate EPHV88O8B is a 10 Westinghouse flex wedge gate valve equipped with an SBD-3 operator. Valve closure is controlled by torque. This valve has no Flex safety function to open and must close against 0 Torque EPHV88O8B SI ACC TK B OUT ISO Rising Wedge DP. None Switch Stem Gate EPHV88O8C is a 10 Westinghouse flex wedge gate valve equipped with an SBD-3 operator. Valve closure is controlled by torque. This valve has no Flex safety function to open and must close against 0 Torque EPHVBBO8C SI ACC TK C OUT ISO OPER Rising Wedge DP. None Switch Stem Gate ATTACHMENT 2 25 of 34
DESCRIPTION OF MOTOR OPERATED VALVES EPHV88O8D is a 10 Westinghouse flex wedge gate valve equipped with an SBD-3 operator. Valve closure is controlled by torque. This valve has no Enclosure 5 to safety function to open, but does have a safety function to close against 0 psid. EPHV88O8D is set ULNRC-06410 Flex up to open and close against 726 psid for EPHV88O8D SI ACC TK D OUT ISO Torque Rising Wedge Page 37 of 45 commercial purposes Close Switch Stem Gate FCHVO312 is a 4 inch Gimpel globe valve equipped with an SMB-000 Limitorque actuator. The actuator functions only to open the valve. The valve is closed rapidly by a spring mechanism when a trip lever is released by a solenoid. The actuator does not assist in the closing of the valve, but motors a short distance in the close direction following a spring-actuated close stroke. The open stroke of this MOV is also unique. The actuator first motors in the close direction frecompressing the spring mechanism and latching the trip lever), with the motor stopped by the torque switch. The actuator then opens the valve in a standard manner, running in the open direction, opening the valve, with the motor stopped by a limit switch. The MOV has AFP TURB MECH been set up to open against 1220 psid as required FCHVO312 TRIP/THROT HV Torque Rising for its active safety function. Open Switch Stem Globe GSHVOO2O is a 6 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and an HBC-0 Limitorque gearbox. This motor operated Limit valve (MOV) has been setup to open and close Switch against 3 and 48 psid, respectively, as required by without its active safety functions. Limit switch control is Open & Torque GSHVOO2O H2 PURGE IN CTMT ISO HV Quartet used for both open and close stroke control Close Switch Turn Butterfly AUACHMENT2 26of34
DESCRIPTION OF MOTOR OPERATED VALVES GSHVOD21 is a 6 inch Fisher butterfly valve equipped with an SMB-000 Limitorque actuator and Enclosure 5 to an HBC-0 Limitorque gearbox. This motor operated Limit valve (MOV) has been setup to open and close ULNRC-06410 Switch against 3 and 48 psid, respectively, as required by without H2 PURGE OUTER CTMT ISO its active safety functions. Limit switch control Page 38 of 45 is Open & Torque Quarter GSHVOO21 HV used for both open and close stroke control Close Switch Turn Butterfly KAHVOO3O is a 1.5 BorgWarner solid wedge gate valve equipped with a type SMB-000 operator. The MOV has no active safety function to open or close.
It is setup to open and close against a DP of 149 Solid psid as desired to meet its commercial function. Torque KAHVO030 H2 CTRL SYS M/U AIR HV Rising Wedge Closure is controlled by torque switch None Switch Stem Gate KCHVO253 is a 4-inch Velan Parallel Disk Gate valve equipped with a limit controlled SMB 000 Limit Limitorque actuator. This MOV is set up to open Switch with F-PROT LOOP TO RX BLD and close against 789 psid as required by its active Open & Torque Rising Parallel KCHVO253 OUTER CTMT DNSTRM ISO safety functions. Close Switch Stem Disk Gate LFFVOO95 is a 6 Anchor Darling flex wedge gate valve with a type SMB-00 actuator. The close stroke is torque switch controlled. The motor operated valve (MOV) has been set up to close against 58 psid as required for its active safety function. The MOV has no safety function to open, CTMT NORM SMP PMPS Flex but has been set up to open against 10 psid for Torque LFFVOO95 DISCH HDR CTMT FV Rising Wedge commercial purposes. Close Switch Stem Gate LFHVO1O5 is a 6 Anchor Darling flex wedge gate valve with a type SMB-000 actuator. The close stroke is torque switch controlled. The MDV has been set up to close against 18 psid as required for its active safety function. The MDV has no safety DRW SMPS DISCH HDR Flex function to open, but has been set up to open Torque LFHVO1O5 DNSTRM HV Rising Wedge against 18 psid for commercial purposes. Close Switch Stem Gate AUACHMENT2 27of34
DESCRIPTION OF MOTOR OPERATED VALVES LFHVO1O6 is a 6 Anchor Darling flex wedge gate valve with a type SMB-000 actuator. The close stroke is torque switch controlled. This motor Enclosure 5 to operated valve (MOV) has been set up to close against 18 psid as required for its active safety ULNRC-06410 function. The MOV has no safety function to open, DRW SMPS DISCH HDR but has been set up to open against 18 psid for Flex Page 39 of 45 LFHVO1O6 UPSTRM HV Torque Rising Wedge commercial purposes. Close Switch Stem Gate ATFACHMENT2 28of34
RISING STEM-TORQUE SWITCH CONTROLLED MOTO R OPERATED VALVES Close Close Close Enclosure 5 to Test Safety Close Operable Valve ID Margin Close RV Thrust Valve Description Cycle Test Date ULNRC-06410 Functions Control Load Limit (%) Limit ALHV0005 MDAFP 810 S/G D HV Limit 20 11/17/2014 CC IS 0.35 ALHV0009 MDAFP TO S/G B HV 182 0.17 0.8 Page 40 of 45 20 10/23/2014 CC IS 0.73 ALHVOO11 MDAFPTOS/GCHV 36 0.53 0.71 20 10/26/2014 00 IS 0.71 BBHV8351A RCP A SEAL WTR SPLY ISO HV 41 0.49 0.86 20 11/05/2014 None IS 0.77 BBHV8351D RCP D SEAL WIR SPLY ISO HV 29 0.87 0.63 20 11/01/2014 None TS 0.55 CVCS CCP A DISCH TO RCP SEALS 83 0.99 0.88 BGHV8357A THROTTLE VLV 20 02/15/2014 CC TS BGLCVOI12C 0.47 113 0.47 0.37 CVCSVCTOUTDNSTRM ISO 20 11/01/2014 C TS 0.66 51 0.59 EFPDVOO2O ESW S-C STR B DRN DP CTRLVLV 0.57 20 11/05/2014 00 TS 0.48 EGHVOO1I ESWTOCCWTRNAUPSTRM HV 109 0.49 0.39 20 10/29/2014 0 TS 0.06 EGHVOO12 ESW TO CCW IRN B UPSIRM HV 1563 0.78 0.5 20 09/25/2013 0 TS 0.48 EGHVOO14 [SW TO CCW TRN B DNSTRM HV 133 0.56 0.48 20 09/25/2014 o IS 0.06 EGHVOO71 CCWTOCTMTOUTERISOVLV 137 0.8 0.57 20 10/31/2014 None IS 0.75 37 0.91 0.59 EGHVO 126 CCW TO CTMT BYP VLV 20 10/27/2014 None IS 0.75 33 0.79 0.52 CCW FROM RCS CTMT EGHVOO6O BYP EGHVO13O ISO HV 20 10/29/2014 00 IS 0.84 0.74 0.61 EGHVO131 CCW FROM CTMT EGHVOO59 BYP ISO 20 10/30/2014 00 TS ENHV0006 0.74 35 0.87 0.69 CTMT SPRY PMP A DISCH HV 20 11/26/2013 0 TS 0.92 9 0.68 CTMTRECIRCSMPTOCTMTSPRY 0.7 ENHV0007 PMP B HV 20 11/02/2014 00 TS EPHV88O8A-A( 0.41 142 0.63 0.5 SIACCTKAOUTISO 20 11/02/2014 None IS 0.06 1600 0.52 FCHVO3J2 AFPTURB MECHTRIP/THROTHV 0.47 20 11/07/2014 0 TS 0.74 CTMTNORMSMPPMPSDISCHHDR NA NA 0.33 LFFVOO95 CTMT FV 20 11/02/2014 C TS 0.33 200 0.76 0.42 ATTACHMENT 2 29 of 34
RISING STEM-TORQUE SWITCH CONTROLLED MOTOR OPER ATED VALVES Close Enclosure 5 to Torque Lubrication Unseating Current Valve ID Limit COF Limit RV Limit Limit Remarks ULNRC-06410 ALHV0005 0.44 0.0331 0.22 0.02 NA ALHV0009 0.5$ 0.0738 0.49 Page 41 of 45 0.21 NA ALHVOOJ1 0.5 0.0470 0.31 0.04 NA 33HV8351A 0.74 0.0666 0.44 0.19 0.82 BBHV8351D 0.82 0.0467 0.31 0.12 0.89 BGHV8357A 0.31 0.1000 0.67 0.63 0.85 BGLCVO112C 0.26 0.0451 0.30 0.29 0.86 EFPDVOO2O 0.45 0.0890 0.55 0.31 0.8$
EGHVOO1I 0.6$ NA NA 0.52 0.97 EGHVOO12 0.56 NA NA 0.57 0.92 EGHVOO14 0.73 NA NA 0.38 0.83 EGHVOO71 0.57 0.0035 0.02 0.77 0.94 Current Limit Acceptable to EGHVO126 0.5 0.0914 0.61 0.79 1.00 200%
EGHVO13O 0.71 0.0752 0.50 0.35 0.7 EGHVO131 0.74 0.1003 0.67 0.18 0.79 ENHV0006 1.16 0.1011 0.67 0.34 0.9 Current Limit Acceptable to ENHV0007 0.51 0.0399 0.27 0.29 1.04 200%
EPHV88O8A-AI 0.34 0.0943 0.63 0.41 0.46 FCHVO312 0.86 NA 0.00 0.23 NA LFFVOO95 0.21 0.0780 0.52 0.38 0.86 AUACHMENT2 30o134
RISING STEM-LIMIT SWITCH CONTROLLED MOTOR OPER ATED VALVES Close Close Valve Test Close RV Thrust Torque Valve ID Valve Description Thrust Enclosure 5 to Cycle Test Date Limit Limit Limit CCP B SUCT FROM RWST ISO COF Limit BGLCVO1J2E VLV 20 ULNRC-06410 09/25/2013 0.83 0.25 0.38 EJHV88O4B RHR IRN B SI PUMPS SPLY ISO 0.31 20 11/01/2014 0.88 0.50 0.43 BORON INJ HDR TRAIN A OUT TO 0.71 Page 42 of 45 EMHV88O1A COLD LEGS ISO 20 11/06/2014 0.55 0.58 0.38 0.0700 0.68 ATTACHMENT 2 31 of 34
RISING STEM-LIMIT SWITCH CONTROLLED MOTOR OPERATED VALVES Lubrication Unseating Current Enclosure 5 to Valve ID Limit RV Limit Limit Remarks ULNRC-06410 BGLCVO112E 1.03 0.39 0.69 EJHV88O4B 0.66 0.33 0.81 Page 43 of 45 EMHV88O1A 0.47 0.10 0.68 AUACHMENT2 32 of 34
QUARTER TURN-LIMIT SWITCH CONTROLLED MOTOR OPERATED VALVES Open Open Open Enclosure 5 to Stroke Open Stroke Stroke Stroke Test Operable Unseating Disk/Pin Valve ULNRC-06410 Valve ID Valve Description Cycle Test Date Load Limit RV Limit Limit Stem Limit Page 44 of 45 ALHVOO31 ESW TO MD AFP A HV 20 09/09/2014 0.58 0.21 0.42 043 ALHVOO33 ESW TO TD AFP HV 20 11/19/2014 0.3$ 0.75 0.74 0.90 EFHVOO23 SERV WTR TO ESW TRN A UPSTRM HV 20 06/11/2014 0.13 0.15 0.01 0.16 EFHVOO37 ESW IRN A TO UHS HV 20 11/13/2014 0.70 0.79 0.19 0.82 EFHVOO41 ESW IRN A TO SERV WTR DNSTRM HV 20 06/11/2014 0.14 0.34 0.24 0.36 EFHVOO42 ESW TRN B TO SERV WTR DNSTRM HV 20 05/19/2014 0.60 0.51 0.15 0.54 EFHVOO49 ESW TRN A FROM CTMT AIR CLRS OUTER CTMT HV 20 10/28/2014 0.08 0.45 0.24 0.28 EFHVOO59 ESW TRN A FROM CCW HX A HV 20 05/04/2013 0.55 0.31 0.19 0.36 EGHVOO15 CCW TRN A SPLY/RTN ISO HV 20 01/27/2015 0.28 0.18 0.02 0.25 ATTACHMENT 2 33 of 34
QUARTER TURN-LIMIT SWITCH CONTROLLED MOTOR OPERATED VALVES Open Close Close Close Close Enclosure 5 to Stroke Design Close Stroke Stroke Stroke Stroke Design Current Margin Stroke RV Actuator Disk/Pin Valve Current Margin ULNRC-06410 Valve ID Limit Open (3/4) Limit Limit Limit Stem Limit Limit Close (3/4) Remarks ALHVOO31 Page 45 of 45 1.00 131.00 0.24 0.17 0.95 0.78 1.01 349 Current Limit Acceptable to 200%
ALHVOO33 0.81 115.00 0.47 0.27 0.56 0.60 0.22 205 EFHVOO23 0.79 287.00 0.34 0.50 0.22 0.47 0.82 145 EFHVOO37 0.87 22.00 0.82 0.87 0.19 0.82 0.88 17 EFHVOO41 0.79 399.00 0.11 0.28 0.16 0.27 0.79 434 EFHVOO42 0.80 47.00 0.69 0.71 0.21 0.67 0.83 69 EFHVOO49 0.75 407.00 0.53 0.26 0.16 0.32 0.73 139 EFHVOO59 0.97 47.00 0.18 0.15 0.04 0.22 0.97 183 EGHVOO15 0.88 254.00 0.60 0.64 0.60 0.85 0.88 282 AUACHMENT2 34of34