~ PRIORI"I Y Z ~

REGULATORY'$HQFISA fB&M86TION SYSTEM (RIDS)

ACCESSION NBR:9503020256 DOC.DATE: ~~~

FACIL:50-400 Shearon Harris Nuclear Power Plant, Unit 1, Carolina NOTARIZED: NO DOCKET 05000400 AUTH. NAME AUTHOR AFFILIATION ROBINSOR,W.R. Carolina Power & Light Co.

RECIP.NAME RECIPIENT AFFILIATION

SUBJECT:

"Annual Operating Rept," consisting of info re number o". F individuals receiving exposures greater than 100 mrem/yr, primary coolant iodine spikes & challenges to PORVs & F safe" y valves for 1994.Wi~50~22 ltr.

I DISTRIBUTION CODE: IE56D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: 20.407 Annual Personnel Monitoring Rpt/Annual Rad Exposure Rpt by Fun NOTES:Application for permit renewal filed. 05000400 F

RECIPIENT COPIES RECIPIENT COPIES 1D CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD2-1 PD 0 LE,N 1 1 INTERNAL: ACNW 6 6 FILE NTER 02 1 1 NMSS/SCDB/SSSS 1 1 RR7DRSS PRPB 2 2 RES/RPHEB 1 1 RGN2 01 1 1 EXTERNAL: LITCO BRYCEiJ H 1 1 NOAC 1 1 NRC PDR 1 1 iOTE TOALL "RIDS" RECIPIENTS:

DIS'I'Rl!If "I'IOi I.ISTS I'OR DOC!.'ilEi'I'S YOL'Oi i

PLEASE I IELP I.'S TO RLDI;CE '6:KSTE! CONTACT TI IE DOCL'i!Ei'TCOi'TROL iI "I'EED!

if DESK, ROOi I P I .37 ( EX I: 504.2IN3 ) TO F L I I ATE YOI.'R YA E F ROTI TOTAL NUMBER OF COPIES REQUIRED: LTTR 17 ENCL 16

I-Carolina Power & Light Company William R. Robinson PO Box 165 Vice President New Hill NC 27562 Harris Nuclear Plant FEB 2 ~ 1995 File: HO-950132 Serial: HNP-95-018 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT DOCKET NO. 50-400/LICENSE NO. NPF-63 ANNUALOPERATING REPORT - 1994 Gentlemen:

In accordance with Technical Specification 6.9.1.2 for the Shearon Harris Nuclear Power Plant, Carolina Power & Light Company herewith submits the annual report of (a) individuals receiving exposures greater than 100 mrem/yr and their associated man-rem exposure according to work and job functions, (b) primary coolant iodine spikes, and (c) challenges to the pressurizer power-operated relief valves (PORVs) and safety valves for 1994.

Questions regarding this submittal may be referred to Mr. D. C. McCarthy at (919) 362-2100.

Sincerely, W. R. Robinson MGW:mgw Attachments c: Mr S. D. Ebneter (NRC-RII)

Mr S. A. Elrod (NRC-SHNPP)

Mr N. B. Le (NRR)

Ms C. T. Raddatz (NRC-REIRS Project Manager) 9503020256 941231 PDR ADOCK 05000400 R PDR State Road 1134 New Hill NC Tel 919362-2502 Fax 919362-6950

Attachment to HNP-95-018 Page 1 of 3 RIMS ZI NUMBER OF PERSONNEL AND MAN-REM BY WORK'ND JOB FUNCTION, 1994 HARRIS PLANT NUMBER OF PERSONNEL > 100 MREM I TOTAL MAN-REM WORK AND JOB FUNCTION STAT UTIL CNTR I STAT UTIL CNTR REACTOR OPERATIONS AND SURVEILLANCE MAINTENANCE PERSONHEL 3 1 1.267 0.015 1.220 OPERATING PERSONNEL 18 0 5.468 0.000 0.669 HEALTH PHYSICS PERSONNEL 23 15 5.825 0.000 5.395 SUPERVISORY PERSONNEL 0 0 0.326 0.071 6.019 ENGINEERING PERSONNEL 1 0 1.239 0. 323 0.392 ROUTINE MAINTENANCE MAINTENANCE P ERSONHEL 23 1 94 8.078 0.885 30.834 OPERATING PERSONNEL 1 0 0 0. 207 0.000 0. 126 HEALTH PHYSICS PERSONNEL 7 0 21 3 .252 0.006 5.291 SUPERVISORY PERSONNEL 2 0 0 0.415 0.012 6. 124 ENGINEERING PERSONNEL 3 0 54, 1. 171 0. 100 27. 173 INSERVICE INSPECTION MAIttTENANCE P ERSONNEL 0 1 5 8.234 0.213 1.559 OPERATING PERSONNEL 0 0 0 0. 159 0.060 0.019 HEALTH PHYSICS PERSONNEL 0 0 0 8.206 0.600 8.314 SUPERVISORY PERSONNEL 8 8 0 8.001 0.000 0.000 ENGINEERING PERSONNEL 0 0 19 0.414 0.082 6.220 SPECIAL MAINTENANCE MAINTENANCE PERSONNEL 21 6 33 6.578 0.042 8.707 OPERATING PERSONNEL 1 0 0 0.294 0.080 0.024 HEALTH PHYSICS PERSONNEL 18 0 15 2.571 0.000 4.294 SUPERVISORY PERSONNEL 8 0 0 0.080 0.800 0.016 ENGINEERING PERSONNEL 1 8 12 0.390 0.014 2,844 WASTE PROCESSING MAINTENANCE PERSONNEL 0 6 0.001 0.000 0.277 OPERATING PERSONNEL 0 0 0.007 0.000 0.000 HEALTH PHYSICS PERSONNEL 2 0 0.601 0.000 0.015 SUPERVISORY PERSONNEL 0 0 0.000 0.060 0.000 ENGINEERING PERSONNEL 0 8 0.000 0.000 0.031 REFUELING MAINTEHANCE PERSONNEL 29 5 145 8.765 1.431 48.592 OPERATING PERSONNEL 3 0 0 1.391 0.000 8.011 HEALTH PHYSICS PERSONNEL 4 0 12 1.458 0.800 3 .758 SUP ERVZSORY PERSONNEL 1 0 0 0. 152 0.040 8. 129 ENGIHEERING PERSONNEL 2 1 49 . 0.838 0.450 18.018 TOTAL MAINTENANCE PERSONNEl 76 7 278 . 24.915 2.586 91. 189 OPERATING PERSONNEL 23 0 0 7.526 0.000 0.849 HEALTH PHYSICS PERSONNEL 46 0 63 13.913 0.668 19.867 SUPERVISORY PERSONNEL 3 0 0 0.974 0. 123 0.288 ENGINEERING PERSONNEL 7 1 134 4.052 0.889 54.678 GRAND TOTAL 155 8 475 51.388 3.598 166.071 Notes: (1) Dose based on pocket dosimeters and electronic dosimeters (2) Stat = Harris Plant Staff Util = CP&L non-Harris personnel Cntr = Contractor (3) Special Maintenance includes special work on spent fuel cask, seal table room equipment and certain valves and pumps

1 Attachment to HNP-95-018 Page 2 of 3 1994 ANNUALREPORT - PRIMARY COOLANT IODINE SPIKES During 1994, the primary coolant did not exceed 1.0 pCi/gram dose equivalent I-131 or 100/E-bar pCi/gram gross radioactivity as set forth in Technical Specification 3.4.8.

Attachment to HNP-95-018 Page 3 of 3 1994 ANNUALREPORT - PRESSURIZER RELIEF AND SAFETY VALVECHALLENGES During 1994, there were no challenges to the pressurizer power operated relief valves (PORVs) or safety valves.