MONTHYEARGO2-14-049, Relief Request for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program2014-04-0202 April 2014 Relief Request for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program Project stage: Request ML14140A6592014-05-20020 May 2014 NRR E-mail Capture - Acceptance Review (TAC Nos. MF3847-49, MF3851-58) Project stage: Acceptance Review ML14183B7042014-07-0202 July 2014 NRR E-mail Capture - Requests for Additional Information - Relief Requests Associated with the Fourth Ten-Year Interval Inservice Testing Program - Columbia Generating Station Project stage: RAI GO2-14-104, Response to Request for Additional Information Related to Relief Requests for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program2014-07-21021 July 2014 Response to Request for Additional Information Related to Relief Requests for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program Project stage: Response to RAI GO2-14-152, Erratum for Relief Requests for the Fourth Ten-Year Interval Inservice Testing Program2014-10-23023 October 2014 Erratum for Relief Requests for the Fourth Ten-Year Interval Inservice Testing Program Project stage: Request ML14337A4492014-12-0909 December 2014 Relief Request Nos. RV-03, RV-02, RV-01, RP-06, RP-05, RP-04, RP-03, PV-04, RP-02, RP-01, RG-01, for the Fourth 10-Year Inservice Testing Interval (TAC MF3847-MF3849, MF3851-MF3858) Project stage: Other ML15030A2322015-02-0909 February 2015 Correction to 10 CFR 50.55a Citation and Administrative Changes - Relief Request Nos. RV-03, RV-02, RV-01, RP-06, RP-05, RP-04, RP-03, PV-04, RP-02, RP-01, RG-01, for the 4th 10-Year Inservice Testing Interval Project stage: Other 2014-05-20
[Table View] |
|
---|
Category:E-Mail
MONTHYEARML24008A0022024-01-0505 January 2024 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of License Amendment Request for Application to Revise TS to Adopt TSTF-584, Eliminate Automatic RWCU System Isolation on SLC Initiation - EPID L-2023-LLA-0170 ML23278A0042023-10-0404 October 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise Technical Specifications to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling - EPID L-2023-LLA-0128 ML23275A0092023-09-29029 September 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise Tech Specs to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling - EPID: L-2023-LLA-0128 ML23150A2502023-05-26026 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - License Amendment Request to Clean-Up Operating License and Appendix a, Technical Specifications - EPID L-2023-LLA-0062 ML23124A2412023-05-0404 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise TS to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position - EPID L-2023-LLA-0063 ML23124A0062023-05-0303 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - Application to Revise Tech Specs to Adopt TSTF-541, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling - EPID L-2023-LLA-0063 ML23065A0422023-02-23023 February 2023 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2022 Biological Monitoring Report ML22343A1802022-12-0808 December 2022 February 2023 Emergency Preparedness Program Inspection - Request for Information ML22349A2002022-12-0101 December 2022 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2022 Priority Pollutant Discharge Monitoring Report ML22312A0042022-11-0707 November 2022 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of Fourth 10 Year ISI RR 4ISI-11 - EPID L-2022-LLR-0071 ML22301A1432022-10-28028 October 2022 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Adopt TSTF-505 - EPID L-2022-LLA-0023 ML22256A2002022-09-13013 September 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22241A0182022-08-26026 August 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22235A1052022-08-22022 August 2022 August 2022 Emergency Preparedness Exercise Inspection Request for Information ML22210A0072022-07-28028 July 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22173A0682022-06-17017 June 2022 Email Concurrence on SE Input for Columbia Pltr LAR ML22166A4122022-06-15015 June 2022 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - Application to Revise TS to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling - EPID L-2022-LLA-0081 ML22144A0342022-05-18018 May 2022 NRR E-mail Capture - Draft - Request for Additional Information - Columbia Generating Station - LAR to Change TS 3.4.11 - Reactor Coolant System Pressure and Temperature Limits - EPID L-2021-LLA-0191 ML22075A3392022-03-15015 March 2022 NRR E-mail Capture - Columbia Generating Station - Audit Questions - Regulatory Audit of License Amendment Request to Adopt 50.69 - Categorization Process - EPID L-2021-LLA-0207 ML22067A0132022-03-0707 March 2022 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of License Amendment Request to Adopt TSTF-505, Revision 2, Provide RISK-INFORMED Extended Completion Times - RITSTF Initiative 4b - EPID L-2022-LLA-0023 A002515, NRR E-mail Capture - (External Sender) Energy Northwest Columbia Generating Station 2021 Priority Pollutant Discharge Monitoring Report2022-01-12012 January 2022 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2021 Priority Pollutant Discharge Monitoring Report ML21348A1852021-12-14014 December 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia - License Amendment Request to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors - EPID L-2021-LLA-0207 ML21335A0182021-11-30030 November 2021 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of Requested Licensing Action - License Amendment Request to Change TS 3.4.11 Reactor Coolant System Pressure and Temperature Limits - EPID L-2021-LLA-0191 ML21216A0502021-08-0303 August 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia - License Amendment Request to Adopt TSTF-439, Eliminate Second Completion Times Limiting Time from Discovery of Failure to Meet an LCO EPID L-2021-LLA-0259 ML21209A9792021-07-28028 July 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Remove License Condition 2.C.(34) and Revise License Condition 2.C.(35) - EPID L-2021-LLA-0074 ML21162A3062021-06-11011 June 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia Generating Station - License Amendment Request to Adopt TSTF-546, Revise APRM Channel Adjustment Surveillance Requirement - EPID L-2021-LLA-0084 ML21137A0012021-05-14014 May 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia Generating Station - License Amendment Request to Remove License Condition 2.C.(34) and Revise License Condition 2.C.(35) - EPID L-2021-LLA-0074 ML21120A1182021-04-30030 April 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - On-Site Cooling System Sediment Disposal Approval Request - EPID L-2020-LLL-0031 ML21109A2762021-04-0808 April 2021 Email Request for Information for Columbia Generating Station'S PIR Inspection_Redacted ML21068A2842021-03-0404 March 2021 2021002 Inservice Inspection (ISI) Request for Information (RFI) ML21036A2932021-02-0404 February 2021 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2020 Biological Monitoring Report ML20357B1502020-12-22022 December 2020 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia - License Amendment Request - Adoption of TSTF-439, Eliminate Second Completion Times Limiting Time from Discovery of Failure to Meet an LCO, Rev. 2 - EPID L-2020-LLA-0259 ML20336A1852020-11-30030 November 2020 NRR E-mail Capture - Final - RAI - Columbia - One -Time Exemption from 10 CFR 73, App B, Sect VI, Subsection C.3.(l)(1) Regarding Annual Force-On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20325A0402020-11-19019 November 2020 NRR E-mail Capture - Draft - RAI - Columbia - One -Time Exemption from 10 CFR 73, Appendix B, Section VI, Subsection C.3.(I)(1) Regarding Annual Force -On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20314A0452020-11-0606 November 2020 NMFS to Energy Northwest, Entrainment Study Results for Columbia Generating Station ML20297A3032020-10-22022 October 2020 NRR E-mail Capture - LIC-109 Acceptance Review of License Amendment Request for Columbia - Application to Revise Tech Specs to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements - EPID L-2020-LLA-0212 ML20267A5162020-09-23023 September 2020 NRR E-mail Capture - Columbia Generating Station - Final - Request for Additional Information - Fourth Ten-Year Interval Inservice Inspection (ISI) Program Relief Request 4ISI-09 - EPID L-2020-LLR-0068 ML20265A3242020-09-20020 September 2020 Email 9-20-2020 - Req_ Kick-Off Call Columbia Generating Station RFI Provided for Roll-Back EP Program Inspection (Week of Nov 2 2020) ML20245E2822020-08-31031 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20239A9702020-08-26026 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20149K4362020-05-26026 May 2020 NRR E-mail Capture - Formal RAIs for Columbia (COVID-19) QA Plan Change Surveillance, Request Response by Tuesday June 2, 2020 ML20136A0112020-05-14014 May 2020 NRR E-mail Capture - Acceptance Columbia Relief Request ISI Reactor Pressure Vessel Feedwater Nozzles, 4ISI-09 ML20112F4572020-04-21021 April 2020 NRR E-mail Capture - Official Release of NRC RAIs for Columbia Covid Exigent Due Friday April 24, 2020 ML20090F5532020-03-30030 March 2020 NRR E-mail Capture - Accepted: Columbia Relief Request, EPID: L-2020-LLR-0035 ML20063G1522020-03-0202 March 2020 NRR E-mail Capture - Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-564 Amendment ML20056E3592020-02-25025 February 2020 NRR E-mail Capture - Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-566 Amendment ML20034E6082020-02-0303 February 2020 NRR E-mail Capture - RAI Formal Release Columbia TSTF 563 LAR, 30 Day Response Period Due March 3, 2020 ML20013G7642020-01-10010 January 2020 Revised Questions to Support the Columbia SPRA Audit ML19305C9342019-11-0101 November 2019 50.54(f) SPRA Submittal - Completeness Review Done and Path Forward ML19291A0322019-10-17017 October 2019 NRR E-mail Capture - Subject: Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-529 Amendment 2024-01-05
[Table view] |
Text
NRR-PMDAPEm Resource From: George, Andrea Sent: Wednesday, July 02, 2014 1:49 PM To: llwilliams@energy-northwest.com
Subject:
Requests for Additional Information - Relief Requests Associated with the Fourth Ten-Year Interval Inservice Testing Program - Columbia Generating Station (TAC NOS. MF3851, MF3854, MF3856, MF3857)
Attachments: MF3856 MF3857 MF3854 MF3851 - Columbia RAIs RP-01 RP-02 RP-03 RP-06.docx Ms. Williams, By letter dated April 2, 2014 (Agencywide Document Access and Management System (ADAMS) Accession Number ML14101A365), Energy Northwest (the licensee) submitted a series of relief requests for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program. The U.S. Nuclear Regulatory Commission (NRC) staff has reviewed the submittal and requests additional information (RAI) as detailed in the attachment.
Draft RAIs were issued on July 2, 2014. The NRC project mananger was notified that a clarification call is not needed and it was agreed that Energy Northwest will respond to these RAIs within 30 days, which is August 1, 2014.
If circumstances result in the need to revise the agreed-upon response date, please contact me at (301) 415-1081 or via email at andrea.george@nrc.gov.
Thank you, Andrea George Project Manager Nuclear Regulatory Commission Division of Operating Reactor Licensing andrea.george@nrc.gov 301-415-1081 1
Hearing Identifier: NRR_PMDA Email Number: 1410 Mail Envelope Properties (Andrea.George@nrc.gov20140702134900)
Subject:
Requests for Additional Information - Relief Requests Associated with the Fourth Ten-Year Interval Inservice Testing Program - Columbia Generating Station (TAC NOS. MF3851, MF3854, MF3856, MF3857)
Sent Date: 7/2/2014 1:49:26 PM Received Date: 7/2/2014 1:49:00 PM From: George, Andrea Created By: Andrea.George@nrc.gov Recipients:
"llwilliams@energy-northwest.com" <llwilliams@energy-northwest.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 1117 7/2/2014 1:49:00 PM MF3856 MF3857 MF3854 MF3851 - Columbia RAIs RP-01 RP-02 RP-03 RP-06.docx 23300 Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:
Recipients Received:
REQUESTS FOR ADDITIONAL INFORMATION (RAI)
ENERGY NORTHWEST COLUMBIA GENERATING STATION RELIEF REQUESTS RP-01, RP-02, RP-03 REQUEST FOR ALTERNATIVE RP-06 DOCKET NUMBER 50-387 By application dated April 2, 2014, to the U.S. Nuclear Regulatory Commission (NRC)
(Agencywide Document Access and Management System (ADAMS) Accession Number ML14101A365), Energy Northwest, the licensee, submitted a series of relief requests for the Columbia Generating Station Fourth Ten-Year Interval Inservice Testing Program.
Based on its review, the NRC staff requests the following additional information in order to complete their technical review.
EPNB-RAI-RP-01-1 Please provide the discharge pressures for standby service water pumps SW-P-1A and SW-P-1B, and standby service water, HPCS pump HPCS-P-2 from the inservice tests for the past year.
EPNB-RAI-RP-02-1 It appears that this alternative request is requesting the use of parts of Code Case OMN-16 for the standby service water pumps and the standby service water, HPCS pump. Please confirm if this is correct. If this is correct, please explain how your proposed testing differs from Code Case OMN-16 and provide justification for the differences.
EPNB-RAI-RP-03-1 Relief request RP-03 lists several elements that are used to develop and implement the provided reference pump curves. Relief request RP-03 states that these elements follow the guidance of Code Case OMN-16. Please clarify what portions of ASME OM Code Case OMN-16 are being followed. Also, please explain any deviations from ASME OM Code Case OMN-16 that are being requested in relief request RR-03.
EPNB-RAI-RP-06-1 Alternative request RP-06 provides a table that compares the test flow rate to the design basis accident flow rate. Please provide a table that compares test differential pressure and design basis differential pressure for the pumps for which an alternative is requested.