UNITED STATES ary 16, 2014
SUBJECT:
EDWIN I. HATCH NUCLEAR PLANT - NRC TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000321/2013009 AND 05000366/2013009 AND EXERCISE OF ENFORCEMENT DISCRETION
Dear Mr. Vineyard:
On December 6, 2013, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your Edwin I. Hatch Nuclear Plant, Units 1 and 2, and discussed the results of this inspection with you and other members of your staff. Inspectors documented the results of this inspection in the enclosed inspection report.
The inspection examined activities conducted under your license as they related to safety and compliance with the Commissions rules and regulations and with the conditions of your license.
The team reviewed selected procedures and records, observed activities, and interviewed personnel.
The NRC inspectors did not identify any findings or violations of more than minor significance.
However, the enclosed report documents three noncompliances for which the NRC is exercising enforcement discretion in accordance with Section 9.1 of the NRC Enforcement Policy, Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48). The noncompliances are associated with your implementation of the requirements and standards of 10 CFR 50, Appendix R, Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979. The non-compliances were identified by the NRC, and are violations of NRC requirements. The inspectors have screened the violations and determined that they warranted enforcement discretion per the Interim Enforcement Policy Regarding Enforcement Discretion for Certain Fire Protection Issues, and Section 11.05(b) of Inspection Manual Chapter 0305 Operating Reactor Assessment Program. You are not required to respond to this letter. In accordance with 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Website at http://www.nrc.gov./reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely, RA Scott M. Shaeffer, Chief Engineering Branch 2 Division of Reactor Safety Docket Nos.: 50-321, 50-366 License Nos.: DPR-57, NPF-5
Enclosures:
Inspection Report 05000321/2013009, 05000366/2013009 w/Attachment: Supplementary Information
REGION II==
Docket Nos: 50-321, 50-366 License Nos.: DPR-57, NPF-5 Report Nos.: 05000321/2013009 and 05000366/2013009 Licensee: Southern Nuclear Operating Company, Inc.
Facility: Edwin I. Hatch Nuclear Plant Location: Baxley, GA 31513 Dates: November 18 - 22, 2013 (Week 1)
December 2 - 6, 2013 (Week 2)
Inspectors: J. Montgomery, Reactor Inspector (Lead Inspector)
O. López, Senior Reactor Inspector M. Thomas, Senior Reactor Inspector P. Braxton, Reactor Inspector Accompanying Personnel: W. Monk, Reactor Inspector (Training)
Approved by: Scott M. Shaeffer, Chief Engineering Branch 2 Division of Reactor Safety Enclosure
SUMMARY
IR 05000321/2013-009, 05000366/2013-009; 11/18-22/2013 and 12/2-6/2013; E.I. Hatch
Nuclear Plant, Units 1 and 2; Fire Protection (Triennial).
This report covers an announced two-week triennial fire protection inspection by a team of four regional inspectors and one inspector in training. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process Rev. 4, dated December 2006.
No findings were identified.
REPORT DETAILS
REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity
1R05 Fire Protection
This report documents the results of a triennial fire protection inspection of the E.I. Hatch Nuclear Plant (HNP) Units 1 and 2. The inspection was conducted in accordance with the guidance provided in NRC Inspection Procedure 71111.05T, Fire Protection (Triennial), dated January 31, 2013. The objective of the inspection was to review a minimum sample of three risk-significant fire areas (FAs) to evaluate implementation of the Hatch Fire Protection Program (FPP). An additional objective was to review site specific implementation of one mitigating strategy from Section B.5.b of NRC Order EA-02-026, Order for Interim Safeguards and Security Compensatory Measures (commonly referred to as B.5.b), as well as the storage, maintenance, and testing of B.5.b mitigating equipment. The sample FAs were chosen based on a review of available risk information as analyzed by a senior reactor analyst from Region II, a review of previous inspection results, plant walkdowns of FAs, consideration of relational characteristics of combustible material to targets, and location of equipment needed to achieve and maintain safe shutdown (SSD) of the reactor. In selecting a B.5.b mitigating strategy sample, the team reviewed licensee submittal letters, safety evaluation reports (SERs), licensee commitments, B.5.b implementing procedures, and previous NRC inspection reports. Section 71111.05-05 of the IP specifies a minimum sample size of three FAs and one B.5.b mitigating strategy for addressing large fires and explosions. This inspection fulfilled the requirements of the procedure by selecting a sample of three FAs and one B.5.b mitigating strategy. The FAs chosen were identified as follows:
1. Fire Zone 0024B, Computer Room 2. Fire Area 1017, East 600V Switchgear Room 1D 3. Fire Area 1020, East DC Switchgear Room 1B For each of the selected FAs, the team evaluated the licensees FPP against applicable NRC requirements and licensee design basis documents. Applicable licensing and design basis documents reviewed by the team are listed in the Attachment to this report.
.01 Protection of Safe Shutdown Capabilities
a. Inspection Scope
The team reviewed the licensees FPP referenced in the Unit 1 Updated Final Safety Analysis Report (UFSAR) Section 10.8; the licensees safe shutdown analysis report (SSAR); fire hazards analysis (FHA); plant procedures; piping and instrumentation drawings (P&IDs);electrical drawings; and other supporting documents. The team performed the review to verify that hot and cold shutdown could be achieved and maintained from the main control room (MCR) for postulated fires in FAs 1017 and 1020. The review included verification that shutdown from the MCR could be performed both with and without the availability of offsite power. The team performed in-plant inspections to verify that the plant configuration was consistent with that described in the FHA and SSAR. The team reviewed the licensees shutdown methodology to verify that it properly identified the components and systems necessary to achieve and maintain SSD conditions for postulated fires resulting in shutdown from the MCR. The team focused their inspection activities on systems specified in the SSAR for reactivity control, reactor coolant makeup, and decay heat removal, as well as process monitoring instrumentation and necessary support systems.
The team reviewed and performed a walkthrough of procedure steps used for post-fire SSD to ensure the technical and human factors adequacy of the procedures. The team verified the licensee personnel credited for performance of procedures were available in the event a fire occurred, had procedures available, and were trained on implementation. The team also verified that operators could reasonably be expected to perform the procedure actions in order to maintain plant parameters within specified limits. The team reviewed and walked down applicable sections of Abnormal Operating Procedure (AOP) 34AB-X43-001-1, Fire Procedure for Unit 1 FAs 1017 and 1020. The team reviewed operator actions to ensure these actions could be implemented in accordance with plant procedures in a manner necessary to support the SSD method for the applicable fire area.
b. Findings
No findings were identified.
.02 Passive Fire Protection
a. Inspection Scope
The team walked down the selected FAs and fire zone (FZ) to evaluate the adequacy of the fire resistance of walls, ceilings, and floors. This evaluation also included fire barrier concrete block walls, penetration seals, fire doors, and fire dampers to ensure that at least one train of SSD equipment would be maintained free of fire damage. Construction detail drawings and fire tests were reviewed as necessary. Where applicable, the team observed the installed barrier assemblies and compared the as-built configurations to the approved construction details. The team also reviewed supporting fire endurance test data; licensing basis commitments; and standard industry practices.
b. Findings
No findings were identified.
.03 Active Fire Protection
a. Inspection Scope
The team reviewed the redundancy of fire protection water sources and fire pumps to confirm they were installed in accordance with the National Fire Protection Association (NFPA) codes of record. The team performed in-plant observations of the material condition and operational lineup of the fire water pumps and fire protection water supply distribution piping, including manual fire hose and standpipe systems for the selected FAs/FZ. Using operating and valve cycle/alignment procedures, as well as engineering drawings, the team examined the electric motor-driven and the diesel-driven fire pumps and accessible portions of the fire main piping system to evaluate operational status, accuracy of as-built configurations, and to verify correct system valve lineups (i.e. position of valves).
The team compared the fire detection and fire suppression systems for the selected FAs/FZ to the applicable NFPA standard(s) by reviewing design documents; and observed the as-installed configurations of the systems during plant walkdowns. The team reviewed selected fire protection vendor equipment specifications, drawings, and engineering calculations to determine whether the fire detection and suppression methods were appropriate for the types of fire hazards that existed in the selected FAs/FZ. During plant walkdowns, the team observed the placement of the fire hose stations, fire extinguishers, fire hose nozzle types, and fire hose lengths, as designated in the firefighting pre-plan strategies, to verify they were not blocked, and that adequate reach and coverage was provided consistent with the firefighting strategies and FPP documents. The team reviewed completed periodic surveillance testing and maintenance program procedures for the fire detection and suppression systems and compared them to operability requirements, testing criteria, and compensatory measures. This review was to assess whether the test program was sufficient to validate proper operation of the fire detection and suppression systems in accordance with their design requirements.
Aspects of fire brigade readiness were reviewed, including, but not limited to, the fire brigades personal protective equipment, self-contained breathing apparatuses, portable communications equipment, and other fire brigade equipment to determine accessibility, material condition and operational readiness of equipment. During plant walkdowns, the team compared firefighting pre-plan strategies to existing plant layout and equipment configurations and to fire response procedures for the selected FAs/FZ. This was done to verify that firefighting pre-fire plan strategies and drawings were consistent with the fire protection features and potential fire conditions within the area and also to determine if appropriate information was provided to fire brigade members to facilitate suppression of an exposure fire that could impact the SSD strategy.
b. Findings
1. Adequacy of Carbon Dioxide (CO2) Concentration in FZ 0024B
Introduction:
The NRC identified a non-compliance of Hatch Renewed Operating License Conditions (OLCs) 2.C.(3) and 2.C.(3)(a), for Units 1 and 2 respectively, because the installed carbon dioxide (CO2) fire suppression system in the computer room (FZ 0024B) could not deliver the required gas concentration.
Description:
The computer room (FZ 0024B) CO2 gas suppression system was designed in accordance with NFPA 12, Carbon Dioxide Extinguishing Systems 1973. NFPA 12 required a minimum concentration of 50 percent to extinguish fires in dry electrical and wiring insulation hazards. The computer room contained dry electrical wiring insulation hazards in the form of cable insulation and computer/server components. The licensee could not show that 50 percent concentration could be met for the installed system configuration in the computer room.
The team identified the problem by calculating the initial CO2 concentration that would be achieved upon system activation. The team reviewed calculation SX11992, FP-LP CO2 Flow Calculation Cable Spreading Room;Section IV.C of the FHA; and procedure 52SV-FPX-010-0, Low Pressure CO2 System Surveillance, Version 3. Procedure 52SV-FPX-010-0 stated that the acceptable range for discharge time was between 3 minutes and 17 seconds and 3 minutes and 23 seconds. The team obtained the volume of the room, the required design concentration, expected CO2 loss due to leakage, and CO2 discharge rate in 2 minutes. Based on the room volume, including expected losses due to leakage, and expected flow rate, the team determined a discharge time of 3 minutes and 45 seconds would be required to reach the design concentration. Using the criteria in procedure 52SV-FPX-010-0, the team determined that the system would discharge approximately 88% of the required concentration.
As a result, the team determined that the time of discharge was not sufficient to release the needed concentration of CO2 in the room to adequately suppress a fire in that room. Since system discharge testing had not been performed, the problem went undetected until identified by the team. The licensee performed a preliminary calculation that confirmed the teams results, and entered the issue into the corrective action program (CAP) as Condition Report (CR) 736771. Additionally, the licensee determined that the current procedure did not address leakage out of the room to ensure that the required concentration was maintained.
The licensee implemented interim actions to ensure adequate CO2 concentration in the event of a fire in the computer room. The interim actions included increasing the minimum CO2 level in the associated tank to 70%; and revising procedure 34SO-Z43-002-2 to require an additional 60 seconds of discharge time.
Analysis:
The team determined that the licensees failure to implement design requirements for the CO2 system in the computer room was a performance deficiency. This performance deficiency was determined to be more than minor because it was associated with the reactor safety Mitigating Systems cornerstone attribute of protection against external factors (i.e. fire),and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences.
Specifically, the discharge time for the fire suppression system in FZ 0024B was not sufficient to release the required CO2 concentration to adequately suppress a fire.
The finding was screened in accordance with NRC Inspection Manual Chapter (IMC) 0609, Significance Determination Process (SDP), Attachment 4, Initial Characterization of Findings, which determined that an IMC 0609 Appendix F, Fire Protection Significance Determination Process, review was required because the finding affected fixed fire protection systems. Using the Fire Protection SDP Phase 1 Screening, the finding was assigned a category of Fixed Fire Protection Systems.
Using IMC 0609, Appendix F, Attachment 2, the finding was assigned a High degradation rating because the suppression system would not reach the designed concentration as required by NFPA 12. The team used step 1.4 Qualitative Screening Question Set for Seven Individual Categories, task 1.4.2 Fixed Fire Protection System of IMC 0609, Appendix F, Attachment 1 to determine the finding to be of very low safety significance (i.e., Green) because the finding affected only a manually actuated suppression system for an area that is accessible by the fire brigade.
The team determined that no cross cutting aspect was applicable to this performance deficiency because this finding was not indicative of current licensee performance.
Enforcement:
Hatch Renewed OLCs 2.C.(3) and 2.C.(3)(a), for Units 1 and 2 respectively, state, in part, that Southern Nuclear shall implement and maintain in effect all provisions of the fire protection program, which is referenced in the Updated Final Safety Analysis Report for the facility, as contained in the updated Fire Hazards Analysis and Fire Protection Program for the Edwin I. Hatch Nuclear Plant, Units 1 and 2, which was originally submitted by letter dated July 22, 1986.
Section IV.C.5, Carbon Dioxide Suppression Systems, of Appendix D of the FHA states, in part, that the computer room design concentrations are in compliance with NFPA Standard No. 12, Section 2421, which requires a 50-percent concentration for "dry electrical, wiring insulation hazards in general". NFPA 12 states, in part, that an acceptable CO2 system deliver and hold a minimum gas concentration of 50 percent in the protected area.
Contrary to the above, the CO2 system design concentration in the computer room is not in compliance with the Hatch FHA, in that the CO2 system would not deliver and hold a minimum gas concentration of 50 percent in the protected area. The violation has existed since initial plant start-up. The licensee entered the deficiency in the CAP as CR 736771.
Because the licensee committed to adopt NFPA 805 and change their fire protection licensing bases to comply with 10 CFR 50.48(c), the NRC is exercising enforcement and reactor oversight process (ROP) discretion for this issue in accordance with the NRC Enforcement Policy, Section 9.1, Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48)and Inspection Manual Chapter 0305. Specifically, this issue was identified and will be addressed during the licensees transition to NFPA 805, was entered into the licensees corrective action program, immediate corrective action and compensatory measures were taken, was not likely to have been previously identified by routine licensee efforts, was not willful, and it was not associated with a finding of high safety significance (i.e., Red).
2. Failure to Meet Section IV.C, Fire Detection and Suppression of Appendix D of the Fire Hazards
Analysis
Introduction:
The NRC identified a non-compliance of Hatch OLCs 2.C.(3) and 2.C.(3)(a), for Units 1 and 2 respectively, for the failure to locate fire extinguishers in the cable spreading room (CSR) in accordance with NFPA 10 and for the failure to locate manual hose stations in or near the CSR, such that an effective hose stream could be directed to any area in the room.
Description:
The FHA stated that the CSR (FZ 0024A) was equipped with a hose station and a fire extinguisher located in the adjacent room (FA 0025 mezzanine) for manual firefighting. The FHA stated that the area had mostly Class A (cable insulation) combustibles with a fire duration of greater than three hours. As a result, the licensee designated the CSR as having a high combustible loading. The FHA stated that manual firefighting equipment was fully adequate to extinguish the fire if the automatic suppression system failed.
The requirements for manual firefighting capabilities were described in Section IV.C, Fire Detection and Suppression of Appendix D of the FHA.Section IV.C.6 required the licensee to provide portable fire extinguishers in the plant in accordance with NFPA 10, Standard for Portable Fire Extinguishers. For Class A hazards (such as cable insulation), NFPA 10 required fire extinguishers to be located such that the maximum travel distance to an extinguisher was 75 feet.
The team identified that there were no fire extinguishers located in the CSR. The closest fire extinguisher to the CSR was located in an adjacent room (FA 0025 mezzanine). Based on the physical dimensions of the CSR, and physical obstructions in the room due to cable trays, the team determined that the travel distances from at least half of the CSR to the closest fire extinguisher exceeded the 75 foot maximum travel distance specified in NFPA 10.
Section IV.C.3.d of Appendix D of the FHA required the licensee to provide manual hose stations throughout the plant to ensure that an effective hose stream could be directed to any area in the plant. The team observed that there was one hose station (HS-C20) inside the CSR and another hose station (HS-C21) in the adjacent room (FA 0025 mezzanine). However, the team noted that the licensee had deemed HS-C20 as not usable because cable trays blocked access to the hose. On July 20, 2011, the licensee implemented LDCR 2011-024 to remove the regulatory requirements for this hose station. Hose station HS-C21 was selected to serve the CSR. Additional fire hose was staged at HS-C21 to ensure that area wide coverage of the CSR was available with the fire hose stream. The team noted that the licensee did not consider physical obstructions presented in the room due to cable trays and the torturous path that responders would have to take to cover the entire CSR. Therefore, the team determined that the additional fire hose staged at HS-C21 was not sufficient to provide an effective hose stream to all areas in the CSR.
In response to these issues, the licensee initiated CR 740396 for the deficiency related to fire extinguisher placement; and CR 741521 for the deficiency related to the CSR fire hose coverage. The licensee also began evaluating potential locations in the CSR where fire extinguishers could be installed to facilitate firefighting efforts in the CSR.
Analysis:
The team determined that the licensees failure to locate fire extinguishers in the CSR, and failure to locate manual hose stations in or near the CSR such that an effective hose stream could be directed to any area in the room were performance deficiencies. The performance deficiencies were determined to be more than minor because they were associated with the reactor safety Mitigating Systems cornerstone attribute of protection against external factors (i.e. fire), and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the performance deficiencies could adversely impact timely manual fire suppression capability of a fire.
The finding was screened in accordance with IMC 0609, Significance Determination Process (SDP), Attachment 4, Initial Characterization of Findings, which determined that an IMC 0609 Appendix F, Fire Protection Significance Determination Process, review was required because the finding affected manual firefighting. Using the Fire Protection SDP Phase 1 Screening, the finding was assigned a category of Manual Firefighting.
The team used step 1.3 Ability to Achieve Safe Shutdown, task 1.3.1 Screen Fire Finding for Ability to Achieve Safe Shutdown of IMC 0609, Appendix F, Attachment 1 to determine the finding to be of very low safety significance (i.e., Green) because the finding was assigned a low degradation rating. Using IMC 0609, Appendix F, Attachment 2, the finding was assigned a low degradation rating because the CSR was equipped with pre-action sprinkler system and fire detection that would alarm in the control room. Additionally, a hose station and fire extinguisher located outside the room would provide partial coverage for the CSR.
The team determined that no cross cutting aspect was applicable to this performance deficiency because this finding was not indicative of current licensee performance.
Enforcement:
Hatch Renewed OLCs 2.C.(3) and 2.C.(3)(a), for Units 1 and 2 respectively, states, in part, that Southern Nuclear shall implement and maintain in effect all provisions of the fire protection program, which is referenced in the Updated Final Safety Analysis Report for the facility, as contained in the updated Fire Hazards Analysis and Fire Protection Program for the Edwin I. Hatch Nuclear Plant, Units 1 and 2, which was originally submitted by letter dated July 22, 1986.Section IV.C, Fire Detection and Suppression of Appendix D of the FHA, contains requirements for the licensees manual suppression capability.
Contrary to the above, the licensee failed to meet the requirements of Section IV.C. of Appendix D of the FHA, with the following examples:
1.Section IV.C.3.d, Water Sprinkler and Hose Standpipe Systems, of Appendix D of the FHA states, in part, that manual hose stations are located throughout the plant. An effective hose stream can be directed to any area in the plant. Contrary to the above, the licensee failed to locate manual hose stations in or near the CSR such that an effective hose stream could be directed to any area of the CSR. This issue has existed since 2011, when the licensee completed a plant change to take credit for hose HS-C21 to combat a fire in the CSR.
2.Section IV.C.6, Portable Extinguishers, of Appendix D of the FHA states that portable fire extinguishers are provided in the plant in accordance with NFPA 10. NFPA 10 (1975 Edition), requires that fire extinguishers serving Class A hazards (such as cable insulation) be located such that the maximum travel distance to extinguisher is 75 feet.
Contrary to the above, the licensee failed to locate fire extinguishers in an area serving Class A hazards such that the maximum travel distance to an extinguisher was not greater than 75 feet. Specifically, the licensee failed to locate portable fire extinguishers in the CSR, which contained Class A hazards such as cable insulation. This issue has existed since initial plant startup.
Because the licensee committed to adopt NFPA 805 and change their fire protection licensing bases to comply with 10 CFR 50.48(c), the NRC is exercising enforcement and reactor oversight process (ROP) discretion for this issue in accordance with the NRC Enforcement Policy, Section 9.1, Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48)and Inspection Manual Chapter 0305. Specifically, this issue was identified and will be addressed during the licensees transition to NFPA 805, was entered into the licensees corrective action program, immediate corrective action and compensatory measures were taken, was not likely to have been previously identified by routine licensee efforts, was not willful, and it was not associated with a finding of high safety significance (i.e., Red).
04. Protection From Damage From Fire Suppression Activities
a. Inspection Scope
The team evaluated whether water-based manual firefighting activities could adversely affect equipment credited for SSD, inhibit access to alternate shutdown equipment, or adversely affect local operator manual actions (OMAs) required for SSD in the selected FAs/FZ. The team reviewed available documentation related to flooding analysis from fire protection activities, being sensitive to potential flooding through unsealed concrete floor cracks.
The team reviewed firefighting pre-plan strategies; fire brigade training procedures; fire damper locations; heating, ventilation and air conditioning (HVAC) drawings; and fire response procedures to verify that inter-area migration of ventilation of gaseous heat and smoke was addressed, and access to SSD equipment and OMAs would not be inhibited by smoke migration from the affected fire area to adjacent plant areas used to accomplish SSD.
b. Findings
No findings were identified.
.05 Alternative Shutdown Capability
a. Inspection Scope
Methodology The team reviewed the licensees FPP referenced in Unit 1 UFSAR Section 10.8, the FHA, SSAR, plant procedures, P&IDs, electrical drawings, and other supporting documents for postulated fires in FZ 0024B. The team performed the review to ensure that the required functions for post-fire SSD, and the corresponding equipment necessary to perform those functions, were included in the procedures. The team assessed whether transfer of control from the MCR to the remote shutdown panel (RSDP), as well as hot and cold shutdown from outside the MCR, could be successfully accomplished. The review included verification that shutdown from outside the MCR could be performed both with and without the availability of offsite power.
The team performed in-plant inspections to verify that the plant configuration was consistent with that described in the SSAR. The team focused their inspection activities on systems specified in the SSAR for reactivity control, reactor coolant makeup, and decay heat removal, as well as process monitoring instrumentation and necessary support systems.
Operational Implementation The team reviewed shift attendance records to verify that personnel required to accomplish SSD, exclusive of those assigned as fire brigade members, were available. The team also verified that licensee personnel had adequate SSD procedures and were trained on implementation. The team reviewed training lesson plans, job performance measures, and simulator scenarios for licensed and non-licensed operators to verify that the training included the shutdown methodology of the SSAR and the SSD procedures required to be used for a fire in FZ 0024B.
The team reviewed and walked down selected applicable steps of AOP 34AB-X43-001-1, Abnormal Operating Procedure, Fire Procedure and remote shutdown procedure 31RS-OPS-001-1, Shutdown From Outside Control Room, in order to assess technical and human factors adequacy of the procedures. The team also verified that operators could reasonably be expected to perform the procedure actions in order to maintain plant parameters within specified limits. The team reviewed periodic test procedures and test records of alternate shutdown transfer capability and instrumentation and control functions, to ensure that the tests were adequate to verify the functionality of alternative shutdown capability.
b. Findings
No findings were identified.
.06 Circuit Analyses
a. Inspection Scope
This segment was suspended for plants that have been in transition to NFPA 805 for less than 3 years because a more detailed review of cable routing and circuit analysis will be conducted as part of the FPP transition to NFPA 805.
b. Findings
No findings were identified.
.07 Communications
a. Inspection Scope
The team reviewed the communication capabilities required to support plant personnel in the performance of OMAs to achieve and maintain SSD, as credited in the Hatch FPP. The team performed plant walkdowns with the licensees operations staff to assess the credited method of communications used to complete SSD actions as specified in post-fire SSD procedures for the selected FAs/FZ. The team assessed the operators ability to communicate by observing the performance of radio checks from applicable control locations by licensee operations personnel.
The team assessed if communications were possible, given the background noise from plant equipment, to determine if this would deter the operators ability to implement the response strategy within the time required by the plant feasibility analysis. The team also verified that portable radio communications, sound powered phones and fixed emergency communication systems were available, operable, and adequate for the performance of designated activities to support fire event notification and fire brigade firefighting activities. The team reviewed preventive maintenance and surveillance test records and vendor manuals to verify that the communication equipment was being properly maintained and tested.
b. Findings
No findings were identified.
.08 Emergency Lighting
a. Inspection Scope
The team reviewed maintenance and design aspects of the fixed 8-hour battery pack emergency lighting units (ELUs) required by 10 CFR 50 Appendix R, Section III.J, and the Hatch approved FPP. The team performed plant walkdowns of the post-fire SSD procedures for the selected FAs/FZ to observe the placement and coverage area of the ELUs required to illuminate operator access and egress pathways, and any equipment requiring local operation and/or instrumentation monitoring for post-fire SSD. In some instances, operations personnel performed onsite tests of the ELUs to verify operation. The team also reviewed completed surveillances, system health reports, and maintenance tests to verify that adequate surveillance testing was in place. The manufacturers information and vendor manuals for the fixed and portable 8-hour battery pack ELUs were reviewed to verify that the battery power supplies were rated with at least an 8-hour capacity, and that the ELUs were being stored and maintained in accordance with vendor guidance.
b. Findings
No findings were identified.
.09 Cold Shutdown Repairs
a. Inspection Scope
The team reviewed the licensees FHA and SSAR to verify that the licensee had evaluated the need for cold shutdown repairs. The team determined from the review that the licensee did not take credit for repairs to cold shutdown components in order to achieve cold shutdown.
b. Findings
No findings were identified.
.10 Compensatory Measures
a. Inspection Scope
- (1) Compensatory Measures for Degraded Fire Protection Components The team reviewed the administrative controls for out-of-service, degraded and/or inoperable fire protection features (e.g. detection and suppression systems and passive fire barriers) to verify that short-term compensatory measures adequately compensated for the degraded function or feature until appropriate corrective actions could be taken.
- (2) Operator Manual Actions as Compensatory Measures for Safe Shutdown The team reviewed the SSAR, FHA, and applicable AOPs, to determine if the licensees SSD methodology credited OMAs outside the MCR as compensatory measures for SSD, for postulated fires in Unit 1 FAs 1017 and 1020, and Unit 2 FA 2203.
b. Findings
No findings were identified.
.11 Review and Documentation of Fire Protection Program Changes
a. Inspection Scope
The team reviewed a sample of FPP changes made between August 2010 and December 2013 to assess the licensees effectiveness of the FPP change process, and to determine if the changes to the FPP were in accordance with the fire protection license condition and had no adverse effect on the ability to achieve SSD. The team also reviewed additional FPP changes to support review of LER 2013-004-01.
b. Findings
Introduction:
The NRC identified a non-compliance of Hatch Unit 2 Renewed OLC 2.C.(3)(a),
Fire Protection, for making a change to the FPP that adversely affected the licensees ability to achieve and maintain safe shutdown. Specifically, the licensee removed the installed Unit 2 RSDP halon suppression system that was required to meet an approved exemption. The licensee failed to submit the FPP change to the NRC for review and approval prior to implementing the modification, which impacted the ability of the NRC to perform its regulatory oversight function.
Description:
In an SER dated April 18, 1984, the NRC allowed an exemption request from 10 CFR 50, Appendix R, Section III.G.2 for the Unit 2 Reactor Building elevation 130. In this SER, the NRC documented that the licensee committed to several modifications, which included the installation of an automatic halon fire suppression system for the Unit 2 RSDP. The halon suppression system would limit the consequences of a fire internal to the RSDP. The NRC concluded that the existing fire protection measures, with the proposed modifications, would achieve a level of safety equivalent to that provided by 10 CFR 50, Appendix R, Section III.G.2.
During a plant walkdown of FA 2203 to support the review of LER 2013-004, the team noted that the halon suppression system had been abandoned in place. Discussions with the licensee revealed that the system had been abandoned since 1999. Additionally, in 2006, the licensee initiated a design change (DCP 2009001901) to completely remove the halon system, along with its associated piping and support, from the Unit 2 RSDP.
The team noted that the licensees FPP is based on the defense-in-depth concept, and that this approach includes promptly detecting and extinguishing fires that occur. The condition of not having the committed suppression system was a degradation of the defense-in-depth concept.
Specifically, the lack of a suppression system would adversely affect the ability to control and promptly extinguish a fire. The licensee entered the deficiency into their CAP as CR 736483.
An hourly fire watch was already in place for the affected FA, because of LER 2013-004.
Analysis:
The team determined that the failure to obtain NRC approval prior to making a change to the FPP that was adverse to safe shutdown was a performance deficiency. This performance deficiency was determined to be more than minor because it was associated with the reactor safety Mitigating Systems cornerstone attribute of protection against external factors (i.e. fire), and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences.
Specifically, the licensee removed the halon suppression system for the RSDP, which degraded the ability to suppress a fire that originated in the panel.
The finding was screened in accordance with IMC 0609, Significance Determination Process (SDP), Attachment 4, Initial Characterization of Findings, dated June 19, 2012, which determined that an IMC 0609 Appendix F, Fire Protection Significance Determination Process review was required because the finding affected fixed fire protection systems. Using the Fire Protection SDP Phase 1 Screening, the finding was assigned a category of Fixed Fire Protection Systems.
The team used step 1.3 Ability to Achieve Safe Shutdown, task 1.3.1 Screen Fire Finding for Ability to Achieve Safe Shutdown, of IMC 0609, Appendix F, Attachment 1 to determine the finding to be of very low safety significance (i.e., Green) because the reactor would have been able to reach and maintain safe shutdown conditions. The reactor would be able to reach and maintain safe shutdown conditions because photoelectric detectors were installed inside the RSDP and linear heat detection was installed along the sides of the cable raceways located directly above the RSDP. The installed detectors would aid in preventing the growth and spread of a fire by allowing sufficient time for the fire brigade to intervene.
The team determined that no cross cutting aspect was applicable to this performance deficiency because this finding was not indicative of current licensee performance.
Additionally, the licensees failure to submit the adverse FPP change to the NRC for review was screened under the traditional enforcement criteria, because it impacted the ability of the NRC to perform its regulatory oversight function. In accordance with Section 6.1.d.2 of the NRC Enforcement Policy, this violation was characterized as Severity Level IV because the resulting changes were evaluated by the SDP as having very low safety significance (Green).
Enforcement:
Hatch Unit 2 Renewed OLC 2.C.(3)(a) states, in part, that the licensee may make changes to the fire protection program without prior Commission approval only if the changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire. This license condition also states that the Hatch Fire Protection Program is referenced in the Updated Final Safety Analysis Report for the facility, as contained in the updated Fire Hazards Analysis and Fire Protection Program for the Edwin I. Hatch Nuclear Plant Units 1 and 2, which was originally submitted by letter from GPC to the Commission dated July 22, 1986.
Contrary to the above the licensee made a change to the FPP, without prior Commission approval, that adversely affected the ability to achieve and maintain SSD in the event of a fire.
Specifically the licensee completed a 10 CFR 50.59 evaluation that erroneously concluded that the halon suppression system installed for the RSDP was not required to meet Appendix R requirements and, therefore, could be removed without prior Commission approval. The removal of the halon suppression system degraded the ability to suppress a fire and challenged the ability to achieve and maintain SSD in the event of a fire.
Because the licensee committed to adopt NFPA 805 and change their fire protection licensing bases to comply with 10 CFR 50.48(c), the NRC is exercising enforcement and reactor oversight process (ROP) discretion for this issue in accordance with the NRC Enforcement Policy, Section 9.1, Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48),and Inspection Manual Chapter 0305. Specifically, this issue was identified and will be addressed during the licensees transition to NFPA 805, was entered into the licensees corrective action program, immediate corrective action and compensatory measures were taken, was not likely to have been previously identified by routine licensee efforts, was not willful, and it was not associated with a finding of high safety significance (i.e., Red).
.12 Control of Combustibles and Ignition Sources
a. Inspection Scope
The team conducted tours of numerous plant areas that were important to reactor safety, including the selected FAs/FZ, to verify the licensees implementation of FPP requirements as described in the FHA and administrative procedure 31GO-OPS-026-0, Use, Control, and Storage of Flammable/Combustible Materials. For the selected FAs/FZ, the team evaluated generic fire protection training; fire event history; the potential for fires or explosions; the combustible fire load characteristics; and, the potential exposure fire severity to verify that adequate controls were in place to maintain general housekeeping consistent with the FPP, administrative procedures, and other FPP procedures. There were no hot work activities ongoing within the selected fire areas during the inspection and observation of this activity could not be performed.
b. Findings
No findings were identified.
.13 B.5.b Inspection Activities
a. Inspection Scope
The team reviewed, on a sample basis, the licensees mitigation measures for reactor pressure vessel depressurization and injection for large fires and explosions to verify that the measures were feasible, personnel were trained to implement the measures, and equipment was properly staged and maintained. The team reviewed surveillance testing records to verify that required equipment was adequately maintained. Through discussions with plant staff, review of documentation, and plant walkdowns, the team verified the engineering basis to establish reasonable assurance that the makeup capability could be provided using the specified equipment and water sources. The team reviewed the licensees capability to provide a reliable and available water source and the ability to provide the minimum fuel supply. The team reviewed inventory records and performed a walkdown of the storage and staging areas for the B.5.b equipment to verify that equipment identified for use in the procedures was available and maintained. The team conducted an independent audit and inventory of required equipment and a visual inspection of the dedicated credited power and water source. The team reviewed training records to verify that operations and security personnel training/familiarity with the strategy objectives and implementing guidelines were accomplished according to the established training procedures.
b. Findings
No findings were identified.
OTHER ACTIVITIES
4OA2 Problem Identification and Resolution
a. Inspection Scope
The team reviewed recent independent licensee audits, self-assessments, and system/program health report for thoroughness, completeness and conformance to FPP requirements. The team also reviewed CAP documents, including completed corrective actions documented in selected CRs, and operating experience program documents, to ascertain whether industry identified fire protection issues (actual or potential) affecting HNP were appropriately entered into the CAP for resolution. Items included in the operating experience program effectiveness review were NRC Information Notices, Regulatory Issue Summaries, industry or vendor generated reports of defects and non-compliances submitted pursuant to 10 CFR Part 21, and vendor information letters. The team evaluated the effectiveness of the corrective actions for the identified issues. The documents reviewed are listed in the Attachment.
b. Findings
No findings were identified.
4OA3 Follow-up of Events
(Discussed) Licensee Event Report (LER) 50-366/2013-004-01, Postulated Inter-cable Fault Vulnerability for RHR Shutdown Cooling Isolation Valves During A Postulated Fire Event Results in Unanalyzed Condition The licensee described a condition in Revision 0 of the subject LER (dated October 8, 2013)where, during a postulated fire scenario for Unit 2 FA 2203F, an inter-cable hot short could occur on the control cables for two RHR shutdown cooling isolation valves, causing the valves to spuriously open while at rated power. The valves spuriously opening at rated power could result in an inter-system loss of coolant accident. The vulnerability was identified in August 2013 during circuit analysis that considered inter-cable shorts as a plausible vector in the SSA for some high/low pressure interface components. Originally, Hatchs FHA and SSAR limited the circuit analysis to intra-cable hot shorts (conductors within the cable), but did not consider inter-cable hot shorts (conductors within co-located cables in the same tray). Additionally, the FHA and the SSAR stated, in part, that hot shorts between conductors of different cables need not be postulated.
Upon discovering this condition, the licensee took immediate corrective actions that included establishing hourly fire watches, and de-energizing both valves in the closed position to remove the vulnerability. The licensee concluded that the vulnerability did not exist for the corresponding Unit 1 set of valves. Revision 1 of the LER (dated November 14, 2013) stated, upon further evaluation, the cause of the event was attributed to the ineffective monitoring and follow-up of regulatory activities/guidance (Regulatory Guide 1.189 and Nuclear Energy Institute 00-01) involving inter-cable hot shorts in identifying the vulnerability associated with the RHR isolation valves. This LER remains open pending further NRC review.
4OA6 Meetings, Including Exit
On December 6, 2013, the lead inspector presented the preliminary inspection results to Mr.
David Vineyard and other members of the licensees staff, who acknowledged the results.
Following completion of additional reviews in the Region II office, a conference call was held with Mr. Steve Tipps on January 16, 2014, to provide an update on changes to the preliminary inspection findings. The licensee acknowledged the findings. Proprietary information is not included in this inspection report.
ATTACHMENT:
SUPPLEMENTARY INFORMATION
KEY POINTS OF CONTACT
Licensee Personnel
- S. Beverly, Licensing Engineer
- M. Dean, Maintenance
- D. Edenfield, PRA Engineer
- J. Gardner, Fire Marshall
- J. Lattner, Principal Fire Protection Engineer, SNC Corporate
- J. Moser, Fire Brigade Instructor
- D. Patel, Component Supervisor
- S. Tipps, Licensing Supervisor
- D. Vineyard, Site Vice President
- J. Yurkosky, Fire Protection Engineer
NRC Personnel
- D. Hardage, Resident Inspector
- E. Morris, Senior Resident Inspector
- S. Shaeffer, Chief, Engineering Branch 2, DRS, Region II
LIST OF ITEMS OPENED, CLOSED, DISCUSSED, AND UPDATED
Discussed
- 05000366/2013-004-01 LER Postulated Inter-cable Fault Vulnerability for RHR Shutdown Cooling Isolation Valves During A Postulated Fire Event Results in Unanalyzed Condition (Section 4OA3)
LIST OF FIRE BARRIER FEATURES INSPECTED (Refer Report Section 1RO5.02- Passive Fire Barriers)
Fire Barriers Floors/Walls/Ceiling Identification Description 1Z43-H007D FA 1017 to FZ 0014N 1Z43-H004D FA 1017 to FA 1104 1Z43-H810D FA 1017 to FA 1020 1Z43-H010D FA 1020 to FA 1104 1Z43-H012D FA 1020 to FZ 0014N 1Z43-H063F FZ 0024B to FA 0025 1Z43-H062F FZ 0024B to FA 0025 1Z43-H064F FZ 0024B to FA 0025 1X43-H522D Fire Pump House 1X43-H521D Fire Pump House Fire Door Identification Description 1L48C31 FA 1017 to FZ 0014N 1L48C29 FA 1020 to FZ 0014N 1L48D214 Fire Pump House 1L48D215 Fire Pump House Fire Damper Identification Description 1Z41-FD-F071 FZ 0024B to FA 0025 1Z41-FD-F064 FA 1017 to FA 1020