MONTHYEARIR 05000269/20240032024-10-31031 October 2024 Integrated Inspection Report 05000269/2024003 and 05000270/2024003 and 05000287/2024003 (2) ML24255A3322024-10-16016 October 2024 SLRA - Revised SE Letter ML24297A6172024-10-11011 October 2024 PCA Letter to NRC Oconee Hurricane Helene ML24269A0912024-10-0909 October 2024 Request for Withholding Information from Public Disclosure ML24145A1782024-08-26026 August 2024 Issuance of Amendment Nos. 430, 432, and 431, to TS 5.5.2, Containment Leakage Rate Testing Program for a one-time Extension of the Type a Leak Rate Test Frequency IR 05000269/20240052024-08-26026 August 2024 Updated Inspection Plan for Oconee Nuclear Station, Units 1, 2 and 3 (Report 05000269/2024005, 05000270/2024005, and 05000287-2024005) 05000287/LER-2024-001, Procedure Deficiency Results in Inadvertent Automatic Feedwater Isolation and Automatic Emergency Feedwater Actuation2024-08-0202 August 2024 Procedure Deficiency Results in Inadvertent Automatic Feedwater Isolation and Automatic Emergency Feedwater Actuation IR 05000269/20240022024-07-25025 July 2024 Integrated Inspection Report 05000269/2024002 and 05000270/2024002 and 05000287/2024002 ML24192A1312024-07-15015 July 2024 Licensed Operator Positive Fitness-For-Duty Test ML24183A0972024-07-12012 July 2024 ISFSI; Catawba 1, 2 & ISFSI; McGuire 1, 2 & ISFSI; Oconee 1, 2, 3 & ISFSI; Shearon Harris 1; H. B. Robinson 2 & ISFSI; and Radioactive Package Shipping Under 10 CFR 71 (71-266 & 71-345) – Review of QA Program Changes EPID L-2024-LLQ-0002 ML24183A2352024-06-29029 June 2024 Update 3 to Interim Report Regarding a Potential Defect with Schneider Electric Medium Voltage Vr Type Circuit Breaker Part Number V5D4133Y000 ML24179A1102024-06-27027 June 2024 Submittal of Updated Final Safety Analysis Report Revision 30, Technical Specifications Bases Revisions, Selected Licensee Commitment Revisions, 10 CFR 50.59 Evaluation Summary Report, and 10 CFR 54.37 Update, and Notification ML24141A0482024-05-17017 May 2024 EN 56958_1 Ametek Solidstate Controls, Inc IR 05000269/20240012024-05-0303 May 2024 Integrated Inspection Report 05000269/2024001, 05000270/2024001 and 05000287/2024001 IR 05000269/20244022024-04-24024 April 2024 Security Baseline Inspection Report 05000269/2024402 and 05000270/2024402 and 05000287/2024402 ML24108A0792024-04-16016 April 2024 EN 57079 Paragon Energy Solutions Email Forwarding Part 21 Interim Report Re Potential Defect with Schneider Electric Medium Voltage Vr Type Circuit Breaker Part Number V5D4133Y000 IR 05000269/20244012024-03-28028 March 2024 – Security Baseline Inspection Report 05000269-2024401 and 05000270-2024401 and 05000287-2024401 ML24088A3052024-03-25025 March 2024 Fws to NRC, Agreement with Nlaa Determination for Tricolored Bat for Oconee Lr 05000270/LER-2023-001, Inappropriate Procedural Guidance for Planned Online Maintenance Results in Event or Condition That Could Have Prevented Fulfillment of a Safety Function Licensee2024-02-29029 February 2024 Inappropriate Procedural Guidance for Planned Online Maintenance Results in Event or Condition That Could Have Prevented Fulfillment of a Safety Function Licensee 05000287/LER-2023-002, Passive Containment Isolation Device Inoperability Results in Operation or Condition Prohibited by Technical Specifications2024-02-29029 February 2024 Passive Containment Isolation Device Inoperability Results in Operation or Condition Prohibited by Technical Specifications IR 05000269/20230062024-02-28028 February 2024 Annual Assessment Letter for Oconee Nuclear Station Units 1, 2 and 3 - (NRC Inspection Report 05000269/2023006, 05000270/2023006, and 05000287/2023006) ML24045A3042024-02-16016 February 2024 Ltr. to Lisa M. Collins Chief the Wassamasaw Tribe of Varnertown Indians Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24030A0052024-02-16016 February 2024 Ltr. to Brian Harris, Chief, Catawba Indian Nation; Re., Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A2942024-02-16016 February 2024 Ltr. to Carolyn Chavis Bolton Chief Pee Dee Indian Nation of Upper Sc Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A2962024-02-16016 February 2024 Ltr. to David Hill Principal Chief Muscogee Creek Nation Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A2992024-02-16016 February 2024 Ltr. to Eric Pratt Chief the Santee Indian Organization Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3082024-02-16016 February 2024 Ltr. to Ralph Oxendine Chief Sumter Tribe of Cheraw Indians Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3022024-02-16016 February 2024 Ltr. to Joe Bunch United Keetoowah Band of Cherokee Indians in Ok Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3072024-02-16016 February 2024 Ltr. to Pete Parr Chief Pee Dee Indian Tribe Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3032024-02-16016 February 2024 Ltr. to John Creel Chief Edisto Natchez-Kusso Tribe of Sc Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3012024-02-16016 February 2024 Ltr. to Harold Hatcher Chief the Waccamaw Indian People Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A2952024-02-16016 February 2024 Ltr. to Chuck Hoskin, Jr, Principal Chief Cherokee Nation Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A2972024-02-16016 February 2024 Ltr. to Dexter Sharp Chief Piedmont American Indian Assoc Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3052024-02-16016 February 2024 Ltr. to Louis Chavis Chief Beaver Creek Indians Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24045A3062024-02-16016 February 2024 Ltr. to Michell Hicks, Principal Chief Eastern Band of Cherokee Re Oconee Nuclear Station Units 1,2, and 3 Section 106 ML24019A1442024-02-13013 February 2024 Letter to Reid Nelson, Executive Director, Achp; Re Oconee Nuclear Station Units 1, 2, and 3 Section 106 ML24011A1532024-02-13013 February 2024 Letter to Tracy Watson EPA-Oconee Nuclear Sta, Unites 1, 2 & 3 Notice of Avail of the Draft Site-Specific Supp. 2, 2nd Renewal to the Generic EIS for Lic. Renew of Nuclear Plants ML24030A5212024-02-13013 February 2024 Letter to Elizabeth Johnson, Director, SHPO; Re Oconee Nuclear Stations Units 1, 2, and 3 Section 106 ML24011A1482024-02-13013 February 2024 Letter to Steven M. Snider-Oconee Nuclear Sta, Unites 1,2 & 3 Notice of Avail of the Draft Site-Specific Supp. 2, 2nd Renewal to the Generic EIS for Lic. Renew of Nuclear Plants IR 05000269/20230042024-02-13013 February 2024 Integrated Inspection Report 05000269/2023004, 05000270/2023004, and 05000287/2023004; and Inspection Report 07200040/2023001 ML23304A1422024-02-0101 February 2024 Issuance of Environmental Scoping Summary Report Associated with the U.S. Nuclear Regulatory Commission Staff’S Review of the Oconee Nuclear Station, Units 1, 2, & 3, Subsequent License Renewal Application ML24005A2492024-01-24024 January 2024 Exemption from Select Requirements of 10 CFR Part 73 (Security Notifications, Reports, and Recordkeeping and Suspicious Activity Reporting) IR 05000269/20243012024-01-11011 January 2024 Notification of Licensed Operator Initial Examination 05000269/2024301, 05000270/2024301, and 05000287/2024301 ML23331A7982023-12-14014 December 2023 Review of the Fall 2022 Steam Generator Tube Inspection Report (01R32) ML23262A9672023-12-13013 December 2023 Alternative to Use RR-22-0174, Risk-Informed Categorization and Treatment for Repair/Replacement Activities in Class 2 and 3 Systems Section XI, Division 1 ML23317A3462023-11-14014 November 2023 Duke Fleet - Correction Letter to License Amendment Nos. 312 & 340 Issuance of Amendments Regarding the Adoption of Technical Specifications Task Force Traveler TSTF-554, Revision 1 IR 05000269/20230032023-11-14014 November 2023 Integrated Inspection Report 05000269/2023003, 05000270/2023003, and 05000287/2023003; and IR 07200040/2023001; and Exercise of Enforcement Discretion ML23219A1402023-10-10010 October 2023 Audit Report Proposed Alternative to Use ASME Code Case N-752, Risk Informed Categorization and Treatment for Repair/Replacement Activities in Class 2 and 3 Systems XI, Division 1 ML23269A1102023-10-0606 October 2023 Letter to Steven Snider-Revised Schedule for the Environmental Review of the Oconee Nuclear Station, Unit 1, 2, and 3, Subsequent License Renewal Application ML23256A0882023-09-25025 September 2023 Issuance of Alternative to Steam Generator Welds 2024-08-26
[Table view] Category:Technical Specification
MONTHYEARRA-24-0092, Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required LPSW Pump Inoperable on a One-Time Basis2024-07-29029 July 2024 Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required LPSW Pump Inoperable on a One-Time Basis RA-22-0292, License Amendment Request to Revise Technical Specification 5.5.2, Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies2023-04-0404 April 2023 License Amendment Request to Revise Technical Specification 5.5.2, Containment Leakage Rate Testing Program, for Permanent Extension of Type a and Type C Leak Rate Test Frequencies RA-22-0091, Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements2023-02-16016 February 2023 Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements RA-22-0118, License Amendment Request to Revise Restrictive Technical Specification Surveillance Requirement Frequencies2023-02-0101 February 2023 License Amendment Request to Revise Restrictive Technical Specification Surveillance Requirement Frequencies RA-20-0107, Duke Energy Progress, LLC, and Duke Energy Carolinas, LLC, Application to Revise Technical Specifications to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position2022-01-18018 January 2022 Duke Energy Progress, LLC, and Duke Energy Carolinas, LLC, Application to Revise Technical Specifications to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position RA-21-0005, Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required Inoperable LPSW Pump on a Temporary Basis2021-09-0202 September 2021 Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required Inoperable LPSW Pump on a Temporary Basis ML20237F4352020-09-0404 September 2020 Issuance of Amendments Regarding the Technical Specification Requirements Pertaining to Mode Change Limitations RA-19-0039, License Amendment Request to Revise Technical Specifications to Adopt Two NRC-Approved Generic Technical Specification Changes2020-04-13013 April 2020 License Amendment Request to Revise Technical Specifications to Adopt Two NRC-Approved Generic Technical Specification Changes RA-20-0011, Application for Technical Specifications Change Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process2020-02-0606 February 2020 Application for Technical Specifications Change Regarding Mode Change Limitations Using the Consolidated Line Item Improvement Process RA-19-0006, License Amendment Application to Relocate Technical Specification Unit/Facility Staff Qualification ANSI N18.1-1971, ANSI/ANS-3.1-1978 and ANSI/ANS-3.1-1981 Requirements to the Duke Energy Corporation Quality Assurance Program Description2019-07-0808 July 2019 License Amendment Application to Relocate Technical Specification Unit/Facility Staff Qualification ANSI N18.1-1971, ANSI/ANS-3.1-1978 and ANSI/ANS-3.1-1981 Requirements to the Duke Energy Corporation Quality Assurance Program Description RA-18-0282, Technical Specification Bases Changes2019-06-26026 June 2019 Technical Specification Bases Changes RA-18-0281, Technical Specification Bases Changes2019-06-25025 June 2019 Technical Specification Bases Changes RA-18-0023, License Amendment Request (2017-05) to Add a Surveillance Requirement to Technical Specification 3.8.1, AC Sources2018-05-17017 May 2018 License Amendment Request (2017-05) to Add a Surveillance Requirement to Technical Specification 3.8.1, AC Sources ONS-2018-013, Technical Specification Bases Changes2018-02-22022 February 2018 Technical Specification Bases Changes RA-17-0005, Application to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Inservice Testing Program Removal & Clarify SR Usage Rule Application to Section 5.5 Testing2017-11-0707 November 2017 Application to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Inservice Testing Program Removal & Clarify SR Usage Rule Application to Section 5.5 Testing ONS-2017-050, Technical Specification Bases Change 2017-042017-07-21021 July 2017 Technical Specification Bases Change 2017-04 ONS-2017-043, Technical Specification Bases Change 2017-012017-07-20020 July 2017 Technical Specification Bases Change 2017-01 ONS-2017-052, Technical Specification Bases Change 2017-032017-07-20020 July 2017 Technical Specification Bases Change 2017-03 ML17095A5302017-03-30030 March 2017 Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process; License Amendment Request No. 2015-03 ONS-2017-019, Technical Specification Bases Change 2015-092017-02-23023 February 2017 Technical Specification Bases Change 2015-09 ONS-2016-082, Technical Specification Bases Change for TS Bases 3.4.16, Steam Generator Tube Integrity2016-09-0808 September 2016 Technical Specification Bases Change for TS Bases 3.4.16, Steam Generator Tube Integrity ONS-2016-071, Duke Energy Carolinas, LLC - Oconee Nuclear Station, Docket Numbers 50-269, 50-270, and 50-287 - Technical Specification (TS) Bases Change2016-08-0404 August 2016 Duke Energy Carolinas, LLC - Oconee Nuclear Station, Docket Numbers 50-269, 50-270, and 50-287 - Technical Specification (TS) Bases Change ONS-2016-059, Technical Specification Bases Changes2016-07-11011 July 2016 Technical Specification Bases Changes RA-16-0007, Duke Energy Carolinas, LLC, Application to Revise TS to Adopt TSTF-427, Revision 2, Allowance for Non Technical Specification Barrier Degradation on Supported System Operability Using the Consolidated Line Item Improvement Process2016-06-23023 June 2016 Duke Energy Carolinas, LLC, Application to Revise TS to Adopt TSTF-427, Revision 2, Allowance for Non Technical Specification Barrier Degradation on Supported System Operability Using the Consolidated Line Item Improvement Process ONS-2016-049, Technical Specification Bases Change2016-06-0606 June 2016 Technical Specification Bases Change ONS-2016-029, Technical Specification (TS) Bases Change2016-03-29029 March 2016 Technical Specification (TS) Bases Change ONS-2016-009, Technical Specification (TS) Bases Change2016-02-0909 February 2016 Technical Specification (TS) Bases Change ML16028A1912016-01-20020 January 2016 Technical Specification Base Change ONS-2015-106, Technical Specification (TS) Bases Change2015-10-26026 October 2015 Technical Specification (TS) Bases Change ML15175A4472015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 5 of 6 ML15175A4482015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 6 of 6 ML15175A4452015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 4 of 6 ML15175A4422015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 3 of 6 RA-15-0006, Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 2 of 62015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 2 of 6 ONS-2015-069, Technical Specification (TS) Bases Change2015-06-23023 June 2015 Technical Specification (TS) Bases Change ONS-2015-047, License Amendment Request (LAR) to Add High Flux Trip for 3 Reactor Coolant Pump Operation, License Amendment Request No. 2014-052015-05-19019 May 2015 License Amendment Request (LAR) to Add High Flux Trip for 3 Reactor Coolant Pump Operation, License Amendment Request No. 2014-05 ONS-2015-057, Technical Specification (TS) Bases Changes2015-05-18018 May 2015 Technical Specification (TS) Bases Changes ONS-2015-033, Technical Specification (TS) Bases Change2015-03-18018 March 2015 Technical Specification (TS) Bases Change ONS-2015-006, Technical Specification (TS) Bases Change2015-01-29029 January 2015 Technical Specification (TS) Bases Change ONS-2014-145, Submittal of Technical Specification Bases Change2014-11-20020 November 2014 Submittal of Technical Specification Bases Change ONS-2014-103, Technical Specification (TS) Bases Change2014-07-23023 July 2014 Technical Specification (TS) Bases Change RA-14-0001, License Amendment Request to Reflect Changes to Organization, Unit Staff Responsibility, Unit Staff Qualifications, Programs and Manuals, and High Radiation Area2014-07-21021 July 2014 License Amendment Request to Reflect Changes to Organization, Unit Staff Responsibility, Unit Staff Qualifications, Programs and Manuals, and High Radiation Area ONS-2014-093, Technical Specification (TS) Bases Change2014-07-10010 July 2014 Technical Specification (TS) Bases Change ONS-2014-079, Submittal of Technical Specification (TS) Bases Change2014-06-0303 June 2014 Submittal of Technical Specification (TS) Bases Change ONS-2014-064, Technical Specification (TS) Bases Change2014-05-12012 May 2014 Technical Specification (TS) Bases Change ONS-2014-031, Technical Specification (TS) Bases Change2014-03-0404 March 2014 Technical Specification (TS) Bases Change ONS-2014-012, Submittal of Technical Specification Bases Change2014-02-0303 February 2014 Submittal of Technical Specification Bases Change ML13357A6742014-01-0808 January 2014 Issuance of Amendments Regarding the Temporary Technical Specification Change to Extend the Completion Time for an Inoperable Keowee Hydro Unit (TAC ME9021, ME9022, and ME9023) ONS-2013-006, Technical Specification Bases Change2013-11-13013 November 2013 Technical Specification Bases Change ML13234A3362013-08-0808 August 2013 Technical Specification Bases Change 2024-07-29
[Table view] Category:Bases Change
MONTHYEARRA-24-0092, Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required LPSW Pump Inoperable on a One-Time Basis2024-07-29029 July 2024 Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required LPSW Pump Inoperable on a One-Time Basis RA-22-0091, Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements2023-02-16016 February 2023 Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements RA-22-0118, License Amendment Request to Revise Restrictive Technical Specification Surveillance Requirement Frequencies2023-02-0101 February 2023 License Amendment Request to Revise Restrictive Technical Specification Surveillance Requirement Frequencies RA-20-0107, Duke Energy Progress, LLC, and Duke Energy Carolinas, LLC, Application to Revise Technical Specifications to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position2022-01-18018 January 2022 Duke Energy Progress, LLC, and Duke Energy Carolinas, LLC, Application to Revise Technical Specifications to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position RA-21-0005, Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required Inoperable LPSW Pump on a Temporary Basis2021-09-0202 September 2021 Application to Revise Technical Specification 3.7.7, Low Pressure Service Water (LPSW) System, to Extend the Completion Time for One Required Inoperable LPSW Pump on a Temporary Basis RA-19-0039, License Amendment Request to Revise Technical Specifications to Adopt Two NRC-Approved Generic Technical Specification Changes2020-04-13013 April 2020 License Amendment Request to Revise Technical Specifications to Adopt Two NRC-Approved Generic Technical Specification Changes RA-18-0282, Technical Specification Bases Changes2019-06-26026 June 2019 Technical Specification Bases Changes RA-18-0281, Technical Specification Bases Changes2019-06-25025 June 2019 Technical Specification Bases Changes RA-18-0023, License Amendment Request (2017-05) to Add a Surveillance Requirement to Technical Specification 3.8.1, AC Sources2018-05-17017 May 2018 License Amendment Request (2017-05) to Add a Surveillance Requirement to Technical Specification 3.8.1, AC Sources ONS-2018-013, Technical Specification Bases Changes2018-02-22022 February 2018 Technical Specification Bases Changes ONS-2017-050, Technical Specification Bases Change 2017-042017-07-21021 July 2017 Technical Specification Bases Change 2017-04 ONS-2017-052, Technical Specification Bases Change 2017-032017-07-20020 July 2017 Technical Specification Bases Change 2017-03 ONS-2017-043, Technical Specification Bases Change 2017-012017-07-20020 July 2017 Technical Specification Bases Change 2017-01 ML17095A5302017-03-30030 March 2017 Application to Revise Technical Specifications Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process; License Amendment Request No. 2015-03 ONS-2017-019, Technical Specification Bases Change 2015-092017-02-23023 February 2017 Technical Specification Bases Change 2015-09 ONS-2016-082, Technical Specification Bases Change for TS Bases 3.4.16, Steam Generator Tube Integrity2016-09-0808 September 2016 Technical Specification Bases Change for TS Bases 3.4.16, Steam Generator Tube Integrity ONS-2016-071, Duke Energy Carolinas, LLC - Oconee Nuclear Station, Docket Numbers 50-269, 50-270, and 50-287 - Technical Specification (TS) Bases Change2016-08-0404 August 2016 Duke Energy Carolinas, LLC - Oconee Nuclear Station, Docket Numbers 50-269, 50-270, and 50-287 - Technical Specification (TS) Bases Change ONS-2016-059, Technical Specification Bases Changes2016-07-11011 July 2016 Technical Specification Bases Changes RA-16-0007, Duke Energy Carolinas, LLC, Application to Revise TS to Adopt TSTF-427, Revision 2, Allowance for Non Technical Specification Barrier Degradation on Supported System Operability Using the Consolidated Line Item Improvement Process2016-06-23023 June 2016 Duke Energy Carolinas, LLC, Application to Revise TS to Adopt TSTF-427, Revision 2, Allowance for Non Technical Specification Barrier Degradation on Supported System Operability Using the Consolidated Line Item Improvement Process ONS-2016-049, Technical Specification Bases Change2016-06-0606 June 2016 Technical Specification Bases Change ONS-2016-029, Technical Specification (TS) Bases Change2016-03-29029 March 2016 Technical Specification (TS) Bases Change ONS-2016-009, Technical Specification (TS) Bases Change2016-02-0909 February 2016 Technical Specification (TS) Bases Change ML16028A1912016-01-20020 January 2016 Technical Specification Base Change ONS-2015-106, Technical Specification (TS) Bases Change2015-10-26026 October 2015 Technical Specification (TS) Bases Change ML15175A4482015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 6 of 6 ML15175A4472015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 5 of 6 ML15175A4452015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 4 of 6 ML15175A4422015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 3 of 6 RA-15-0006, Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 2 of 62015-06-24024 June 2015 Application to Revise Technical Specifications to Adopt TSTF-523, Revision 2, Generic Letter 2008-01, Managing Gas Accumulation, Using the Consolidated Line Item Improvement Process. Part 2 of 6 ONS-2015-069, Technical Specification (TS) Bases Change2015-06-23023 June 2015 Technical Specification (TS) Bases Change ONS-2015-047, License Amendment Request (LAR) to Add High Flux Trip for 3 Reactor Coolant Pump Operation, License Amendment Request No. 2014-052015-05-19019 May 2015 License Amendment Request (LAR) to Add High Flux Trip for 3 Reactor Coolant Pump Operation, License Amendment Request No. 2014-05 ONS-2015-057, Technical Specification (TS) Bases Changes2015-05-18018 May 2015 Technical Specification (TS) Bases Changes ONS-2015-033, Technical Specification (TS) Bases Change2015-03-18018 March 2015 Technical Specification (TS) Bases Change ONS-2015-006, Technical Specification (TS) Bases Change2015-01-29029 January 2015 Technical Specification (TS) Bases Change ONS-2014-145, Submittal of Technical Specification Bases Change2014-11-20020 November 2014 Submittal of Technical Specification Bases Change ONS-2014-103, Technical Specification (TS) Bases Change2014-07-23023 July 2014 Technical Specification (TS) Bases Change RA-14-0001, License Amendment Request to Reflect Changes to Organization, Unit Staff Responsibility, Unit Staff Qualifications, Programs and Manuals, and High Radiation Area2014-07-21021 July 2014 License Amendment Request to Reflect Changes to Organization, Unit Staff Responsibility, Unit Staff Qualifications, Programs and Manuals, and High Radiation Area ONS-2014-093, Technical Specification (TS) Bases Change2014-07-10010 July 2014 Technical Specification (TS) Bases Change ONS-2014-079, Submittal of Technical Specification (TS) Bases Change2014-06-0303 June 2014 Submittal of Technical Specification (TS) Bases Change ONS-2014-064, Technical Specification (TS) Bases Change2014-05-12012 May 2014 Technical Specification (TS) Bases Change ONS-2014-031, Technical Specification (TS) Bases Change2014-03-0404 March 2014 Technical Specification (TS) Bases Change ONS-2014-012, Submittal of Technical Specification Bases Change2014-02-0303 February 2014 Submittal of Technical Specification Bases Change ONS-2013-006, Technical Specification Bases Change2013-11-13013 November 2013 Technical Specification Bases Change ML13234A3362013-08-0808 August 2013 Technical Specification Bases Change ML13211A2832013-07-24024 July 2013 Technical Specification Bases (Tsb) Change ML12333A3152012-11-27027 November 2012 Technical Specification Bases (Tsb) Changes ML12319A4792012-11-12012 November 2012 Technical Specification Bases (Tsb) Changes ML12307A2192012-10-30030 October 2012 License Amendment Request for Approval to Operate a Reverse Osmosis System to Remove Silica from the Borated Water Storage Tanks and Spent Fuel Pools During Unit Operation and Associated Proposed Tech Specs and Bases.. ML12310A3822012-10-29029 October 2012 Technical Specification Bases (Tsb) Changes ML12243A4012012-08-29029 August 2012 Technical Specification Bases (Tsb) Change 2024-07-29
[Table view] |
Text
Duke Duker T.PRESTON GILLESPIE, JR.
Vice President Pok=nergy Oconee Nuclear Station Duke Energy ONO VP / 7800 Rochester Hwy.
Seneca, SC 29672 864-873-4478 864-873-4208 fax T.Gillespie@duke-energy.com April 24, 2012 U. S. Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk
Subject:
Duke Energy Carolinas, LLC Oconee Nuclear Station Docket Numbers 50-269, 50-270, and 50-287 Technical Specification Bases (TSB) Changes Pursuant to Technical Specification 5.5.15, Technical Specifications (TS) Bases Control Program, please find attached the latest change to the Oconee Technical Specification Bases.
On April 10, 2012, Station Management approved a revision to TSB 3.3.20, EPSL CT-5 Degraded Grid Voltage Protection (DGVP) to reflect the correct required voltage for operation of emergency equipment with each Unit's auxiliary power aligned to Central Switchyard via CT-5.
Attachment 1 contains the new TSB pages, Attachment 2 contains the marked up version of the TSB pages.
If any additional information is needed, please contact Kent Alter at 864-873-3255.
Sincerely, T.Preston Gillespie, Jr.
Vice President Oconee Nuclear Station www. duke-energy. corn
U. S. Nuclear Regulatory Commission April 24, 2012 Page 2 cc: John Boska Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 8 C2 Washington, DC 20555 Victor McCree Regional Administrator, Region II U.S. Nuclear Regulatory Commission Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Ga. 30303-1257 Andy Sabisch Senior Resident Inspector Oconee Nuclear Station Susan E. Jenkins, Manager Radioactive & Infectious Waste Management SC Dept. of Health and Environmental Control 2600 Bull St.
Columbia, SC 29201 TSB revision
EPSL CT-5 DGVP B 3.3.20 B 3.3 INSTRUMENTATION B 3.3.20 Emergency Power Switching Logic (EPSL) CT-5 Degraded Grid Voltage Protection (DGVP)
BASES BACKGROUND Two levels of protection are provided for the standby buses to assure that degradation of voltage from the 100 kV transmission system does not adversely impact the function of safety related systems and components.
The first level of protection is provided by the EPSL CT-5 Degraded Grid Protection System. The second level of protection is provided by undervoltage relaying on the standby buses (reference LCO 3.3.18, "EPSL Voltage Sensing Circuits") which protects from loss of voltage.
Three undervoltage sensing relays provide common input to two channels of actuating logic. In addition to the three phase undervoltage sensing relays, each channel includes one time-delay relay, one auxiliary relay, and one associated single phase undervoltage sensing relay. Each channel trip signal passes through a selector switch, which either allows or inhibits the trip signal, to actuate one trip coil in each SL breaker. Inoperability of any voltage sensing channel reduces the logic for the voltage sensing function to a two-out-of-two. Loss of two or more voltage sensing relays results in inoperability of both channels of actuation logic.
APPLICABLE The EPSL CT-5 Degraded Grid Voltage Protection function is required to SAFETY ANALYSES ensure adequate voltage is available during an ES actuation concurrent with a loss of offsite power or degraded voltage from the 230 kV switchyard when ES loads are supplied by the standby buses (Ref.1). The minimum voltage that will ensure proper operation of loads during ES actuation is 3858 V as documented in site calculations.
This system is only required to be OPERABLE when the unit is in MODES 1, 2, 3, and 4 and the standby buses are energized without being electrically separated from the grid and offsite loads. System design is to provide protection for ES components caused by voltage droop due to inrush as the unit connects to the standby buses. The system is not a substitute for the dedicated line from Lee Gas Turbines.
The Lee Feeder breakers (SL) have no automatic close functions.
However, this system does provide additional flexibility for the Station electrical system and operators in available power source options.
The EPSL CT-5 Degraded Grid Voltage Protection satisfies Criterion 3 of 10 CFR 50.36 (Ref. 2).
OCONEE UNITS 1, 2, & 3 B 3.3.20-1 BASES REVISION DATED 04/11/12 I
EPSL CT-5 DGVP B 3.3.20 BASES (continued)
LCO Three CT-5 degraded grid voltage sensing relay channels are required to be OPERABLE. Failure of one channel reduces the reliability of the function. The requirement for three channels to be OPERABLE ensures that two channels will remain OPERABLE if a failure has occurred in one channel. The remaining voltage sensing channels can perform the safety function.
Two channels of the CT-5 Degraded Grid Voltage Protection Actuation Logic function are required to be OPERABLE. The requirement for two channels to be OPERABLE ensures that one channel will remain OPERABLE if a failure has occurred in one channel. The remaining channel can perform the safety function.
APPLICABILITY The CT-5 DGPS functions are required to be OPERABLE in MODES 1, 2, 3, and 4 when standby buses are energized without being electrically separated from the grid and offsite loads to ensure adequate voltage protection should a unit be transferred to the standby bus during an event requiring an ES actuation.
The EPSL CT-5 DGVP functions are not required to be OPERABLE in MODES 5 and 6 since more time is available for the operator to respond to a loss of power event.
ACTIONS A. 1 If one CT-5 DGVP voltage sensing relay channel. is inoperable, the channel must be placed in trip within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. Tripping the affected channel places the function in a one-out-of-two configuration. Operation in this configuration may continue indefinitely since the DGVP function is capable of performing its DGVP function in the presence of any single random failure. With one channel inoperable, the remaining voltage sensing channels are capable of providing the DGVP function. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> completion time is based on engineering judgement taking into consideration the infrequency of actual grid system voltage degradation, and the probability of an event requiring an ES actuation.
B. 1 If one CT-5 DGVP actuation logic channel is inoperable, the actuation logic channel must be restored to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. With one actuation logic channel inoperable, the remaining actuation logic channel is OCONEE UNITS 1, 2, & 3 B 3.3.20-2 BASES REVISION DATED 04/11/12 I
EPSL CT-5 DGVP B 3.3.20 BASES ACTIONS B.1 (continued) capable of providing the CT-5 DGVP function. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> completion time is based on engineering judgement taking into consideration the infrequency of actual grid system voltage degradation and the probability of an event requiring an ES actuation.
C.1 and C.2 If two or more voltage sensing relay channels or two actuation logic channels are inoperable, automatic protection from degraded grid voltage for the standby buses powered from the 100 kV transmission system is not available. Continued operation is allowed provided that the SL breakers are opened within one hour.
Additionally, with the Required Action and associated Completion Time of Condition A or B not met, the SL breakers must be opened within one hour.
This arrangement provides a high degree of reliability for the emergency power system. The one hour Completion Time is based on engineering judgement taking into consideration the infrequency of actual grid system voltage degradation and the probability of an event requiring an ES actuation.
SURVEILLANCE SR 3.3.20.1 REQUIREMENTS A CHANNEL FUNCTIONAL TEST is performed on each CT-5 DGVP voltage sensing channel and each CT-5 DGVP actuation logic channel to ensure the entire channel will perform its intended function. Any setpoint adjustments shall be consistent with the assumptions of the setpoint analysis. The Frequency of 18 months is based on engineering judgment and operating experience that determined testing on an 18 month interval provides reasonable assurance that the circuitry is available to perform its safety function.
SR 3.3.20.2 A CHANNEL CALIBRATION is a complete check of the instrument channel, including the sensor. The test verifies that the channel responds to the measured parameter within the necessary range and accuracy.
CHANNEL CALIBRATION leaves the channel adjusted to account for instrument drift to ensure that the instrument channel remains operational OCONEE UNITS 1, 2, & 3 B 3.3.20-3 BASES REVISION DATED 04/11/12 I
EPSL CT-5 DGVP B 3.3.20 BASES SURVEILLANCE SR 3.3.20.2 (continued)
REQUIREMENTS between successive tests. CHANNEL CALIBRATION shall find that measurement errors and bistable setpoint errors are within the assumptions of the setpoint analysis. CHANNEL CALIBRATIONS must be performed consistent with the assumptions of the setpoint analysis.
The Frequency is justified by the assumption of an 18 month calibration interval in the determination of the magnitude of equipment drift in the setpoint analysis.
REFERENCES 1. UFSAR, Chapter 8.
- 2. 10 CFR 50.36.
OCONEE UNITS 1, 2, & 3 B 3.3.20-4 BASES REVISION DATED 04/11/12 I
Attachment 2 Markup of current TSB
EPSL CT-5 DGVP B 3.3.20 B 3.3 INSTRUMENTATION B 3.3.20 Emergency Power Switching Logic (EPSL) CT-5 Degraded Grid Voltage Protection (DGVP)
BASES BACKGROUND Two levels of protection are provided for the standby buses to assure that degradation of voltage from the 100 kV transmission system does not adversely impact the function of safety related systems and components.
The first level of protection is provided by the EPSL CT-5 Degraded Grid Protection System. The second level of protection is provided by undervoltage relaying on the standby buses (reference LCO 3.3.18, "EPSL Voltage Sensing Circuits") which protects from loss of voltage.
Three undervoltage sensing relays provide common input to two channels of actuating logic. In addition to the three phase undervoltage sensing relays, each channel includes one time-delay relay, one auxiliary relay, and one associated single phase undervoltage sensing relay. Each channel trip signal passes through a selector switch, which either allows or inhibits the trip signal, to actuate one trip coil in each SL breaker. Inoperability of any voltage sensing channel reduces the logic for the voltage sensing function to a two-out-of-two. Loss of two or more voltage sensing relays results in inoperability of both channels of actuation logic.
APPLICABLE The EPSL CT-5 Degraded Grid Voltage Protection function is required to SAFETY ANALYSES ensure adequate voltage is available during an ES actution cpcurre .
wit offsite ower ide e he 2'kV swI~tchyard
- l m,4.
,04.1 qiet beOEAL o
w en ES loads e su ed by the standby buses (Ref. 1). .Seeed a'
. he minimum voltage that will ensure proper operation of loads during ES actuation* m 3'25ffle
\
This systemýis on~ly required to ýbe OPE2RABLE wh~eeýu 1, 2, 3, and 4 and the standby buses are energized without being electrically separated from the grid and offsite loads. System design is to provide protection for ES components caused by voltage droop due to inrush as the unit connects to the standby buses. The system is not a substitute for the dedicated line from Lee Gas Turbines.
The Lee Feeder breakers (SL) have no automatic close functions.
However, this system does provide additional flexibility for the Station electrical system and operators in available power source options.
The EPSL CT-5 Degraded Grid Voltage Protection satisfies Criterion 3 of 10 CFR 50.36 (Ref. 2).
6?A$SE 3EcV 15-o 104 AIED 4CX OCONEE UNITS 1, 2, & 3 3.3.204, tened,9,e1 PNes. 3 O8613O&
EPSL CT-5 DGVP B 3.3.20 BASES (continued)
LCO Three CT-5 degraded grid voltage sensing relay channels are required to be OPERABLE. Failure of one channel reduces the reliability of the function. The requirement for three channels to be OPERABLE ensures that two channels will remain OPERABLE if a failure has occurred in one channel. The remaining voltage sensing channels can perform the safety function.
Two channels of the CT-5 Degraded Grid Voltage Protection Actuation Logic function are required to be OPERABLE. The requirement for two channels to be OPERABLE ensures that one channel will remain OPERABLE if a failure has occurred in one channel. The remaining channel can perform the safety function.
APPLICABILITY The CT-5 DGPS functions are required to be OPERABLE in MODES 1, 2, 3, and 4 whe r ized without being electrically separated fr *nto ensure a ate voltage protection should a unit be tra sf rredsto t bus during qn*vent requiring an ES actuation. +& C and Wk loads The EPSL CT-5 DGVP functions are not required to be OPERABLE in MODES 5 and 6 since more time is available for the operator to respond to a loss of power event.
ACTIONS A.1 If one CT-5 DGVP voltage sensing relay channel is inoperable, the channel must be placed in trip within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. Tripping the affected channel places the function in a one-out-of-two configuration. Operation in this configuration may continue indefinitely since the DGVP function is capable of performing its DGVP function in the presence of any single random failure. With one channel inoperable, the remaining voltage sensing channels are capable of providing the DGVP function. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> completion time is based on engineering judgement taking into consideration the infrequency of actual grid system voltage degradation, and the probability of an event requiring an ES actuation.
B. 1 If one CT-5 DGVP actuation logic channel is inoperable, the actuation logic channel must be restored to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. With one actuation logic channel inoperable, the remaining actuation logic channel is vISfO,'J JQq~C)qX3(
OCONEE UNITS 1, 2, & 3 B 3.3.20-2 Nes. ~9O, aee,.&-~e~