LER-2011-002, Regarding Failure of an RPS Trip Unit
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function
2852011002R01 - NRC Website

text

Omaha Public Power District 444 South 16" 1Street Mall Omaha, NE 68102-2247 July 27, 2011 LlC-11-0080 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001

Reference:

Docket No. 50-285

Subject:

Licensee Event Report 2011-002, Revision 1, for the Fort Calhoun Station Please find attached Licensee Event Report 2011-002, Revision 1, dated, July 27,2011. This report is being submitted pursuant to 10CFR50.73(a)(2)(i)(B). If you should have any questions, please contact me.

JAR/rda Attachment c:

E. E. Collins, Jr., NRC Regional Administrator, Region IV L. E. Wilkins, NRC Project Manager J. C. Kirkland, NRC Senior Resident Inspector I NPO Records Center Employment with Equal Opportunity

NRC FORM 366 (10-2010)

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digits/characters for each block)

APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2013

, the NRC may not conduct or sp onsor, and a person is not required to respond to, th e

information collection.

1. FACILITY NAME Fort Calhoun Station
2. DOCKET NUMBER 05000285
3. PAGE 1 OF 4
4. TITLE Failure of an RPS Trip Unit
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO.

MONTH DAY YEAR FACILITY NAME DOCKET NUMBER 05000 2

4 2011 2011 - 002 -

1 7

27 2011 FACILITY NAME DOCKET NUMBER 05000

9. OPERATING MODE 1
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply) 20.2201(b) 20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii) 20.2201(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(c)(1)(i)(A) 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(c)(1)(ii)(A) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x) 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71(a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(B) 73.71(a)(5) 20.2203(a)(2)(v) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C)

OTHER 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D)

Specify in Abstract below or in LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET CONCLUSION The root causes are determined to be:

1. Management has not effectively enforced expectations of rigorous troubleshooting standards for equipment important to safety and/or operation.
2. The standards for implementation of the Corrective Action Program have been ineffective in identifying and driving resolution of repeat and less-significant failures of equipment important to safety and/or operation.

There are an additional six contributing causes identified as well.

CORRECTIVE ACTIONS

The wire between terminals T-74 and relay contact terminal 12 was replaced. Additional corrective actions are identified in the condition reporting system. Corrective actions include: training on the correct use of Operating Experience (OE) in work orders; observations for each maintenance discipline of routine maintenance activities to ensure/assess that personnel are rigorously following procedures and work order instructions will be performed and; System Health Reports to document equipment failures for the period and repeat equipment failures within the past five years will be revised.

Additionally, trending of these indicators will be performed.

SAFETY SIGNIFICANCE

The overall effect on the one SG Low Pressure trip setpoint was less than 10 pounds per square inch (psi) at 39 millivolts and not more than 30 psi at the highest ever recorded difference of 120 millivolts recorded on May 14, 2009.

Even with a failed instrument channel, the margin of safety as defined in the basis of the FCS TS was maintained. The plant was able to trip on Low SG pressure in, at least, a two out of two reactor protection logic. Even with these RPS channels inoperable, the single failure criteria for the RPS system was met. Therefore the health and safety of the public was not impacted by this RPS failure.

SAFETY SYSTEM FUNCTIONAL FAILURE This event does not result in a safety system functional failure in accordance with NEI-99-02.

PREVIOUS EVENTS:

No previous LER has documented problems with this RPS circuitry.