Submittal Report on Changes to the University of Florida Training Reactor (Uftr) Final Safety Analysis Report (FSAR) for the Digital Reactor Protection System Upgrade
ML103230019
Person / Time
Site: 05000083
Issue date: 11/16/2010
From: Hintenlang D
Univ of Florida
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML103230019 (32)


Text

MM UNIVERSITY of College of Engineering Department of Nuclear & Radiological Engineering University of Florida Training Reactor 202 Nuclear Science Bldg.

PO Box 118300 Gainesville, FL 32611-8300 352-392-1401 352-392-3380 Fax dhinten@ufl.edu November 16, 2010 Document Control Desk U.S, Nuclear Regulatory Commission Washington, DC 20555 Attn: Mr. Duane Hardesty De'r Mr. Hardesty,

Subject:

Submittal Report on changes to the University of Florida Training Reactor (UFTR) Final Safety Analysis Report (FSAR) for the Digital Reactor Protection System Upgrade

.-Please find enclosed the Submittal Report on changes to the UFTR's FSAR for the Digital Reactor Protection System Upgrade. Note that the following Chapters will be revised by the UFTR Management:

Chapter 8. Electrical Power System Chapter 12. Conduct of Operation o

12.2 Procedures; o

12.3 Operator Training and Requalification o

12.4 Emergency Plan o

12.5 Physical Plan If you need further information, please do not hesitate to contact me at dhinten@ufl.edu or (352) 392-1401.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on November 16, 2010.

Sincerely, David Hintenlang, PhD Director of UFTR Interim Chair of NRE SDIANA L. DAMPIER S

Notary Public - State Of Florida MY Comm. Expires Jul 20, 2013 Commission # DO 894207 Bonded Throughi National Notary Assn.7 Cc Jack Donohue, NRC Alireza Haghighat, UF UFTR - NRC file The Foundation for The Gator Nation An Equal Opportunity Institution 0O

SUBMITTAL REPORT To Cover Analyses of University of Florida Training Reactor (UFTR)

Digital Reactor Protection System Upgrade Submitted by Alireza Haghighat, Ph.D.

Prof. of the Nuclear and Radiological Engineering Department University of Florida Training Reactor Facility Nuclear and Radiological Engineering Department College of Engineering University of Florida Gainesville, Florida First Version November 2010 I

First Version Prepared by First Version Reviewed by UF Faculty Contributors Alireza Haghighat Gabriel Ghita Lionel Bates (AREVA NP)

David Hintenlang Gabriel Ghita Alireza Haghighat Glenn Sjoden Noteihat, unless specified otherwise, all contributors are part of the University of Florida

,Department of Nuclear and Radiological Engineering.

2

Table of Contents TABLE OF CONTENTS 3

LIST OF FIGURES 5

LIST OF TABLES 6

SUMMARY

7

1. GENERAL DESCRIPTION OF THE FACILITY 8

1.1 Introduction 8

1.2 Summary and Conclusions of Principal Safety Considerations 9

1.3 Summary of Reactor Facility Changes 10 1.4 Summary of Operating License, Technical Specifications, and Procedural Changes 10 1.5 Comparison with Similar Facilities Already Converted 10

2. SITE CHARACTERISTICS 11
3. DESIGN OF STRUCTURES, SYSTEMS, AND COMPONENTS 12 3.1 Design Criteria 12 3.1.1 Structural Design 12 3.1.2 Overall Requirements 12 3.1.3 Protection of Multiple Fission Barriers 12 3.1.4 Protection and Reactivity Control System 12 3.1.5 Fluid Systems 12 3.1.6 Confinement Design Basis 12 3.1.7 Fuel Radioactivity Control 13 3.2 Meteorological and Water Damage 13 3.3 Seismic Damage 13 3.4 System and Components 13
4. REACTOR DESCRIPTION 14 4.1 Reactor Facility 14 4.2 Reactor Core 14 3
6. ENGINEERING SAFETY FEATURES 16
7. INSTRUMENTATION AND CONTROL 17
8. ELECTRICAL POWER SYSTEM 23
9. AUXILIARY SYSTEM 24
10. EXPERIMENTAL FACILITY AND UTILIZATION 25
11. RADIATION PROTECTION AND RADIOACTIVE WASTE MANAGEMENT 26
12. CONDUCT OF OPERATION 27 12.1 Organization and Staff Qualification 27 12.2 Procedures 27 12.3 Operator Training and Re-qualification 27 12.4 Emergency Plan 27 12.5 Physical Security 27 12.6 Reactor Reload and Startup Plan 27
13. ACCIDENT ANALYSIS 28
14. TECHNICAL SPECIFICATIONS 29
15. OTHER LICENSE CONSIDERATIONS 30 REFERENCES 31 4

List of Figures Figure 1 The UFTR Protection System.....................................................................................

8 Figure 2 Proposed TX S System................................................................................................

.17 Figure 3 TXS System Network Diagram.................................................................................

19 Figure 4 UFTR TXS Cabinet 1 (Including AQP, NI signal processing)..................................

20 Figure 5 UFTR TXS Cabinet 2 (Including SU, GW, MSI, &QDS).........................................

21 5

List of Tables Table 1 Comparison of the proposed digital and existing analog systems................................

9 Table 2 List of signals within the proposed one-train TXS system (parameter, device, type of signal & m onitoring region)......................................................................................................

18 Table 3 Proposed Diverse Monitoring of different regions of the UFTR...............................

18 Table 4 List of the TS sections affected by the UFTR changes..............................................

29 6

Summary This report contains the results of design and safety analyses performed by the University of Florida Nuclear and Radiological Engineering Department (NRE) for upgrade of the analog control/protection system of the University of Florida Training Reactor (UFTR) to two independent digital systems including the TXS Protection System and T-3000 control system.

The new digital systems maintain or improve availability, reliability, safety, and efficiency of the UFTR. This will be accomplished while minimizing operations and maintenance costs. The systems will allow the UFTR to take advantage of the on-line monitoring, self testing, self diagnostics, fault tolerance, information processing, improved human-system interfaces, and higher accuracy capabilities of the new technology.

This study investigates the performance and safety margins of the proposed digital system under nominal and accident conditions. It identifies any necessary changes to the UFTR Final Safety Analysis Report (FSAR, Ref. 1), UFTR Conversion from HEU to LEU fuel (Ref. 2), and UFTR Technical Specifications (TS, Ref. 3).

7

1. General Description of the Facility 1.1 Introduction This section provides an overview of the changes to the physical, nuclear and operational characteristics of the facility required by the digital system upgrade of the UFTR.

The UFTR digital system is comprised of a protection system and control system. The protection system is comprised of three blocks as shown below Nil/Sensors A4RIS TXS T-3000 RTS Figure 1 The UFTR Protection System The above design is developed in order to make sure that the reactor is protected in case the TXS freezes. In this design, the T-3000 is used as an indicator, which informs the operator of the failure of the TXS, and therefore the operator will be able to shutdown the reactor through a diverse manual system, i.e., the Manual Reactor Scram - MRS.

Further detail on the protection system, its design and components are provided in the UFTR-QAI-12 System Description (Ref. 12).

The UFTR control system is the T-3000, which is provided by Siemens Corporation, and has a one-way communication from the TXS system.

In support of the implementation of the new digital protection system application software, a set of documents was prepared related to the Planning and Design Analysis:

1) Planning Documents:

UFTR-QA 1-01 "Software Quality Assurance Plan (SQAP)," (Ref. 4)

UFTR-QA 1-02 "Software Configuration Management Plan (SCMP)," (Ref. 5)

UFTR-QA 1-03 "Software Verification and Validation Plan (SVVP)," (Ref. 6)

UFTR-QA1-05 "Software Safety Plan (SSP)," (Ref. 7)

UFTR-QAl-06.1 "Software Test Plan-SIVAT Plan," (Ref. 8)

UFTR-QA 1-06.2 "Factory Acceptance Test (FAT) Plan," (Ref. 9)

UFTR-QAI-10 "Software Training Plan," (Ref. 10)

UFTR-QAI-1I "Software Review and Audit," (Ref. 11)

UFTR-QA 1-109 "Software Library and Control," (Ref. 19) 8

2) Design Analysis Documents:

UFTR-QAI-12 "System Description," (Ref. 12)

UFTR-QA 1 -14 "Safety System Design Basis," (Ref. 13)

UFTR-QA 1-100 "Functional Requirements Specification," (Ref. 14)

UFTR-QA 1 -101.1 "List of I/Os," (Ref. 15)

UFTR-QA 1-102.3 "ID Coding," (Ref. 16)

UFTR-QA 1-103 "Diversity and Defense-in-Depth (D3) Analysis," (Ref. 17)

UFTR-QA 1 -105 "TELEPERM XS Cyber Security," (Ref. 18) 1.2 Summary and Conclusions of Principal Safety Considerations The new digital protection and control systems provide added redundancy, resulting in improved safety and control of the UFTR. The TXS system protection system consists of both hardware and software that monitors and automatically initiates protective action for the UFTR. The UFTR-QA I-103 "Diversity and Defense in Depth (D3) Analysis" (Ref. 17) shows that the upgraded digital protection system exhibits adequate diversity and defense-in-depth (D3) to address all reasonable vulnerabilities to system failure. Further, safety analysis is presented in the UFTR-QA 1-14 "Safety System Design Basis" document (Ref. 13), which establishes the proposed UFTR protection system design under regulatory bases and specifies the general qualities that the resulting design will satisfy.

In Table 1, we compare the functionality of the proposed UFTR protection system, shown in Fig. 1, as compared to the existing system.

Table 1 Comparison of the proposed digital and existing analog systems Prolk2ct ion S%

Rýýq I I I Ivd I 1,111ý1

[()I I, of" I I I ro I ýc I I I I.,S\\ t,ý I I I V oil it t ýn I I--, an ý I I I Id I CýO I k, I I I ý Lýact, Ir A *ri p As indicated in the above table, for each function of the protection system, i.e. Monitoring and Indicator System (MIS) or Reactor Trip System (RTS), the proposed digital system has two diverse systems, in contrast to one system for the existing analog system. This means that the proposed digital system exceeds the reliability of the existing analog system. For further detail, see the UFTR-QAI -103 "Diversity and Defense in Depth (D3) Analysis" (Ref. 17).

9

1.3 Summary of Reactor Facility Changes The major changes are the new control room and the power supply.

The Power Supply is modified by adding a UPS unit. The change improves the Reactor availability and operability of the protection system. This means the new system improves the system reliability.

The Control Room was moved to the second floor, because of the following reasons:

More space is needed for placement of the TXS and T3000 systems and their auxiliary equipment and displays.

Since, the control room is outside the reactor cell, there is no need for extra radiation protection for the visitors and for the reactor personnel working in this room.

Provides better visibility of the Reactor and easier access for the visitors.

Increase Maintainability Increase Reliability Increase Upgradeability Increase Operator Awareness Increase Operator Effectiveness Storage of Plant History and Trending New console, which provides the following:

o Improved maintainability.

o Enhanced information for the operator.

o Improved human factors and ergonomics.

o Improved reliability and operability o

Improved educational and training capability.

1.4 Summary of Operating License, Technical Specifications, and Procedural Changes The main changes are reflected in the Technical Specifications and some of the operating procedures (OP's). The changes in the Technical Specifications are mainly the addition of new NIs and their impact on the reactor operation. All the OP's, especially those related to the reactor surveillance and operation will be revised and new training documents will be prepared, and new questions will be prepared for examination of operators.

1.5 Comparison with Similar Facilities Already Converted N/A 10

2. Site Characteristics The protection and control systems upgrade does not impact the site characteristics. More details about this topic can be found in Ref. 1.

II

3. Design of Structures, Systems, and Components For this upgrade, we have replaced all the NI's, sensors and radiation monitors Further, the new NI's increase the diversity of monitoring the power, the thermo-couples are replaced with RTD's, which are more reliable, added one more radiation monitor, and improved monitoring the water level in the water storage tank. All the aforementioned changes improve redundancy, diversity, defense-in-depth, and consequently improve the protection and control capabilities, and also availability of the UFTR. The UFTR-QAl-12 "System Description" (Ref. 12) and the UFTR-QA 1-14 "Safety System Design Basis" (Ref. 13) documents elaborate on these changes.

3.1 Design Criteria 3.1.1 Structural Design The Control Room was moved to the second floor (See Section 1.3).

3.1.2 Overall Requirements The protection and control systems upgrade does not impact the overall requirements. More details about this topic can be found in Ref. 1.

3.1.3 Protection of Multiple Fission Barriers The protection and control systems upgrade does not require any changes to this section. More details about this topic can be found in Ref. 1.

3.1.4 Protection and Reactivity Control System The existing UFTR analog protection system includes one train, which is comprised of only two safety channels comprised of Nis. Both safety channels have to be operational, because only one of the channels monitors the low power range, while both cover the high power range in a diverse manner. The proposed new UFTR digital protection system also has one safety train, but this train includes two sets of NI channels and various sensors. It is important to emphasize that the two NI channels monitor the whole power range, therefore introduce new diversity in monitoring the power.

The new digital T-3000 system is used as the reactor control system. This system not only will provide all control functions, but also provides an environment for displaying various reactor parameters and surveillance data during the reactor operations. The final installed system includes utility software for extraction of various reactor physics parameters, which are used for both confirmatory operational data and training.

3.1.5 Fluid Systems The protection and control systems upgrade does not require any changes to this section. More details about this topic can be found in Ref. 1.

3.1.6 Confinement Design Basis The protection and control systems upgrade does not impact the confinement design basis. More details about this topic can be found in Ref. 1.

12

3.1.7 Fuel Radioactivity Control The protection and control systems upgrade does not impact the fuel radioactivity control. More details about this topic can be found in Ref. 1.

3.2 Meteorological and Water Damage The protection and control systems upgrade does not require any changes to this section. More details about this topic can be found in Ref. 1.

3.3 Seismic Damage The protection and control systems upgrade does not require any changes to this section. More details about this topic can be found in Ref. 1.

3.4 System and Components The protection and control systems upgrade does not require any changes to this section. More details about this topic can be found in Ref. 1.

13

4. Reactor DescriDtion 4.1 Reactor Facility The protection and control systems upgrade of the UFTR facility does not change the core configuration and fuel type. All the following aspects of the facility remain unchanged:

Control Blades

  • Neutron Reflector
  • Neutron Source and Holder In-Core Experimental Facilities
  • Reactor Tank and Biological Shielding

" Core Support Structure Functional Design of the Reactivity Control System 4.2 Reactor Core The protection and control systems upgrade does not require any changes to the reactor coolant system. More details about this topic can be found in Ref. I and Ref 2.

14

5. Reactor coolant system The protection and control systems upgrade does not require any changes to the reactor coolant system. More details about this topic can be found in Ref. I and Ref. 2.

15

6. Engineering Safety Features The protection and control systems upgrade does not require any changes to engineering safety features. More details about this topic can be found in Ref. I and Ref. 2.

16

7. Instrumentation and control The proposed TXS protection system includes one safety train of several signals, which are processed by an Acquisition and Processing (AQP) processor, and the processed data are sent to the Main Control Room (MCR) and the Gateway (GW). The GW provides one-way communication with the T-3000 control system. Fig. 2 shows the proposed TXS system.

MCR

[_________

AQP: Acquisition and Processing MSI: Monitoring and Service Interface QDS: Qualified Display System SU: Service Unit GW: Gateway RTS: Reactor Trip System T-00cotl Figure 2 Proposed TXS System Table 2 lists the signals monitored within the above proposed one-train TXS system. Note that the components designated with (*) refer to new Nls or sensors considered for the new system.

17

Table 2 List of signals within the proposed one-train TXS system (parameter, device, type of signal & monitoring region)

Parameter Device AIC DId Monitoring Region Full power range

  • FCa, ICb 2

Core Full power range

Core Temperature

  • Resistive TD 10 core, primary, secondary Flow Rate Flow Rate Monitor 2

2 primary, secondary (FRM)

Water Level Core, storage tank*, shield Monitor* (WLM) tank Area Radiation Level Area Radiationr 4

4 east, north, south, west*

Monitor (ARM)

Core ventilation, stack Fan Availability Fan Monitor (FM) 1 2

d ontilution RPM dilution, stack dilution RPM aFission Chamber; blon Chamber; CAl, Analog Input; DI, Digital Input It is important to note that the new system has two diverse sets of instrumentation for measuring the whole range of power. Further, within the system, for increased reliability, RTD's are used in lieu of thermocouples.

The diverse set of signals within the new safety train shall improve defense-in-depth of the protection system, i.e., TXS, and therefore, the safety and reliability of the UFTR. Table 3 summarizes how different segments of the reactor are monitored by the proposed diverse set of sensors.

Table 3 Pro osed Diverse Monitoring of different regions of the UFTR Sensor/Monitor Core Primary Secondary Reactor Cell Confinement FC+BF3 V

IC V

RTD FRM V

V WLM V

ARM V

FM

/

V 18

The above table indicates that each segment of the reactor is monitored at least by two diverse sensors.

Fig. 3 shows the network diagram corresponding to the above proposed TXS system (Fig. 1.), and Figs. 4 and 5 provide schematics of two cabinets for housing different components of the proposed TXS system.

g I Reactor Trip Channel elli Net,.ork Opfon 0 1 Channel-I MSI -NoVoter P451 AREVA Figure 3 TXS System Network Diagram 19

00, M lop 213 Cl U

N 13 11 2

_Z5 zi) 33 37

-3 v

a,

!z flý

`3 71

Ell L

RC2,:

Al Al C

l OCi Oil 22 DO; r:2 r

C=.,2 DCA oiU 0122 I n 0

Analog Signal Conditioning Nuclear Instrumentation Cabinet Monitoring and Keyswitches Breakers Power Supplies 021 ms2 252

is Cl UC W

13 17 2

5 1

2 23 37

'1 67 el

`4 52 Is5 3

2 I

I I

2*2 222522-0AlREA jp2C~I Figure 4 UFTR TXS Cabinet 1 (Including AQP, NI signal processing) 20

Cabinet Room UFTR Computer Cabinet IJ QDS Backup Keyboard KVM (Keyboard, Video, Mouse)

Fiber Optic Ethernet Connection

[1 I-z Electrical Ethernet Connection FElectrical / Fiber Optic Ethernet HC Converter S

Electrical I Fiber Optic Ethernet Converter SCP3 TXS Communication Processor Comnuter Cabinet Dimensions 37.5" x 23.5" x 72" (DxWxH) 37 U Height Figure 5 UFTR TXS Cabinet 2 (Including SU, GW, MSI, &QDS) 21

Finally, the T-3000 system is used as the reactor control system. This system not only will provide all the necessary control functions, but also provides an environment for displaying various reactor parameters and surveillance data during the reactor operations. The final installed system includes utility software for extraction of various reactor physics parameters, which are used for both confirmatory operational data and training.

Further information about the system are provided in the following documents: UFTR-QA 1-12 "System Description," (Ref. 12), UFTR-QAI-14 "Safety System Design Basis," (Ref. 13), and UFTR-QAI-100 "Functional Requirements Specifications" (Ref. 17).

22

8. Electrical power system The Power Supply is modified and information has to be provided by the reactor management.

The new power supply includes UPS, which contribute to improved operability and reliability of the TXS protection and T-3000 control systems. It also improves the availability of the UFTR.

23

9. Auxiliary system The protection and control systems upgrade does not impact the auxiliary system. More details about this topic can be found in Ref. 1.

24

10. Experimental Facility and utilization The protection and control systems upgrade does not require any changes to experimental facility and utilization of UFTR. More details about this topic can be found in Ref. I and Ref. 2.

25

11. Radiation Protection and Radioactive Waste Management The protection and control systems upgrade does not require any changes to the radiation protection and radioactive waste management of UFTR facility. More details about this topic can be found in Ref. I and Ref. 2.

26

12. Conduct of Operation 12.1 Organization and Staff Qualification The protection and control systems upgrade does not require any changes on the organization and staff qualification. More details about this topic can be found in Ref. 1.

12.2 Procedures This section has to be completed by the UFTR management.

12.3 Operator Training and Re-qualification This section has to be completed by the UFTR management.

12.4 Emergency Plan The change of the location of the control room will require some changes to the Emergency Planning document. This has to be provided by the UFTR management.

12.5 Physical Security This section has to be completed by the UFTR management.

12.6 Reactor Reload and Startup Plan The protection and control systems upgrade does not require any changes to the reactor reload and startup plan. More details about this topic can be found in Ref. 1.

27

13. Accident Analysis The protection and control systems upgrade does not introduce any new accident scenarios. More details about this topic can be found in Ref. I and Ref. 2.

28

14. Technical SDecifications The protection and control systems upgrade, and the changes in NI's and sensors and their operation will require changes in the UFTR TS (Ref. 3). The main sections affected are presented in Table 4:

Table 4 List of the TS sections affected by the UFTR changes Chapter Section Subsection Comment

3. Limiting 3.2 Reactor Control Conditions for and Safety Systems Operations (LCO) 3.4 Radiation 3.4.1 Aerial Radiation Monitoring Systems Monitors and Air and Radioactive Particulate Detectors Effluents 3.10 UFTR Shield Change is only Tank necessary if a new device were to be installed,
4. Surveillance 4.2 Reactor Control Requirements and Safety Systems 29
15. Other License Considerations The necessary documentation of reactor parameters and status will be provided after the installation of the new protection and control systems.

30

References I. Diaz and Vernetson, "Final Safety Analysis Report (FSAR)," 1981 updated to Rev. 11, University of Florida, 1998.

2. A. Haghighat, "Submittal Report to Cover Analyses of UFTR Conversion from HEU to LEU Fuel," Second Version, August 2009.
3. UFTR Technical Specification (TS)
4. UFTR-QA 1-01 "Software Quality Assurance Plan (SQAP)"
5. UFTR-QA 1-02 "Software Configuration Management Plan (SCMP)"
6. UFTR-QA 1-03 "Software Verification and Validation Plan (SVVP)"
7. UFTR-QA 1-05 "Software Safety Plan (SSP)"
8. UFTR-QA 1-06. 1 "Software Test Plan-SIVAT Plan"
9. UFTR-QA 1-06.2 "Factory Acceptance Test (FAT)Plan"
10. UFTR-QAI-10 "Software Training Plan"
11. UFTR-QA 1-11 "Software Review and Audit"
12. UFTR-QA 1-12 "System Description,"
13. UFTR-QAI-14 "Safety System Design Basis"
14. UFTR-QA 1-100 "Functional Requirements Specification"
15. UFTR-QA 1-101.1 "List of I/Os"
16. UFTR-QA I-102.3 "ID Coding"
17. UFTR-QA 1-103 "Diversity and Defense-in-Depth (D3) Analysis"
18. UFTR-QA 1-105 "TELEPERM XS Cyber Security"
19. UFTR-QA I - 109 "Software Library and Control" 31